Specifications

Issue 6 February 2007 405
AC power distribution
A typical AC power-distribution unit for an MCC1 contains:
Circuit breakers
Ring generator
Optional batteries
Optional battery charger
The power distribution cables carry 120 VAC during normal operation and 144 VDC from
optional batteries if AC power fails. Another cable connects 120-VAC to the battery charger.
The following figures show an AC power-distribution unit and battery charger (J58890CE-2 List
15 or later). The AC power-distribution unit and the battery charger sit at the bottom of some
MCC1s.
AC power-distribution unit (J58890CE-2) (front)
Figure 85: AC power-distribution unit (J58890CE-2) (front)
The AC power-distribution unit contains the following additional components that are not shown
in the figure:
Electromagnetic interference (EMI) filter
AC input fuse
Five circuit breakers, one for each carrier
20-A fuses
A signal connector
-48 VDC fan power
The optional battery charger sits at the bottom of some MCC1s.
Circuit
breakers
Ring
generator
631DB
power unit
Ring generator
fuse
psdfacpd RP Y 053097