Datasheet
Resistance measurement ranges:
Full Scale
Resistance
Test Current Resolution Normal
Resistance Mode
Inductive Mode Long Test Lead
Mode (1 A only)
15000 µΩ 2.00 A 1 μΩ
120.00 mΩ 2.00 A 0.01 mΩ
1000.0 mΩ 2.00 A 0.1 mΩ
30.000 mΩ 1.00 A 0.001 mΩ
240.00 mΩ 1.00 A 0.01 mΩ
2200.0 mΩ 1.00 A 0.1 mΩ
300.00 mΩ 100 mA 0.01 mΩ
2500.0 mΩ 100 mA 0.1 mΩ
20.000 Ω 100 mA 0.001 Ω
3000.0 mΩ 10.0 mA 0.1 mΩ
24.000 Ω 10.0 mA 0.001 Ω
200.00 Ω 10.0 mA 0.01 Ω
30.000 Ω 1.00 mA 0.001 Ω
240.00 Ω 1.00 mA 0.01 Ω
2000.0 Ω 1.00 mA 0.1 Ω
ENVIRONMENT
Noise immunity: Less than 1% ±20 digits additional
error with 80 mV peak 50/60 Hz
with on screen noise limit indicator.
Less than 1% ±20 digits additional
error with 80 mV peak 400 Hz with
on screen noise limit indicator.
EMC: IEC61326-1, industrial specification
IEC61326-2-2.
Dust and moisture
ingress: IP54 to IEC60529 in use
Altitude: Operational to 3000m
Temperature: Operational range 0 ºC to 50 ºC
Storage range -20 ºC to 50 ºC
Humidity: Operational to 95 %
Storage to 90 %
POWER SUPPLY
Rechargeable 6 x HR6 NiMH batteries with built-in fast
charge
(also has the ability to use non-rechargeable alkaline
AA batteries (LR6))
Battery charge time < 4 hours
Battery life >1000 bi-directional tests at
2 A auto into a 1 Ω load
BATTERY CHARGER ADAPTOR
Mains/line input voltage: 100 to 240 V
Mains/line input frequency:
47 to 63 Hz
Output: 12 V DC 1.2 A 14.4 W max
Type: Travel adaptor/interchangeable plug
adaptor
Plug types: Australia, USA, Europe and UK plugs
CONNECTIONS
Test terminals: 4 X 4 mm shrouded sockets
Data: USB (For firmware updates only),
the user may update instrument
firmware to latest version themselves
Battery charger: 2.5 mm DC jack connector
DLRO2
Ducter™ Low Resistance Ohmmeter 2 A