Specifications
Avaya UPS Units
366 Hardware Description and Reference for Avaya Communication Manager
1000 VA 120 V models include the following accessories:
● Extended Battery Module (EBM24)
● Bypass Distribution Module 1000 VA to 1500VA 120 volts
● SNMP module
Safety Compliance: UL, CSA, NOM
EMC Compliance: FCC Class B, VCCI Class II.
Input: 120 Vac, 45-65 Hz, auto sensing; user-selectable 100 or 127 VAC; 6-foot (183
centimeter) attached cord with 5-15 P
AS1 1000VA 230V online UPS
The 1000 VA 230 V online UPS provides up to 700 watts and basic battery holdover of 5
minutes at full load. Output current for 208/220/230/240 volts is 4.8/4.5/4.3/4.2 A. Two optional
extended battery modules (EBM24) extend the run time to 104 minutes at full load.
1000VA 230 V models include the following accessories:
● Extended Battery Module (EBM24)
● Bypass Distribution Module 700-2000 VA 230 V
● SNMP Module
Safety Compliance: UL, CSA, NOM, CE
EMC Compliance: FCC Class B, EN 50091-2, VCCI Class II, IECS-003
Input: 230Vac, 50/60 Hz, auto sensing, user-selectable 220, 240; 2-meter cord with
unterminated plug-end.
AS1 1500VA 120V online UPS
The AS1 1500 VA 120 V online UPS provides 1500 VA/1050 watts/12.5 A at 120 Volts AC and
battery holdover of 8 minutes at full load. Four optional extended battery modules-EBM48
extend the run time to 144 minutes at full load.
The AS1 1500 VA model includes the following accessories:
● Extended battery module (EBM48)
● Bypass distribution module AS1 1000-1500 VA 120 V
● SNMP module