Specifications

172 Hardware Description and Reference for Avaya Communication Manager
Temperature and humidity
The G600 Media Gateway must be installed in a well-ventilated area. Maximum equipment
performance is achieved at an ambient temperature between 40 °F and 120 °F (4 °C and 49 °C)
for a short-term operation of not more then 72 consecutive hours or 15 days in one year. A
continuous operation requires up to 110 °F (43 °C).
The relative humidity range is 10 to 95% at up to 84 °F (29 °C). Above 84 °F (29 °C), maximum
relative humidity decreases from 95% to 32% at 120 °F (49 °C). Installations outside these limits
might reduce system life or affect operation. The recommended temperature range and
humidity range is 65 °F to 85 °F (18 °C to 29 °C) at 20 to 60% relative humidity.
Power requirements
The G600 Media Gateway has the following AC power requirements using the 650A integrated
power supply.
Note:
Note: There is no integrated DC power supply. DC rectifiers can be used if desired;
follow manufacturer’s instructions.
Power sources Power input receptacles
1
1. Japan installations use country-specific receptacles for 100 VAC and 200 VAC,
50/60 Hz
.
Circuit
Amperes
Single-phase 120-VAC with
neutral
120-VAC, 60-Hz NEMA 5-15R 15
Single-phase 240-VAC with
neutral
240-VAC, 50-Hz IEC 320 10