Datasheet
SPECIFICATION
600W Single Output Battery Charger
HEP-600C series
File Name:HEP-600C-SPEC 2018-04-26
HEP-600C-12 HEP-600C-24 HEP-600C-48
MODEL
BOOST CHARGE VOLTAGE Vboost
FLOAT CHARGE VOLTAGE Vfloat
OUTPUT CURRENT
BATTERY TYPE
RECOMMENDED BATTERY
CAPACITY(AMP HOURS)
(Note 3)
OUTPUT
VOLTAGE RANGE
FREQUENCY RANGE
INPUT
ENVIRONMENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
OVER VOLTAGE
PROTECTION
AC CURRENT (Typ.)
14.4V 28.8V 57.6V
13.6V
11.5 ~ 15.1V
17.5 ~ 35A
35A
Open & Sealed Lead Acid
135 ~ 400AH
27.2V
23 ~ 30.2V
10.5 ~ 21A
54.4V
46.1 ~ 60.5V
5.2 ~ 10.5A
21A 10.5A
70 ~ 210AH 35 ~ 105AH
90 ~ 305VAC 127 ~ 431VDC
47 ~ 63Hz
93.5% 94.5% 95.5%
7A / 115VAC 3.3A / 230VAC 2.9A / 277VAC
<0.75mA / 277VAC
16.5 ~ 20.5V 32.5 ~ 36.5V 68 ~ 73V
-40 ~ +70 (Refer to "Derating Curve")℃
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH℃
non-condensing
±℃℃0.05%/ (0 ~ 60 )
20 ~ 500Hz, 10G 10min./1cycle, 72min. each along X, Y, Z axes
NOTE
1. Modification for charger specification may be required for different battery specification. Please contact battery vendor and MEAN WELL for details.
2. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
3. This is Mean Well's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation.
4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
5. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
POWER FACTOR (Typ.) PF>0.98/115VAC, PF>0.95/230VAC, PF>0.93/277VAC at full load
I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
℃
SAFETY STANDARDS
MTBF
DIMENSIONOTHERS
PACKING
Compliance to ,EN55032 (CISPR32), radiation class A, conduction class B, EN61000-3-2,-3 EAC TP TC 020
Compliance to ,
EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level EAC TP TC 020
UL60950-1, TUV EN60950-1 EAC TP TC 004 approved
,
73.1K hrs min. MIL-HDBK-217F (25 )
℃
280*144*48.5mm (L*W*H)
3.9Kg; 4pcs/16Kg/0.9CUFT
SAFETY &
EMC
(
Note.4)
EMC IMMUNITY
EMC EMISSION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
VOLTAGE ADJ. RANGE
CURRENT ADJ. RANGE
EFFICIENCY (Typ.)
COLD START 70A(t =1010 s measured at 50% I ) at 230VACwidth peak
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, re-power on to recover
FUNCTION
REMOTE ON/OFF CONTROL
5V STANDBY
Power on : "Hi" >2 ~ 5V or Open circuit Power off : "Low" <0 ~ 0.5V or Short circuit
5V : 5V@0.5A ; tolerance 5%, ripple : 100mVp-p(max.)
SB ±
μ