Data Sheet
1600W Power Supply with Single Output
RSP-1600 series
File Name:RSP-1600-SPEC 2018-01-15
4. Remote ON-OFF Control
5. Alarm Signal Output
※ The power supply can be turned ON/OFF individually or along with other units by using the "Remote ON-OFF" function.
※ There are 2 alarm signals, DC OK and T-ALARM, in TTL signal form, on CN1. These signals are isolated from output. The maximum sink current
is 10mA.
Between Remote ON-OFF and +5V-AUX
Switch Short
Switch Open
Power Supply Status
ON
OFF
switch
PIN4 Remote ON-OFF
PIN6 T-ALARM
PIN2 GND-AUX
Application
Circuit
PIN3 +5V-AUX
PIN5 DC OK
CN1
CN1
+V
+V
-V
-V
3. Constant Current Level Programming (or, PC / remote current programming / dynamic current trim)
Iout
V
0.4 1 4.7 5
20
100
EXTERNAL VOLTAGE (VDC)
OUTPUT CURRENT (%)
Non-Linear
110
※ The constant current level can be trimmed to 20~100% of the rated current by applying EXTERNAL VOLTAGE.
EXTERNAL VOLTAGE (DC)
CN1
PIN14 -V(signal)
PIN11 PC
+V
-V
◎ For Remote Sense / Local Sense, please refer to “Voltage Drop Compensation” section.