User manual
3
2.Belowtheambienttemperatureof40 ,PB-360canprovidethemaximumchargingcurrenttothebatteries.Iftheambient
temperatureishigherthan40 ,theoutputcurrentofPB-360willdecreaseautomatically.Pleaserefertothederatingcurveshown
asbelow:
Pleasechoosewireswithsuitablediameterofitscrosssectionbasedonthecurrentrating.Pleaserefertothefollowingtableforthe
informationofsomefrequentlyusedwires.Usingredwirestoconnectthe(+)terminalsandblackonesfor(-)terminalsishighly
recommended.(Blackwiresforgroundingisausualpracticeinelectricalapplications.)
SelectionOfOutputConnection:
1.Itwillnothaveanyproblemifthecapacityofbatterieslargerthanthesuggestedvalue.
Itjusttakesmoretimetomakethebatteriesfullycharged!
2.Ifyouhaveanyquestionaboutthesuitablechargingcurrentforthebatteries,pleaserefertothetechnicaldataprovidedbythe
batterymanufacturersorconsultthevendorofthebatteries.
SuggestedBatteryCapacity:
40 50 60 70302010-20
LOAD(%)
90
100
80
70
60
40
30
AMBIENTTEMPERATURE( )
AWG
Model Model
10
PB-300-12 PB-360-12
5.262
60-200Ah 80-240Ah
35
12
PB-300-24 PB-360-24
3.309
30-100Ah 40-125Ah
22
14
PB-300-48 PB-360-48
2.081
15-50Ah 20-65Ah
12
16 1.309 8
18 0.823 6
20 0.517 4
CROSSSECTION(mm)
SuggestedBatterycapacity SuggestedBatterycapacity
Max.Current(A)
UL1015(600V105 )
2
NotesOnFailureElimination
Ifyoustillcannoteliminatethefailuresituation,pleaseconsult MEANWELL oranyofourdistributors
Status
Nooutput
voltage
Outputvoltage
istoolow
Can'tachieve
theFLOAT
(greenlight)
stageafter
longperiod
ofcharging
operation
PossibleReasons
PowerswitchisnotsettoON(-)
Setthepowerswitchto
ON(-)
Replacethefuse
Repairrequired.Please
senditbacktousorany
ofourdistributors
Choosethecorrectinput
voltagerangethroughthe
115/230Vacswitch
Replacethebatteries
Chooseconnectingwires
withsuitablegauge
Wrongpolarityofthebattery
connection(outputfuseopen)
Wrongselectionofthe115/230Vac
switch
Wrongselectionofthe115/230Vac
switch
Batteriesareagingorbroken
Thegaugeofoutputwireisnot
largeenough
WaystoEliminate