Data Sheet

SPECIFICATION
DDR-60 series
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.4
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVER VOLTAGE
DC CURRENT (Typ.)
G-type: 5ms@24Vdc input
9 ~ 36Vdc
20A /24Vdc
-40 ~ +85 (Refer to "Derating Curve")
5 ~ 95% RH non-condensing
-40 ~ +85 , 5 ~ 95% RH non-condensing
±℃℃0.03%/ (0 ~60 )
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
611K hrs min. MIL-HDBK-217F (25 )
52.5*90*54.5mm (W*H*D)
216g; 60pcs/14Kg/0.97CUFT
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:4KVdc
I/P-O/P>100M Ohms / 500Vdc / 25 / 70% RH
ENVIRONMENT
SAFETY &
EMC
(Note 5)
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
L-type: 10ms@48Vdc input
18 ~ 75Vdc
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Conducted
Radiated
Voltage Flicker
Standard
Standard
EN55032
EN55032
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
Test Level / Note
Test Level / Note
Class A
Class A for 1m I/O cable , Class B for 30cm I/O cable
-----
EMC IMMUNITY
EMC EMISSION
EN55024 , EN61000-6-2(EN50082-2)
Level 3, 8KV air ; Level 3, 6KV contact; criteria A
Level 3, 10V/m ; criteria A
Level 4, 30A/m ; criteria A
Level 3, 10V ; criteria A
Level 3, 2KV ; criteria A
3A /24Vdc 1.5A /48Vdc
20A /48Vdc
DDR-60G-5
5V
10.8A
0 ~ 10.8A
54W
60mVp-p
4.5 ~ 5.5V
±2.0%
±0.5%
±1.5%
87.5%
5.75 ~ 7V
DDR-60G-12
12V
5A
0 ~ 5A
60W
75mVp-p
9 ~ 13.2V
±2.0%
91%
13.8 ~ 16.2V
DDR-60G-15
15V
4A
0 ~ 4A
60W
75mVp-p
13.5 ~ 16.5V
±2.0%
91%
17.25 ~ 20.25V
DDR-60G-24
24V
2.5A
0 ~ 2.5A
60W
100mVp-p
21.6 ~ 28V
±2.0%
91%
28.8 ~ 34V
5V
12A
0 ~ 12A
60W
60mVp-p
DDR-60L-5
4.5 ~ 5.5V
±2.0%
87.5%
5.75 ~ 7V
DDR-60L-12
12V
5A
0 ~ 5A
60W
75mVp-p
9 ~ 13.2V
±2.0%
91%
13.8 ~ 16.2V
DDR-60L-15
15V
4A
0 ~ 4A
60W
75mVp-p
13.5 ~ 16.5V
±2.0%
92%
17.25 ~ 20.25V
DDR-60L-24
24V
2.5A
0 ~ 2.5A
60W
100mVp-p
21.6 ~ 28V
±2.0%
92%
28.8 ~ 34V
6800 F
μ
OVERLOAD
REVERSE POLARITY
By internal MOSFET, no damage, recovers automatically after fault condition removed
1. All parameters NOT specially mentioned are measured at normal input (G:24Vdc, L:48Vdc), rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1 f & 47 f parallel capacitor.μμ
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltage. Please check the derating curve for more details.
5.The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC
directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
6. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft)℃℃
.
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
4700 F
μ
3300 F
μ
2200 F
μ
6800 F
μ
4700 F
μ
3300 F
μ
2200 F
μ
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±1.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
120ms, 85ms at full load
EXTERNAL CAPACITANCE
LOAD (Max.)
IEC 62368-1 (LVD) approved, Design refer to UL508
UNDER VOLTAGE LOCKOUT
48Vin (L-type):Power V , FF VON 18 O 17≥≤
60W DIN Rail Type DC-DC Converter
24Vin (G-type):Power V , FF VON 9 O 8.5≥≤
Level 3, 1KV/Line-Line ; criteria A
File Name:DDR-60-SPEC 2018-02-02
OPERATING ALTITUDE
2000 meters