User manual
2
5.Ifthebatteriesneedtoconnectinseriesforcharging,oldbatteriesarenotsuggestedtobeusedwithnewonesorthelifetimeof
batteriesmayreduce becauseoftheunbalancechargingvoltagedistributiononnewandoldbatteries.
6.Pleaseturnoffthechargerbeforeconnectingordisconnectingthewires.
7.The charger has a 3-year worldwide warranty, however, damages from misusing the charger will not be included in the coverage of
warranty.
At the beginning stage of operation, the charger provides the largest current with 14.4Vdc of output voltage (for 12V batteries) to
charge batteries. The LED indicator will lighten in red and the built-in fan will spin to dissipate the heat (360W only). After a period of
time (probably a couple of hours, based on the capacity of batteries), the charging current will decrease gradually. After reaching 10%
of its maximum value, the charger will go into "floating-charge" stage. The fan will stop spinning, charging voltage will decrease to
13.6Vdc, and the LED indicator will turn to green. The relationship between charging current and charging voltage for each operation
stageareshowninthecurvesbelow:
StatusUnderGeneralOperation:
NOTE:Outputvoltageofthecharger(V )canbeadjustedthroughSVR1withoutconnectingthebatteriesandthisadjustmentwill
changethevalueofV atthesametime.Forexample,iforiginallyV is13.6VandV is14.4V,afteradjustingV to
13.2Vunderno-loadcondition,V willalsoreduceto14V.So,pleaseconsultthemanufacturerofbatteriesaboutthe
suitablechargingvoltagebeforemakeanyadjustment.
1.ThechargingcurrentofPB-300 willreducewhentheambienttemperaturegoesup.
Pleaserefertothederatingcurveshownasbelow:
FLT
boost FLT boost FLT
boost
ChargingCurrent And AmbientTemperature
EXTERNAL CASETEMPERATURE( )
40 50 603020 25-10 0 10
LOAD(%)
90
100
80
70
60
40
30
ChargeCurrent
stage1
ConstantCurrent
stage2
ConstantVoltage
stage3
Floating
Start
ChargeVoltage
VFLT
100%
Red Green
LEDCOLOR
boostV
State
Vboost 14.4V
PB-300/360-12
28.8V 57.6V
PB-300/360-24 PB-300/360-48
VFLT 13.6V 27.2V 54.4V