Specifications
22 MDS Orbit MCR-4G Technical Manual MDS 05-6628A01, Rev. A
Example #3
Figure 13 shows the MCR-4G #2 device acts as a terminal server to provide connectivity to the serial-based
SCADA device via UDP.
Invisible place holder
Figure 13. Example 3: Unit Providing Connectivity to Serial-Based SCADA Device via UDP
The following commands will configure the MCR-4G #2 for this scenario.
1. %setinterfacesinterfaceWi‐Fiphysical‐interfaceWi‐Fiwifi‐configmodestationstation‐configap
myssidenabledtrue
2. %setinterfacesinterfacemyBridgevirtual‐typebridge
3. %setinterfacesinterfacemyBridgebridge‐settingsportsportETH1
4. %setinterfacesinterfacemyBridgebridge‐settingsportswifi‐stationinterfaceWi‐Fi
5. %setinterfacesinterfacemyBr
idgeipv4address192.168.1.22prefix‐length24
6. %setservicesserialterminal‐serverserverCOM1modeudpport30000remoteaddress
192.168.1.11port30001
Ethernet
Ethernet
SCADA Device
serial
WiFi
SCADA
application
192.168.1.11
WiFi Access
Point
WiFi Access
Point
MCR-4G #2
192.168.1.22
MCR-4G #1
192.168.1.21