6.3.4.2 Setting of Clear Event Log/Data Log and Data Log T ime Interval
6.3.4.3 Setting of Programma ble Re lay
6.3.4.4 PSU ON/OFF set ting
The "E vent L og" and "Da ta Log " buttons are used to clear the data tha t Event log/ Data log has stored . The "Data
"Rela y Setting" se ction is used to se t act iv ating conditions o f the p rogram mabl e rela y s. After sett ing, click the
"save " button to save your setting va lues.
Each relay can be set for the fu nction s below :
Turning a u nit or all the units on/off c an be done b y selecting the "scroll-do wn lis t". "ON (green)" indicates "PSU
ON", "OFF(red)" in dicates "PSU OFF", and "N/A(orange)" indic ates "u nconnected ". Once you h ave chosen a PSU,
you c an clic k the " ON" o r "OFF" buttons to turn it on/off. If the status column displays "N /A(orange)" , it can not be
contr olled d ue to non-connect ion to the RK P-CMU1.
1.Ala rm act ivating : Any Alarm, OVP, OLP, O TP, Short circuit, High Te mp., AC Fai l, Fan lock, o r PMBus Error.
2.PSU ON a ctivating: Immedia tely, o r Delay (1~6 00 sec ).
3.PSU OFF activating: Im medi ately, or Delay (1~600 sec).
4.Dig ital I/P activating: Contro l by DI 1, control by DI2, c ontrol by DI3 , or co ntrol b y DI4.
Log in terval" is use d to se t the time in terval from 1 to 60 minute s.
Adjustable range (1~60)