Instruction manual
Table Of Contents
- Introduction
- Using the Keypad/Display
- Keypad/Display Menu Structure
- System Summary Menu
- Standard Menus
- System Menu
- Occupancy Menu
- Temperature Menu
- Flow Summary Menu
- Supply Fan Speed Menu
- Return/Exhaust Fan Speed Menu
- Cooling Menu
- Head Pressure Menu
- Evap Condensing Menu
- Economizer Menu
- Min OA Damper Menu
- Heating Menu
- Energy Recovery
- Dehumidification Menu
- Daily Schedule Menu
- One Event Schedule Menu
- Holiday Schedule Menu
- Optimal Start Menu
- Operating Hours Menu
- Extended Menus
- Unit Setup Menu
- Timer Settings Menu
- Time/Date Menu
- Supply Fan Setup Menu
- Return/Exhaust Fan Setup Menu
- Zone Temperature Setup Menu
- Compressor Setup Menu
- Head Pressure Setup Menu
- Chilled Water Setup Menu
- Economizer Setup Menu
- Design Flow Setup Menu
- Heating Setup Menu
- Dehumidification Setup Menu
- Alarm Out Configuration Setup Menu
- Alarm Limits Setup Menu
- Manual Control Menu
- LON/BACnetIP/BACnetMSTP Setup Menu
- Active Alarm Menu
- Alarm Log Menu
- Advanced Menus
- Unit Configuration Setup Menu
- Save/Restore Menu
- Alarm Delays Setup Menu
- Analog Input Status Menu
- Universal I/O Status Menu
- Digital Input Status Menu
- Digital Output Status Menu
- Adv Setup Settings Menu
- Adv Status Parameters Menu
- Alarms
- Operator’s Guide
- Determining Unit State
- Off Operating State
- Start Up Operating State
- Recirculating Operating State
- Heating
- Economizer
- Mechanical Cooling
- Determining Unit Status
- Determining Control Mode
- Determining Cooling Status
- Determining Heat Status
- Determining Economizer Status
- Determining Cooling Capacity
- Determining Heating Capacity
- Determining Supply Air Fan Capacity
- Determining RF/EF Capacity
- Determining Outside Air Damper Position
- Determining Emergency Mode
- Determining Application Mode
- Determining Occupancy Status
- Determining Occupancy Mode
- Determining Occupancy Source
- Unoccupied Operation
- Scheduling
- Temperature Control Configurations
- Heat/Cool Changeover
- Dehumidification
- Energy Recovery
- Outside Air Damper Control
- Outside Air Damper Control, Two Position
- Special Procedures for Units with WRV and More Than Two Circuits.
- Water Pump Control
- Cooling: Multistage
- Cooling: Modulating
- Heating Control
- Modulating
- Min DAT
- Indoor Air Fan - On/Off Control

82 McQuay OM 920
Operator’s Guide
Exhaust Fan
A variable speed exhaust fan controlled by a VFD is provided for all Economizer units with
either Constant Volume or VAV Supply Fans and on 100% Outside Air units with VAV Supply
Fans. Either a constant volume exhaust fan or a variable speed exhaust fan controlled by a
VFD may be provided on 100% Outside Air units with Constant Volume Discharge Fans.
The exhaust fan is turned on when one of the following sets of conditions is true:
All four of the following are true:
• The Exhaust Fan is controlled by a VFD
• The OA Dampers are at least open to the Minimum OA Position
• The Minimum OA Position is greater than 0%
• The building static pressure is above the building static pressure setpoint by more than the
deadband for longer than the Minimum Exhaust Fan Start Time (Default = 120 seconds)
OR
All four of the following are true:
• The Exhaust Fan is controlled by a VFD
• The OA Dampers are at least open to the Minimum OA Position
• The Minimum OA Position is greater than 0%
• The Exhaust Fan capacity is commanded to a value above the minimum value (Default =
5%) by a BAS for longer than the Minimum Exhaust Fan Start Time (Default = 120
seconds)
OR
• The Exhaust Fan is Constant Volume AND
• The Supply Fan has been commanded on for at least 4 seconds
The exhaust fan is turned off when one of the following sets of conditions is true:
All three of the following are True:
• The Exhaust Fan is controlled by a VFD
• The building static pressure is below the building static pressure setpoint by more than the
deadband
• The Exhaust Fan capacity is at or below its minimum value (Default = 5%) for longer than
the Min Exhaust Fan Stop Time (Default = 120 seconds)
OR
Both of the following are True:
• The Exhaust Fan is controlled by a VFD
• The Exhaust Fan capacity is commanded to less than or equal to its minimum value (Default
= 5%) by the BAS for longer than the Minimum Exhaust Fan Stop Time (Default = 120
seconds)
OR
• The Supply Fan is Off
Whenever a variable speed exhaust fan is on, its capacity will be modulated using a VFD. The
speed of the fan will be either (1) modulated to maintain the building static pressure at a
desired value or (2) set at a fixed speed provided by a Building Automation System via a
network.