Data Sheet
DPM1000
Power clamp
DESCRIPTION
The new Megger DPM1000 Power Clamp meter combines
the functionality of power meter, harmonics meter and
data logger in one easy to use package. The design meets
the requirements of BSEN 61010-1 CAT IV 600V for supply
side applications. A large backlit LCD clearly displays all
measurements that turns on at the touch of a button
or when rotating the selection dial. It also automatically
switched off to save battery consumption.
The DPM1000 can measure DC, AC, pulsed and mixed
currents up to 1000 A simply by clamping the jaws
around the appropriate conductor, whilst voltages up
to 1000 V AC or DC may be measured by the supplied
test leads, Where power measurements are to be made
both techniques above are performed simultaneously. All
power related parameters including energy consumption,
frequency, total harmonic distortion, distortion factor and
capacitance. It features auto-ranging and has 3 phase
rotation indication.
The DPM1000 measures Single and 3 phase active power
and power factor, the harmonic content of the signal,
up to the 25th harmonic can be displayed. Temperature
measurements can be made up 1000°C using the
thermocouple provided.
The DCM1000 is ideally suited to measuring mains power
quality and applications in the development, installation,
maintenance and repair of equipment and devices used
in power electronics and power engineering. The unit has
an internal torch that lights during the operation of the
clamp and automatic non-contact voltage detection for
identification of live circuits.
The DPM 1000 may be used to perform data logging
to its internal non-volatile memory. You can record a
maximum of 9999 readings/records to the memory over
a period of time and download the data to produce
graphs and reports. The record rate can be set from 1 sec
to 600 sec. The accuracy of the timer is within 3 seconds
per hour.
The meter uses low-power Bluetooth v4.0 wireless
technology to transfer real-time data to the free
Megger Link
TM
app, available for both iOS and Android.
The maximum communication range in open air is
approximately 10 m. This function is invalid for Inrush and
Phase Rotation.
The DPM1000 is supplied complete with test leads and
Thermocouple Probe in full sized Carry case.
AC/DC Voltage to 1000V
AC/DC Current to 1000A
True RMS
Resistance 100kΩ
LCD Display
Phase rotation indication
Inrush peak current
Auto backlight display
Frequency measurement
Capacitance measurement
Power Factor
Measurement
Watt measurement to
1MW
Harmonic measurement
Harmonic distortion
Diode test
Non-contact volt alert
Continuity Beeper
Data Hold/Min-Max/Peak
Hold
Bright LED torch
Temperature to 1000° C
Carrying holster/pouch
CAT IV 600V Rating
Bluetooth/Megger Link
TM
APP
Supplied with carry case