Owner's Manual

NPP-750-24 NPP-750-48NPP-750-12
MODEL
OUTPUT
VOLTAGE RANGE Note.3
FREQUENCY RANGE
POWER FACTOR (Typ.)
INPUT
ENVIRONMENT
INRUSH CURRENT (Typ.)
OVER TEMPERATURE
SAFETY STANDARDS
FUNCTION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING TEMP.
CHARGER OK SIGNAL
REMOTE CONTROL
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
PACKING
PROTECTION
14.4V 28.8V 57.6V
By built-in potentionmeter
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
PF>0.98/115VAC, PF>0.95/230VAC at full load
93% 93%92%
COLD START 50A at 230VAC
43 ~ 52V 82 ~ 100V
21.5 ~ 26V
Protection type : Shut down and latch off o/p voltage, re-power on to recover
Shut down O/P voltage, recovers automatically after temperature goes down
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Open : Power OFF Short : Power ON
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing
±℃0.05%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
230*158*67mm (L*W*H)
8.7A/115VAC 4A/230VAC
AC CURRENT (Typ.)
VOLTAGE ADJUSTABLE RANGE
10.5 ~ 21V 21 ~ 42V 42 ~ 80V
SHORT CIRCUIT
OVER VOLTAGE
EMC IMMUNITY
EMC EMISSION
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
BS EN/EN61000-6-2
Standard
Standard
Test Level / Note
Test Level / Note
BS EN/EN55032 (CISPR32),BS EN/EN55014-1
BS EN/EN55032 (CISPR32),BS EN/EN55014-1
BS EN/EN61000-3-2
BS EN/EN61000-3-3
BS EN/EN61000-4-2
BS EN/EN61000-4-3
BS EN/EN61000-4-4
BS EN/EN61000-4-5
BS EN/EN61000-4-6
BS EN/EN61000-4-8
BS EN/EN61000-4-11
Level 3, 8KV air ; Level 2, 4KV contact
Level 2, 3V/m
Level 2, 1KV
Level 2, 1KV/Line-Line,Level 3, 2KV/Line-Earth
Level 2, 3Vrms
Level 1, 1A/m
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class B
Class A
-----
NOTE
SAFETY &
EFFICIENCY (Typ.)
EMC
(Note 4)
Depends on internal temperature
FAN ON/OFF CONTROL
Protection type : charger will shutdown after 5 sec, re-power on to recoverConstant current limiting,
File Name:NPP-750-SPEC 2021-10-26
HOLD UP TIME (Typ.)
16ms/230VAC at 75% load 10ms/230VAC at full load
1800ms, 60ms/230VAC at full loadSETUP, RISE TIME
RATED CURRENT
DC VOLTAGE
LINE REGULATION
LOAD REGULATION
VOLTAGE TOLERANCE
±1.0% ±1.0%±1.0%
±0.5% ±0.5%±0.5%
±1.0% ±0.5%±1.0%
105 ~ 115% rated output power
OVERLOAD
Protection type : Constant current limiting, unit will shutdown after 5 sec, re-power on to recover
43A 22.5A 11.3A
722.4W 756W 759.36W
RATED POWER
RIPPLE & NOISE(max.)
180mVp-p 300mVp-p 480mVp-p
294.5K hrs min. Telcordia SR-332 (Bellcore) ; 95.7K hrs min. MIL-HDBK-217F (25 )
1.84Kg; 4pcs/ 9Kg / 1.63CUFT
Class B
SPECIFICATION for (Selectable via pin3 & 4 jumper of 14pins connector on panel)
Power Supply mode
-30 ~ +70
(Refer to "Derating Curve")
The TTL signal out, = H(4.5 ~ 5.5V) ; Power supply failure or protection = L(-0.5 ~ +0.5V)DC OK
1. Modification for charger specification may be required for different battery specification. Please contact battery vendor and MEAN WELL for details.
2. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
3. Derating may be needed under low input voltages. Please check the derating curve for more details.
4. PSU All the radiation tests require an additional 13 26 30 NIZN magnetic The is considered a component which will be installed into a final equipment. **
clasp or magnetic ring to the output line for CLASS B and without NIZN magnetic clasp or magnetic ring for CLASS A. The final equipment must be
re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
5. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
Product Liability Disclaimer For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
CB IEC62368-1, , Dekra BS EN/EN62368-1, , UL62368-1, EAC TP TC 004 approvedIEC60335-1/2-29 BS EN/EN60335-1/2-29
750W High Reliable Ultra Wide Output Range Battery Charger & Power Supply 2-in-1
NPP-750 series