Specifications

IG550 Integrated Gateway
Issue 5.1 June 2006 143
Most sites distribute DC power through a main conduit that leads to frame-mounted DC power
distribution panels, one of which might be located at the top of the rack that houses the router. A
pair of cables (one input and one return) connects each set of terminal studs to the power
distribution panel.
Each DC power cable (ñ48 VDC and return) must be 14 AWG single-strand wire cable, or as
permitted by the local code. Each lug attached to the power cables must be a ring-type,
vinyl-insulated TV14-6R lug, or equivalent.
TGM 550 Gateway Module specifications
Grounding cable for IG550
When housing a TGM550, the J-series router must use a grounding cable that meets the
following specifications:
10 AWG
Able to handle up to 8 Amp current
Have a ring-type, vinyl-insulated TV14-6R lug, or equivalent, to accommodate the 10 AWG
cable
The original grounding cable for Juniper Services Routers is 14 AWG only and must be
replaced with a 10 AWG cable
Related hardware
The IG550 Gateway Module supports a variety of swappable internal boards called Telephony
Interface Modules (TIMs). In addition, the Juniper J-series Services Routers support swappable
internal components called Physical Interface Modules (PIMs)
Table 19: TGM550 Gateway Module
Description Value
Ambient working
temperature
32° to 158°F (0° to 70°C)
Operation altitude up to 10,000 ft. (3,048 m)