User`s guide
72 MDS iNET 900 Series User’s Guide MDS 05-2806A01, Rev. E.1
Operation and Data Flow
• Communicate with RTU A by Telneting to Remote 1, port 30011.
• Communicate with RTU B by Telneting to Remote 2, port 30011.
• Communicate with RTUs C and D by sending and receiving data
from the Access Point’s
COM port.
• All communication paths can be used simultaneously.
Invisible place holder
Figure 3-36. Mixed-Modes Application Diagram
EIA-232
Terminal
or Computer
RTU–C
EIA-232
EIA-232
EIA-232
RTU–D
EIA-232
LA
N
COM
1
COM
2
PW
R
LIN
K
iNET 900
Remote 4
Ethernet
Crosssover
RTU–B
RTU–A
iNET 900
Access Point
LA
N
COM
1
COM
2
PW
R
LIN
K
iNET 900
Remote 1
LA
N
COM
1
COM
2
PW
R
LIN
K
iNET 900
Remote 2
LA
N
COM
1
COM
2
PW
R
LIN
K
iNET 900
Remote 3
Table 3-4. Serial Port Application Configuration
Transceiver Location Menu Item Setting
Access Point Status Enabled
Baud Rate 9,600
Flow Control Disabled
IP Protocol UDP
Send to Address A multicast IP address such as
224.254.1.1
Send to Port 30011
Receive on Port 30011
Receive on Address 0.0.0.0 (Not Used)
Remote Units 1 & 2
(COM2)
Status Enabled
Baud Rate 2,400
Flow Control Disabled
IP Protocol TCP
Receive on Port 30011
Remote Units 3 & 4
(COM2)
Status Enabled
Baud Rate 9,600
Flow Control Disabled