Datasheet

SPECIFICATION
SD-200B SD-200C
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
VOLTAGE RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
DC CURRENT (Typ.)
5V 5V12V 12V24V 24V48V 48V
34A 40A16.7A 16.7A8.4A 8.4A4.2A 4.2A
0 ~ 34A 0 ~ 40A0 ~ 16.7A 0 ~ 16.7A0 ~ 8.4A 0 ~ 8.4A0 ~ 4.2A 0 ~ 4.2A
170W 200W200.4W 200.4W201.6W 201.6W201.6W 201.6W
100mVp-p 100mVp-p120mVp-p 120mVp-p150mVp-p 150mVp-p200mVp-p 200mVp-p
±2.0% ±2.0%±1.0% ±1.0%±1.0% ±1.0%±1.0% ±1.0%
4.5 ~ 5.5VDC 4.5 ~ 5.5VDC11 ~ 16VDC 11 ~ 16VDC23 ~ 30VDC 23 ~ 30VDC43 ~ 53VDC 43 ~ 53VDC
±0.5% ±0.5%±0.5% ±0.5%±0.5% ±0.5%±0.5% ±0.5%
±1.0% ±1.0%±1.0% ±1.0%±1.0% ±1.0%±1.0% ±1.0%
300ms, 50ms at full load
B:19 ~ 36VDC C:36 ~ 72VDC D:72 ~144VDC
79% 81%
10.8A/24V 5.4A/48V
82% 84%85% 86%86% 86%
10.6A/24V 5.2A/48V10.4A/24V 6.7A/48V10.4A/24V 5A/48V
C:45A/48VDC D:45A/96VDC
105 ~ 135% rated output power
5.75 ~ 6.75V 5.75 ~ 6.75V16.8 ~ 20V 16.8 ~ 20V31.5 ~ 37.5V 31.5 ~ 37.5V53 ~ 65V 53 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-4-2,3,4,6,8, light industry level, criteria A
-20 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
±℃ )0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
218.2K hrs min. MIL-HDBK-217F (25 )
215*115*50mm (L*W*H)
1.1Kg; 12pcs/14.4Kg/0.92CUFT
File Name:SD-200-SPEC 2013-12-17
1. All parameters NOT specially mentioned are measured at 24,48,96VDC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
200W Single Output DC-DC Converter
2:1 wide input range
Protections: Short circuit / Overload / Over voltage / Over temperature
1500VAC I/O isolation
Cooling by free air convection
100% full load burn-in test
24V and 48V input voltage design refer to LVD
2 years warranty
Features :
SD-200 series
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:1.5KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
ENVIRONMENT
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
UL60950-1approved (for SD-200C-24 type only), IEC60950-1 CB approved by TUV (for D type only)
(for D type only)(for SD-200C-24 type only)
EMC IMMUNITY
EMC EMISSION