Datasheet

SPECIFICATION
SD-50A-5 SD-50B-5 SD-50C-5 SD-50B-12 SD-50C-12 SD-50B-24 SD-50C-24SD-50A-12 SD-50A-24
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT
VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISE,HOLDUP TIME
VOLTAGERANGE
EFFICIENCY (Typ.)
INPUT
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
DCCURRENT
5V 12V 24V
10A 4.2A 2.1A
0~10A 0~4.2A 0~2.1A
50W 50.4W 50.4W
100mVp-p 120mVp-p 150mVp-p
2.0% 1.0% 1.0%
4.5~5.5VDC 11~16VDC 23~30VDC
0.5%
0.5%
0.3%
0.3%
0.2%
0.2%
2.5s,50ms,------atfullload
A:9.2~18VDCB:19~36VDCC:36~72VDC
70%
7A/12V 3A/24V 1.5A/48V
73% 76% 72%
7A/12V 3A/24V 1.5A/48V
75% 78% 74% 80% 83%
7A/12V 3A/24V 1.5A/48V
105~150% ratedoutputpower
5.75~6.75V/10%load 16.8~20V/10%load 31.5~37.5V/10%load
Protectiontype: Hiccupmode,recoversautomaticallyafterfaultconditionisremoved
Protectiontype:Hiccupmode,recoversautomaticallyafterfaultconditionisremoved
CompliancetoEN55022(CISPR22)ClassB
DesignrefertoLVD
CompliancetoEN61000-4-2,3,4,6,8,EN55024,heavyindustrylevel,criteria A
-10~+60 (Referto"DeratingCurve")
20~90%RHnon-condensing
-20~+85 ,10~95%RH
0.03%/ (0~50
10~500Hz,2G10min./1cycle,60min.eachalongX, Y,Zaxes
365.6Khrsmin.(SD-50A)357.5Khrsmin.(SD-50B)368.5KHrsmin.(SD-50C)MIL-HDBK-217F(25 )
159*97*38mm(L*W*H)
0.48Kg;24pcs/12.7Kg/0.75CUFT
FileName:SD-50-SPEC2012-09-12
SAFETY STANDARDS
50WSingleOutputDC-DCConverter
2:1 wide input range
Protections: Short circuit / Overload / Over voltage
1500VAC I/O isolation
Built-in EMI filter, low ripple noise
100% full load burn-in test
Fixed switching frequency at 83KHz
Low cost
High reliability
2 years warranty
Features :
SD-50 se ri es
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
ENVIRONMENT
PROTECTION
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:1.5KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC /25 /70%RH
SAFETY &
EMC
(Note4)
1. All parameters NOT specially mentioned are measured at 12,24,48VDC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
EMCIMMUNITY
EMCEMISSION

Summary of content (2 pages)