Instruction manual
Table Of Contents
- Introduction
- Using the Keypad/Display
- Keypad/Display Menu Structure
- System Summary Menu
- Standard Menus
- System Menu
- Occupancy Menu
- Temperature Menu
- Flow Summary Menu
- Supply Fan Speed Menu
- Return/Exhaust Fan Speed Menu
- Cooling Menu
- Head Pressure Menu
- Evap Condensing Menu
- Economizer Menu
- Min OA Damper Menu
- Heating Menu
- Energy Recovery
- Dehumidification Menu
- Daily Schedule Menu
- One Event Schedule Menu
- Holiday Schedule Menu
- Optimal Start Menu
- Operating Hours Menu
- Extended Menus
- Unit Setup Menu
- Timer Settings Menu
- Time/Date Menu
- Supply Fan Setup Menu
- Return/Exhaust Fan Setup Menu
- Zone Temperature Setup Menu
- Compressor Setup Menu
- Head Pressure Setup Menu
- Chilled Water Setup Menu
- Economizer Setup Menu
- Design Flow Setup Menu
- Heating Setup Menu
- Dehumidification Setup Menu
- Alarm Out Configuration Setup Menu
- Alarm Limits Setup Menu
- Manual Control Menu
- LON/BACnetIP/BACnetMSTP Setup Menu
- Active Alarm Menu
- Alarm Log Menu
- Advanced Menus
- Unit Configuration Setup Menu
- Save/Restore Menu
- Alarm Delays Setup Menu
- Analog Input Status Menu
- Universal I/O Status Menu
- Digital Input Status Menu
- Digital Output Status Menu
- Adv Setup Settings Menu
- Adv Status Parameters Menu
- Alarms
- Operator’s Guide
- Determining Unit State
- Off Operating State
- Start Up Operating State
- Recirculating Operating State
- Heating
- Economizer
- Mechanical Cooling
- Determining Unit Status
- Determining Control Mode
- Determining Cooling Status
- Determining Heat Status
- Determining Economizer Status
- Determining Cooling Capacity
- Determining Heating Capacity
- Determining Supply Air Fan Capacity
- Determining RF/EF Capacity
- Determining Outside Air Damper Position
- Determining Emergency Mode
- Determining Application Mode
- Determining Occupancy Status
- Determining Occupancy Mode
- Determining Occupancy Source
- Unoccupied Operation
- Scheduling
- Temperature Control Configurations
- Heat/Cool Changeover
- Dehumidification
- Energy Recovery
- Outside Air Damper Control
- Outside Air Damper Control, Two Position
- Special Procedures for Units with WRV and More Than Two Circuits.
- Water Pump Control
- Cooling: Multistage
- Cooling: Modulating
- Heating Control
- Modulating
- Min DAT
- Indoor Air Fan - On/Off Control

80 McQuay OM 920
Operator’s Guide
Energy Recovery
Energy recovery is provided by drawing outside air across half of an Enthalpy Wheel and
drawing exhaust air across the other half. Latent and sensible heat is transferred from the
hotter, moister exhaust air to the colder dryer outside air in winter. Latent and sensible heat is
transferred from the hotter more moist outside air to the cooler dryer air exhaust in summer.
Control consists of starting and stopping an exhaust fan, modulating the speed of the exhaust
fan, starting and stopping the Enthalpy Wheel, and optionally controlling the speed of the
Enthalpy Wheel. The outdoor dampers are controlled in the normal manner. The current
statuses as well as editable parameters associated with Energy Recovery are located in the
Standard Menus/Energy Recovery menus.
Enthalpy Wheel
The Enthalpy Wheel is turned on when all of the following are true.
• The Exhaust Fan is on
• The OA Dampers are at the minimum position
• The unit is not in the Economizer State
• The wheel has not been turned off due to Frosting/Condensation
Note – When turned on the speed of the enthalpy wheel is set to the maximum speed for units
with a VFD controlling the speed of the Enthalpy Wheel.
The Enthalpy Wheel is turned off when any of the following is true
• The Exhaust Fan is off OR
• The OA Damper Position is driven above the Minimum OA Damper Position by more than
3%
Additional control is provided for units with a VFD controlling the speed of the Enthalpy
Wheel to prevent Frosting/Condensation on the Enthalpy Wheel. This control is based on an
Intersection Point described in paragraphs that follow.
The Enthalpy Wheel VFD speed is set to zero so it will operate at its internally edited
minimum speed when both of the following are true:
• The wheel has been operating at maximum speed for longer than the edited Wheel Stage
Time
• The exhaust air temperature leaving the Enthalpy wheel is below the Intersection Point plus
an edited Minimum Temperature Difference
To prevent Frosting/Condensation on the Enthalpy Wheel, the Enthalpy Wheel is turned off
when both of the following are true:
• The exhaust air temperature leaving the Enthalpy wheel is below the Intersection Point plus
an edited Minimum Temperature Difference
• The wheel has been operating at its internally edited minimum speed for longer than an
edited Wheel Stage Time
The Enthalpy Wheel is turned on at minimum speed when:
• The Wheel has been off due to Frosting/Condensation for longer than an edited Minimum
off Time
• The exhaust air temperature leaving the Enthalpy wheel is above the Intersection Point plus
an edited Maximum Temperature Difference
The Enthalpy Wheel speed will be increased to its maximum speed when:
• The exhaust air temperature leaving the Enthalpy wheel is above the Intersection Point plus
an edited Maximum Temperature Difference
• The Wheel has been operating at Minimum Speed for longer than the edited Wheel Stage
Time