Datasheet

PAT400 SERIES
Portable Appliance Testers
SPECIFICATIONS
Electrical supply range
PAT410 and PAT450 230 V ± 10% @ 50/60 Hz
Bond test (10 A and 25 A) (not PAT410)
Open circuit voltage: 9 V a.c. ± 10% ± 0.1 V
(Supply: 230 V 50Hz)
Earth bond resistance accuracy:
±5% ±3 digits (0 to 0.49 Ω)
±5% ±5 digits 0.5 to .99 Ω)
Earth bond resistance resolution: 10 mΩ (0 to 1.99 Ω)
Display range: 0 to 1.99 Ω
Continuity test (200 mA)
Continuity test voltage: 4.0 V d.c. -0% +10%
Continuity resistance accuracy: ±5% ±3 digits (0 to 0.49 Ω)
±5% ±5 digits 0.5 to .99 Ω)
Continuity resistance resolution: 10 mΩ (1 to 19.99 Ω)
Display range: 0 to 19.99 Ω
Insulation test (250 V and 500 V)
Insulation resistance accuracy (230 V):
±2% ±5 digits (0 to 19.99 MΩ)
±5% ±10 digits (20 to 99.99 MΩ)
Insulation resistance resolution: 0.01 MΩ
Display range: 0 to 99.99 MΩ
Substitute leakage test
Test voltage and frequency: 40 V a.c. ±10% nominal mains
frequency
Leakage current accuracy: ±5% ±5 digits
Leakage current resolution: 0.01 mA
Display range: 0 to 19.99 mA
Differential leakage current
Test voltage and frequency: Nominal mains supply
Differential leakage current accuracy: ±5% ±5 digits
Differential leakage current resolution: 0.01 mA
Display range: 0 to 19.99 mA
Touch current test
Test voltage and frequency: Nominal mains supply
Touch current accuracy: ±5% ±5 digits
Touch current resolution: 0.01 mA
Display: 0 to 10 mA
Operational test
Test voltage and frequency: Nominal mains supply
VA accuracy: ±5% ±10 digits (0 - 99 VA)
±5% ±50 digits (100 VA - 999 VA)
±5% ±100 digits (1000 VA - 3700 VA)
Resolution: 1 VA (0 to 3700 VA)
Display range: 0 to 3999 VA
Extension lead test
Tests performed: Bond, insulation and polarity
Polarity test voltage: 12 V
Polarity checks: Lead OK
Live neutral S/C
Live neutral reversed
Live/neutral O/C
PAT410 PAT450
SUPPLY
230 V n n
Supply measurement n n
EARTH BOND/CONTINUITY
200 mA n n
10 A n
25 A n
Bond lead null n n
INSULATION TEST
250 V n n
500 V n n
ALTERNATIVE LEAKAGE TESTS
Substitute n n
Differential n n
Touch current n n
OPERATION TEST
VA Measurement n n
EXTENSION LEAD TESTS
Earth bond n n
Insulation n n
Polarity n n
Portable RCD tests n n
FLASH TEST
1.5 kV and 3 kV n
OTHER FEATURES
Low-profile light weight n
Auto test routine n n
Manual testing n n
Fuse check n n
Colour display n n
Configurable tests times n n
Selectable pass limits n n
Lead storage pouch n n
10,000 record on-board storage n n
Download to USB memory stick n n
PowerSuite compatible n n