User manual

2
5.Ifthebatteriesneedtoconnectinseriesforcharging,oldbatteriesarenotsuggestedtobeusedwithnewonesorthelifetimeof
batteriesmayreduce becauseoftheunbalancechargingvoltagedistributiononnewandoldbatteries.
6.Pleaseturnoffthechargerbeforeconnectingordisconnectingthewires.
7.The charger has a 3-year worldwide warranty, however, damages from misusing the charger will not be included in the coverage of
warranty.
At the beginning stage of operation, the charger provides the largest current with 14.4Vdc of output voltage (for 12V batteries) to
charge batteries. The LED indicator will lighten in red and the built-in fan will spin to dissipate the heat (360W only). After a period of
time (probably a couple of hours, based on the capacity of batteries), the charging current will decrease gradually. After reaching 10%
of its maximum value, the charger will go into "floating-charge" stage. The fan will stop spinning, charging voltage will decrease to
13.6Vdc, and the LED indicator will turn to green. The relationship between charging current and charging voltage for each operation
stageareshowninthecurvesbelow:
StatusUnderGeneralOperation:
NOTE:Outputvoltageofthecharger(V )canbeadjustedthroughSVR1withoutconnectingthebatteriesandthisadjustmentwill
changethevalueofV atthesametime.Forexample,iforiginallyV is13.6VandV is14.4V,afteradjustingV to
13.2Vunderno-loadcondition,V willalsoreduceto14V.So,pleaseconsultthemanufacturerofbatteriesaboutthe
suitablechargingvoltagebeforemakeanyadjustment.
1.ThechargingcurrentofPB-300 willreducewhentheambienttemperaturegoesup.
Pleaserefertothederatingcurveshownasbelow:
FLT
boost FLT boost FLT
boost
ChargingCurrent And AmbientTemperature
EXTERNAL CASETEMPERATURE( )
40 50 603020 25-10 0 10
LOAD(%)
90
100
80
70
60
40
30
ChargeCurrent
stage1
ConstantCurrent
stage2
ConstantVoltage
stage3
Floating
Start
ChargeVoltage
VFLT
100%
Red Green
LEDCOLOR
boostV
State
Vboost 14.4V
PB-300/360-12
28.8V 57.6V
PB-300/360-24 PB-300/360-48
VFLT 13.6V 27.2V 54.4V