Product manual
KPMWC00905-10EN - page 4/24
Versions
WMC is available in high efficiency version:
XE: High Efficiency
6 sizes to cover a range from 317 up to 1048 kW (Cooling Capacity), with EER up to 6.00 and
ESEER up to 9.60.
The EER (Energy Efficiency Ratio) is the ratio of the Cooling Capacity to the Power Input of the
unit. The Power Input includes: the power input for operation of the compressor, the power input
of all control and safety devices.
The ESEER (European Seasonal Energy Efficiency Ratio) is a weighed formula enabling to take
into account the variation of EER with the load rate and the variation of water inlet condenser
temperature.
ESEER = A x EER
100%
+ B x EER
75%
+ C x EER
50%
+ D x EER
25%
A B C D
Coefficient 0.03 (3%) 0.33 (33%) 0.41 (41%) 0.23 (23%)
Condenser water inlet temperature (°C) 30 26 22 18
Noise Configuration
WMC is available in standard noise level configuration:
ST: Standard Noise