Datasheet
Pin No. Function
Description
1,8,15
2,9,16
3,10,17
4,11,18
5,12,19
7
23
25
14
6
Remote
ON-OFF
AC-OK
DC-OK
V-TRIM
T-ALARM
GND-AUX
SCL
-V
CS
+5V-AUX
Each unit can separately turn the output on and off by electrical or dry contact between Remote ON-OFF A,B,C(pin 1,8,15) and -S(pin 21). Short: ON, Open:OFF.
Low : When input voltage is 82Vrms +/-4V.≧
High : When input voltage in 82Vrms +/-4V.≦
High : When Vout 80%+/-5%.≦
Low : When Vout 80%+/-5%≧
Connection for output voltage programming.
High : When the internal temperature is within safe limit.
Low : 10 below the thermal shut down limit.℃
Auxiliary voltage output GND.
The signal return is isolated from the output terminals (+V & -V).
Serial clock used in the I C interface option. Refer to the Instruction Manual.
Negative output voltage.
Current sharing signal.
When units are connected in parallel, the CS pins of the units should be connected to allow current balance between units.
Auxiliary voltage output, 4.3~5.3V, referenced to GND-AUX(pin 7).
The maximum load current is 0.3A. This output has the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
2
20
21
+S
-S
Positive sensing for Remote Sense.
Negative sensing for Remote Sense.
22 +V
Positive output voltage.
24 SDA
Serial data used in the I C interface option. Refer to the Instruction Manual.
2
※ IN/OUT Connector Pin No. Assignment( ) : D-Type RightAngle 25 positions(female type)CN500
File Name:RCP-1U Rack System-SPEC 2018-10-30
1000 ~ 3000W 1U Distributed Power System
RCP-1U Rack System
1
14
13
25