Datasheet

SPECIFICATION
40W Single Output with Battery Charger (UPS Function)
DRC-40 series
File Name:DRC-40-SPEC 2014-09-13
MODEL
DC VOLTAGE
OUTPUT NUMBER
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
Note.4
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
SAFETY STANDARDS
WORKING TEMP.
BATTERY CUT OFF
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
400ms, 50ms/230VAC 800ms, 50ms/115VAC at full load
50ms/230VAC 10ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
47 ~ 63Hz
86%
CH1:28.98 ~ 37.26V
20 1V±
87%
0.8A/115VAC 0.6A/230VAC
COLD START 30A/115VAC 60A/230VAC
105 ~ 150% rated output power
CH1:14.49 ~ 18.63V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
UL60950-1, TUV EN60950-1 approved
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A
-30 ~ +70 (Refer to "Derating Curve")
10 0.5V±
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
±℃ 0.03%/ (0 ~ 55 ) on CH1 output
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
536.6K hrs min. MIL-HDBK-217F (25 )
40*90*100mm (W*H*D)
0.3Kg; 42pcs/13.6Kg/0.82CUFT
DRC-40B
27.6V13.8V 27.6V
CH1CH2 CH2
0.95A1A 0.5A
0 ~ 1.45A-------- --------
40.02W
200mVp-p-------- --------
-------- --------
-------- --------
-------- --------
CH1:24 ~ 30V
±1.0%
±0.5%
±0.5%
DRC-40A
13.8V
CH1
1.9A
0 ~ 2.9A
40.02W
120mVp-p
CH1:12 ~ 15V
±1.0%
±0.5%
±0.5%
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE Note.3
ENVIRONMENT
PROTECTION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
SAFETY &
EMC
(Note 5)
EMC IMMUNITY
EMC EMISSION
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power
supplies. (as available on http://www.meanwell.com)
6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.