Instruction manual

Table Of Contents
McQuay OM 920 79
Operators Guide
Dehumidification Mechanical Cooling Control
During Dehumidification, control of Mechanical Cooling is based on the following two
editable values of the Leaving Coil Temperature setpoint. The Leaving Coil Temperature
setpoint parameter is adjustable via the following path: Extended Menus/Dehum Setup/Mn
Lvg Coil T or Mx Lvg Coil T.
Mx Lvg Coil T (Default = 55°F)
Mn Lvg Coil T (Default = 48°F)
For compressorized units, the number of Compressor Stages increases when:
The time since the last stage change exceeds the Clg Stage Time AND
Leaving Coil Temperature is greater than the Mx Lvg Coil T AND
The current cooling stage is less than the available number of stages
During the dehumidification mode, the number of Compressor Stages decreases when:
The time since the last stage change exceeds the Clg Stage Time AND
Leaving Coil Temperature is less than Mn Lvg Coil T Spt AND
The current cooling stage is greater than zero
Units with modulated cooling are controlled by a PI Loop to maintain the temperature leaving
the coil at the Mn Lvg Coil T. The normal DAT Cooling Deadband and PI Loop parameters
are used in this PI Loop.
Hot Gas Reheat Control
During Dehumidification control an analog Hot Gas Reheat (HGRH) output is controlled as
described below.
Cooling/Fan Only: In the Cooling and Fan Only states, a PI Loop is used to control the
HGRH valve to maintain the Discharge Air Temperature at the Dehumidification Reheat
Setpoint. The deadband for this loop is the same one used for other control of heating to
maintain the DAT Heating setpoint.
Cooling: In the Cooling state, the Dehumidification Reheat Setpoint equals the DAT
Cooling Setpoint. For DAT units, this is the normal DAT setpoint resulting from any reset.
For Zone Control units, this setpoint is the result of a PI Loop based on the Control
Temperature as is done in the Economizer state or with modulated cooling in the Cooling
state.
Fan Only: In the Fan Only state, the Dehumidification Reheat Setpoint equals an editable
MaxReheatSpt (Default = 65°F) when the Control Temperature drops to the Zone Heating
setpoint and equals an editable MinReheatSpt (Default = 55°F) when the Control
Temperature rises to the Zone Cooling setpoint. The Dehumidification Reheat Setpoint
varies linearly between these two points.
This means that no matter what the Control temperature is, including OAT, the temperature
leaving the unit is at a maximum just before the unit needs to go into heating and at a
minimum just before the unit needs to go into Cooling. This reduces opportunity for unit to go
into heating or cooling during Dehumidification. The Dehumidification Reheat Setpoints are
editable via the path, Extended Menus/Dehum Setup/Min Rheat Spt or Max Rheat Spt.
Staged HGRH Control
In the Cooling and Fan Only states, a staged output is turned on and off to control the HGRH
valve to maintain the Discharge Air Temperature at the Dehumidification Reheat Setpoint.
The deadband for this setpoint is the same one used for other control of heating to maintain the
DAT Heating setpoint. When the DAT is above the Dehumidification Reheat Setpoint by more
than half the deadband, cooling capacity is greater than 0% and the Dehumidification Reheat
Timer is expired, the reheat output is turned on. When the DAT is below the Dehumidification
Reheat Setpoint by more than half the deadband and the Dehumidification Reheat Timer is
expired, or if the cooling capacity is 0%, the reheat output is turned off.