Datasheet

40
Input/ Output
115VAC
23 0VAC
+12VDC
+24VDC
+48VDC
Other commonly used wires
Module
1 unit
1 unit
1 unit
1 unit
1 unit
2 unit
2 unit
2 unit
3 unit
3 unit
3 unit
Curre nt
16Arms
10Arms
100A dc
80Adc
42Adc
200A dc
160A dc
84Adc
300A dc
240A dc
126A dc
Minimum Cross-sectio n of Co pper Wire
14AWG UL1015
18AWG UL1015
22mm
22mm
5.5mm
60mm
50mm
22mm
30mm
125mm
80mm
16AWG UL1015
12AWG UL1015
10AWG UL1015
30mm
50mm
60mm
80mm
100mm
125mm
150mm
200mm
250mm
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Maximum Current
12A
6A
115A
115A
49A
217A
190A
115A
344A
240A
139A
8A
22A
35A
139A
190A
217A
257A
298A
344A
395A
469A
556A
8.2 De-rating
8.3 EMI Suppression Arrangement
8.4 Warranty
When RCP-2000 units are operating in high ambient temperature or at a low AC input voltage, these units will de-rate their output
current aut omatic ally to prote ct them selve s, as Figure 8-2 sh ows.
EMI radiation test is greatly affected by wiri ng. Att aching an EMI suppresso r (ferrite cor e) to the AC cable as close as po ssible
When using a RJ- 45 cab le as y our int erface cable , it might be needed to att ach an EMI s uppressor (ferrite core) to the ca ble as
close as possible to the Ether net con nector (JK1) to red uce E MI radiation interference. There are TDK ZCAT203 2-093 0, NEC
ESD-SR-1 60, an d EROCORE FH 28 9 16 available for that purpos e.× ×
to th e AC in let to reduce the noise is recom mended. Th ere are sugg ested compo nents for reducing EMI radiation interference
including TDK HF70RU 26*29 *13S, NEC ESD-SR-250H , and EROC ORE FH29.7*13*2 5.9.
Three years of glo bal wa rranty is pro vided for RCP 2000 seri es/ RK P-CM U1 under no rmal operati on. Please do not c hange
any compo nent o r mod ify th e unit b y yourself o r MEA N WE LL ma y rese rve the right not to provid e the comp l ete w a rrant y
service.
Table 8-1 Sugge sted wire selection for input/output wi rings
Fi gure 8-2 Out put de-rating curve s for RCP-20 00 series
INPU T AC VOLTAGE (VAC) 60Hz
90 100 115 180
24V,48V
12V
264
90
100
80
70
75
65
50
40
AMBIENT TEMPERATURE ( )
230VAC
Input only
-40 -25 0-10 15 30 50 60 70
20
40
60
50
80
100
(HORIZONTAL)