Datasheet

SPECIFICATION
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT
VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME Note.5
HOLDUP TIME (Typ.)
VOLTAGERANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
ALARM
INRUSHCURRENT (Typ.)
LEAKAGECURRENT
SAFETY STANDARDS
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
BATTERY CUTOFF
ACOK Note.6
BATTERY LOW
ACCURRENT (Typ.)
2400ms,30ms/230VAC2400ms,30ms/115VACatfullload
40ms/230VAC16ms/115VACatfullload
90~264VAC127~370VDC
47~63Hz
86%
CH1:28.98~37.26V
88%
20 1V
2A/115VAC1.2A/230VAC
COLDSTART 35A/115VAC70A/230VAC
<1mA /240VAC
105~150% ratedoutputpower
CH1:14.49~18.63V
Protectiontype: Hiccupmode,recoversautomaticallyafterfaultconditionisremoved
Protectiontype: Shutdowno/pvoltage,re-powerontorecover
10 0.5V
UL60950-1, TUVEN60950-1approved
CompliancetoEN55022(CISPR22)ClassB, EN61000-3-2,-3
Complianceto EN61000-4-2,3,4,5,6,8,11,EN55024,lightindustrylevel,criteria A
-20~+70
(Referto"DeratingCurve")
20~90%RHnon-condensing
-20~+85 ,10~95%RH
0.03%/ (0~50 )onCH1output
10~500Hz,2G10min./1cycle,60min.eachalongX, Y,Zaxes
417.6Khrsmin.MIL-HDBK-217F(25 )
PCB:127*76.2*31mm(L*W*H) ;withoptionalCASE:130*85*37mm(L*W*H)
PCB:0.23Kg;63pcs/15.5Kg/1.35CUFT ;withoptionalCASE:0.44Kg;32pcs/15Kg/0.64CUFT
FileName:PSC-100-SPEC2011-08-18
FUNCTION
Batterylowvoltage:<11V Batterylowvoltage:<22V
Relaycontactoutput,ON: ACOK;OFF: ACFail;Max.rating:30V/1A
Relaycontactoutput,OFF:BatteryOK;ON:BatteryLow;Max.rating:30V/1A
PSC-100B
27.6V
CH1
2.4A
0~3.5A
100.74W
100mVp-p
CH1:24~29V
1.0%
0.5%
0.5%
27.6V
CH2
1.25A
--------
--------
--------
--------
--------
13.8V
CH2
2.5A
--------
--------
--------
--------
--------
PSC-100A
13.8V
4.75A
0~7A
100.05W
100mVp-p
CH1:12~15V
1.0%
0.5%
0.5%
100WSingleOutputwithBatteryCharger(UPSFunction)
Universal AC input / Full range
5"x3" compact size
Protections: Short circuit / Overload / Over voltage
Battery low protection /
Relay contact signal output for AC OK and Battery Low
Cooling by free air convection
100% full load burn-in test
2 years warranty
Optional L-Bracket and cover (PSC-100x-C, x=A,B)
Battery polarity protection by fuse
Features :
PSC-100
se ri es
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
ENVIRONMENT
PROTECTION
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC /25 /70%RH
SAFETY &
EMC
(Note4)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. Please refer to suggest application (2) (4) in page 3.
7. Heat sink HS2,HS3 can not be shorted.
8. Heat sink HS2,HS3 must have safety isolation distance from system case.
For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
CH1
OUTPUTNUMBER
EMCIMMUNITY
EMCEMISSION

Summary of content (3 pages)