5.2.4.2 Setti ng of C lear E ventL og/D ataLog and DataL og Time Interval
5.2.4.3 Setti ng of P rogra mmable Re lay
The "S et Clear EventLog/DataL og" bo x is used to c lear the data that E vent lo g/Data log h as stored, while the "Set
Each relay can be set for the fu nctions below :
1.Alar m acti vating : Any Alarm, OVP, OLP, OTP, Short circuit, High Temp., AC Fail , Fan lo ck, or PMBu s Error.
2.PSU ON a ctivating: Immediately, or Delay (1~600 sec) .
3.PSU OFF a ctivat ing: Immediately, or Dela y (1~6 00 sec).
4.Digi tal I/P activating: C ontrol by DI1, control by DI2, co ntrol by DI3, or control by DI4.
DataLog time inter val" box can set the time interval from 1 to 60 minu tes.
5.2.4.1 Bus Voltage / PSU Current
If the B us vo ltage/ PSU c urrent you s et is not with in the adjust able range, it will becom e invalid. Make sure the
param eters that you type in are not over or l ess than the range as bel ow.
Adjus table range of Bus voltage/ PSU curre nt:
Note : If the set PSU current ex ceeds 100A, the maximu m rated current, OT P might be trigger ed after ope rating
a pe riod o f time.
Once you in sert th e corr ect u s er name an d pass word, you w ill ent er the settin gs pa ge . On this p age, t here are Bu s
voltag e, PSU over-current, clea r Event Log/Data Lo g, Data Log time in terval setting, programmable relay set ting, a nd PSU
ON/OFF that can b e set and altered.
Model Bus voltage range PSU current range
12V 10.5 ~ 14V 30 ~ 112A
24V 21 ~ 28V 24 ~ 89.6A
48V 42 ~ 56V 12 .6 ~ 47 A
Adjustable
Range
Click the scroll-down list of the "Function"
to select an activation group