Datasheet
SPECIFICATION
File Name:GSM220B-SPEC 2015-10-29
ORDER NO.
DC VOLTAGE Note.2
SAFETY MODEL NO.
RATED CURRENT
CURRENT RANGE
RATED POWER (max.)
RIPPLE & NOISE (max.) Note.3
OUTPUT
VOLTAGE RANGE Note.7
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INPUT
ENVIRONMENT
INRUSH CURRENT (max.)
LEAKAGE CURRENT(max.)
SAFETY STANDARDS
SAFETY &
EMC
(Note. 8)
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSION
OTHERS
NOTE
PACKING
PROTECTION
GSM220B15
GSM220B15-R7B
GSM220B12
GSM220B12-R7B
GSM220B20
GSM220B20-R7B
GSM220B24
GSM220B24-R7B
GSM220B48
GSM220B48-R7B
15V12V 20V 24V 48V
100mVp-p80mVp-p 150mVp-p 180mVp-p 240mVp-p
VOLTAGE TOLERANCE Note.4
LINE REGULATION Note.5
LOAD REGULATION
±5.0%±5.0% ±4.0% ±3.0% ±2.0%
±1.0%±1.0% ±1.0% ±1.0% ±1.0%
±5.0%±5.0% ±4.0% ±3.0% ±2.0%
80 ~ 264VAC 113 ~ 370VDC
47 ~ 63Hz
PF>0.91 / 230VAC PF>0.98 / 115VAC at full load
90%90% 92% 93.5%
94.5%
4A / 115VAC 2A / 230VAC
120A / 230VAC
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
208.66K hrs min. MIL-HDBK-217F(25℃)
-30 ~ +70℃ (Refer to "Derating Curve")
20% ~ 90% RH non-condensing
-40 ~ +85℃, 10 ~ 95% RH
±0.03% / ℃ (0~50℃)
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
210*85*46mm (L*W*H)
1.1Kg; 12pcs/14.2Kg/0.73CUFT
CONNECTOR
PLUG
CABLE
See page 3 ; Other type available by customer requested
See page 3 ; Other type available by customer requested
℃
For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
OVERLOAD
OVER VOLTAGE
105 ~ 135% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
105 ~ 135% rated output voltage
13.4A15A 11A 9.2A 4.6A
0 ~ 13.4A0 ~ 15A 0 ~ 11A 0 ~ 9.2A
0 ~ 4.6A
201W180W 220W 221W 221W
Protection type : Shut down o/p voltage, re-power on to recover
SETUP, RISE TIME Note.6
HOLD UP TIME (Typ.)
2000ms, 50ms / 230VAC 2000ms, 50ms / 115VAC at full load
20ms / 230VAC 20ms / 115VAC at full load
OVER TEMPERATURE
Shut down o/p voltage, recovers automatically after temperature goes down
EMC IMMUNITY
EMC EMISSION
GSM220B seri e s
Touch current < 100 A/264VAC
I/P-O/P: 4KVAC
I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH℃
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN60601-1-2, EN61204-3 medical level, criteria A
ANSI/AAMI ES60601-1 / ES60601-1-11, TUV EN60601-1 / EN60601-1-11 approved
Compliance to EN55011(CISPR11) class B, EN61000-3-2,3, FCC PART 15 class B
ISOLATION LEVEL
Primary-Secondary: 2xMOPP
220W AC-DC High Reliability Medical Adaptor