Data Sheet
※ In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed by applying EXTERNAL VOLTAGE.
2. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
60 80 100 125
V
100
40
60
80
20
OUTPUT CURRENT (%)
OUTPUT VOLTAGE (%)
40
EXTERNAL VOLTAGE (DC)
Function Manual
40
60
OUTPUT VOLTAGE(%)
EXTERNAL VOLTAGE (DC)
100
125
Vout
0.40 1 4.7 5
V
Non-Linear
12V
Others
◎ The rated current should change with the Output Voltage Programming accordingly.
◎ For Remote Sense / Local Sense, please refer to “Voltage Drop Compensation” section.
CN1
PIN14 -V(signal)
PIN12 PV
+V
-V
1600W Power Supply with Single Output
RSP-1600 series
File Name:RSP-1600-SPEC 2018-01-15
◎ The +S signal should be connected to the positive terminal of the load whereas -S signal to the negative terminal.
1. Voltage Drop Compensation
Sense lines should be twisted in pairs to minimize noise pick-up.
L
L
O
O
A
A
D
D
-
-
V
V
+V
+V
PIN16 -S
PIN15 +S
PIN16 -S
PIN15 +S
PIN13 +V(signal)
PIN14 -V(signal)
CN1
CN1
+V
+V
-V
-V
※ The Remote Sense compensates voltage drop on the load wiring up to 0.5V
1.1 Remote Sense
1.2 Local Sense
※ The +S,-S have to be connected to the +V(signal), -V(signal), respectively, as the following diagram, in order to get the correct output voltage if
Remote Sense is not used.