Product Order Code
PAT410-DE 1000-748
PAT410-EU 1000-747
PAT450-EU 1000-751
PAT450-DE 1000-750
Included accessories
Printed quick start guide
Full user guide on CD
Calibration Certificate
Continuity / earth bond lead + probe (black) 2000-870
Extension lead adaptor (ELA) 230 V SC (CEE7/7) 2000-882
Flash lead 3.0 KV 3.5 mA (red) (PAT450 only) 5310-401
Carry case with lead/document pouch 2000-962
Plug adaptor IEC C6 - C13 (3 way 5 A PSU) 2000-551
Screen protector
Product Order Code
Optional accessories
415 V Adaptor lead (4 pin) to SC (CEE7/7) 1000-768
415 V Adaptor lead (5 pin) to SC (CEE7/7) 1000-771
Bar code scanner (USB) 1001-047
Pass/fail barcode label printer (USB) 1001-046
USB lead – PAT – printer 25970-041
Barcode printer label refills (cartridge) 90001-010
Appliance bar-code labels (1-1000) 6121-483
Roll of 1000 FAIL test labels 1001-227
Roll of 1000 PASS test labels 1000-971
PAT accessory pouch 2001-044
Screen protector (2) 1002-572
PAT400 SERIES
Portable Appliance Testers
Flash test
Flash test voltage: 1500 V a.c. nominal for Class 1
3000 V a.c. nominal for Class 2
Flash test current: <3.5 mA short circuit @ 253 V
primary supply voltage
Flash test breakdown current
accuracy: ±5% ±5 digits
Flash test breakdown current
resolution: 0.01 mA
Display range: 0 to 3.0 mA
Portable RCD test
Test voltage and frequency: Nominal mains supply
Test current accuracy: -8% to -2% (1/2 x I)
+2% to +8% (1 x I, 5 x I)
Trip time accuracy: ±1% ±5 digits
Trip time resolution: 0.1 ms
Display range: 0 to 1999 ms (1/2 x I)
0 to 300 ms (1 x I)
0 to 40 ms (5 x I)
Fuse test
Test voltage: 3.3 V
Warning: Audible beep if fuse is OK
Environmental
Operating temperature: -10 to +50 ºC
Storage temperature: -20 to +60 ºC
Humidity: 90% RH @ -10 to +30 ºC
75% RH @ +30 to +50 ºC
Maximum altitude: 2000 m
Ingress protection: IP40
Weight
PAT410 (with packaging) 2.7 kg (3.2 kg)
PAT450 (with packaging) 5.0 kg (5.5 kg)
Dimesions
PAT410 120 (H) x 255 (W) x 320 (L)
PAT450 155 (H) x 255 (W) x 320 (L)
Packaging: 210 (H) x 280 (W) x 390 (L)
Safety
IEC 61010-1: CAT II 300 V
EMC
IEC 61326-1: 2006