Datasheet
1000W Power Supply for Harsh EnvironmentSwitching
105~125% rated output power
SPECIFICATION FOR POWER SUPPLY
OVER TEMPERATURE
DIMENSION
OTHERS
NOTE
OVERLOAD
OVER VOLTAGE
197.9K hrs min. Telcordia SR-332 (Bellcore) ; 52.32K hrs min. MIL-HDBK-217F (25 )℃
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : line regulation and load regulation.includes set up tolerance,
4. Derating may be needed under low input voltages. Please check the for more details.derating curve
5. PV/PC functions when users do not use SVR.
6. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.720 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
7. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
PROTECTION
310*144*48.5mm (L*W*H)
Protection type :Shut down O/P voltage,re-power on to recover
Protection type :Shut down O/P voltage, recovers automatically after temperature goes down
4Kg;4pcs/17Kg/1.04CUFT
Protection type : Constant current limiting, unit will shutdown after 5 sec, re-power on to recover.
FUNCTION
REMOTE ON/OFF CONTROL
AUXILIARY POWER
DC-OK SIGNAL
Power ON : Short circuit Power OFF : Open circuit
12V @ 0.5A tolerance 10%, ripple=150mVp-p±
The TTL signal out, PSU turn on = 4.4 ~ 5.5V ; PSU turn off = -0.5 ~ 0.5V. Please refer to the Function Manual.
SAFETY STANDARDS
SAFETY &
EMC
(Note.6)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:1.25KVAC
I/P-O/P, I/P-FG,O/P-FG:100M Ohms/500VDC/25 / 70%RH℃
UL62368-1,TUV EN62368-1, EAC TP TC 004 approved; design refer to EN61558-1, EN60335-1(by request)
HEP-1000 series
File Name:HEP-1000-SPEC 2019-09-25
MTBF
PACKING
Adjustment of output voltage is allowable to 50 ~ 125% of nominal output voltage
Please refer to the Function Manual.
Adjustment of constant current level is allowable to 20 ~ 100% of rated current.
Please refer to the Function Manual.
OUTPUT VOLTAGE
PROGRAMMABLE(PV)
Note 5
OUTPUT CURRENT
PROGRAMMABLE(PC)
Note 5
SHORT CIRCUIT
Constant current limiting, unit will shutdown after 5 sec, re-power on to recover.
MODEL
DC VOLTAGE
RATED CURRENT
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.4
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT(Typ.)
LEAKAGE CURRENT
1800ms, 80ms at full load 230VAC /115VAC
16ms / 230VAC at 75% load 12ms / 230VAC at full load
90 ~ 305VAC 250 ~ 431VDC
47 ~ 63Hz
PF>0.99/115VAC, PF>0.95/230VAC, PF>0.93/277VAC at full load
10.1A / 115VAC 5.3A / 230VAC 4.5A / 277VAC
<0.75mA / 240VAC
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE
Note.3
95%
96%
±1.0% ±1.0%±1.0%
±0.5% ±0.5%±0.5%
±0.5% ±0.5%±0.5%
HEP-1000-24 HEP-1000-100HEP-1000-48
24V 100V48V
42A 10A21A
1008W 1000W1008W
200mVp-p
24 ~ 30V
500mVp-p250mVp-p
100 ~ 125V48 ~ 60V
Cold start 40A at 230VAC
96%
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-40 ~ +70 (Refer to "Derating Curve")℃
20 ~ 95% RH non-condensing
-40 ~ +80 , 10 ~ 95% RH
℃ non-condensing
±℃ ℃
0.03%/ (0 ~ 50 )
20 ~ 500Hz, 10G 12min./1cycle, period for 72min. each along X, Y, Z axes
ENVIRONMENT
By built-in potentiometer, SVR
125 ~ 145V
30 ~ 35V
60 ~ 70V
EMC IMMUNITY
EMC EMISSION
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
EN55024 , EN61000-6-2
Standard
Standard
EN55032 (CISPR32)
EN55032 (CISPR32)
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-6-2
EN61000-4-6
EN61000-4-8
EN61000-4-11
Test Level / Note
Test Level / Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
2KV/Line-Line 4KV/Line-Earth
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class B
Class B
Class A
-----