Specifications
Issue 6 February 2007 397
Floor load requirements
The equipment room floor must meet the commercial floor loading code of at least 50 pounds
per square foot (242 kilograms per square meter). Floor plans usually allocate space around the
front, the ends, and, if necessary, the rear for maintenance access of the Media Gateways.
Additional floor support might be required if the floor load is greater than 50 pounds per square
foot (242 kilograms per square meter). The following table contains information about weight
and floor loading for the media gateway and battery.
DC power cabinet
3
20 (51 cm) 27 (69 cm) 22 (56 cm) Front and rear
38 (97 cm)
Large battery
cabinet
100
200
300
400
27 (69 cm)
42 (107 cm)
42 (107 cm)
57 (145 cm)
55 (140 cm)
55 (140 cm)
55 (140 cm)
55 i (140 cm)
21 (53 cm)
21 (53 cm)
21 (53 cm)
21 (53 cm)
Front and rear
38 (97 cm)
1. This row includes the auxiliary cabinet, the global AC cabinet, and the global DC cabinet.
2. Cable slack manager is used with MCC1 Media Gateway and the SCC1 Media Gateway.
3. DC power cabinet requires a floor area of 8 square feet (0.74 square meters). The DC power cabinet also
requires 38 inches (97 cm) between the cabinet and the wall.
Cabinet type Height
(inches)
Width (inches) Depth (inches) Clearance
(inches)
Media
Gateway
Weight (pounds) Floor loading (pounds
per square foot)
Notes
SCC1 125 (56 kg) 31 (148.9 kg/m
2
)
MCC1 200 to 800 (90 to
363 kg)
130 (624.2 kg/m
2
) Includes
auxiliary,
global AC, and
global DC
cabinets