Instruction manual
Table Of Contents
- Introduction
- Using the Keypad/Display
- Keypad/Display Menu Structure
- System Summary Menu
- Standard Menus
- System Menu
- Occupancy Menu
- Temperature Menu
- Flow Summary Menu
- Supply Fan Speed Menu
- Return/Exhaust Fan Speed Menu
- Cooling Menu
- Head Pressure Menu
- Evap Condensing Menu
- Economizer Menu
- Min OA Damper Menu
- Heating Menu
- Energy Recovery
- Dehumidification Menu
- Daily Schedule Menu
- One Event Schedule Menu
- Holiday Schedule Menu
- Optimal Start Menu
- Operating Hours Menu
- Extended Menus
- Unit Setup Menu
- Timer Settings Menu
- Time/Date Menu
- Supply Fan Setup Menu
- Return/Exhaust Fan Setup Menu
- Zone Temperature Setup Menu
- Compressor Setup Menu
- Head Pressure Setup Menu
- Chilled Water Setup Menu
- Economizer Setup Menu
- Design Flow Setup Menu
- Heating Setup Menu
- Dehumidification Setup Menu
- Alarm Out Configuration Setup Menu
- Alarm Limits Setup Menu
- Manual Control Menu
- LON/BACnetIP/BACnetMSTP Setup Menu
- Active Alarm Menu
- Alarm Log Menu
- Advanced Menus
- Unit Configuration Setup Menu
- Save/Restore Menu
- Alarm Delays Setup Menu
- Analog Input Status Menu
- Universal I/O Status Menu
- Digital Input Status Menu
- Digital Output Status Menu
- Adv Setup Settings Menu
- Adv Status Parameters Menu
- Alarms
- Operator’s Guide
- Determining Unit State
- Off Operating State
- Start Up Operating State
- Recirculating Operating State
- Heating
- Economizer
- Mechanical Cooling
- Determining Unit Status
- Determining Control Mode
- Determining Cooling Status
- Determining Heat Status
- Determining Economizer Status
- Determining Cooling Capacity
- Determining Heating Capacity
- Determining Supply Air Fan Capacity
- Determining RF/EF Capacity
- Determining Outside Air Damper Position
- Determining Emergency Mode
- Determining Application Mode
- Determining Occupancy Status
- Determining Occupancy Mode
- Determining Occupancy Source
- Unoccupied Operation
- Scheduling
- Temperature Control Configurations
- Heat/Cool Changeover
- Dehumidification
- Energy Recovery
- Outside Air Damper Control
- Outside Air Damper Control, Two Position
- Special Procedures for Units with WRV and More Than Two Circuits.
- Water Pump Control
- Cooling: Multistage
- Cooling: Modulating
- Heating Control
- Modulating
- Min DAT
- Indoor Air Fan - On/Off Control

72 McQuay OM 920
Operator’s Guide
Determining Occupancy Mode
Occ Mode is an adjustable item which sets the unit for manual occupied, unoccupied, tenant
override or automatic operation. The parameter is adjustable via the following path: Standard
Menu/Occupancy/Occ Mode.
Occ
When Occ Mode is set to “Occ,” the unit is manually placed in the occupied mode of
operation.
Unocc
When Occ Mode is set to “Unocc,” the unit is manually placed in the unoccupied mode of
operation.
TntOvrd
When Occ Mode is set to “TntOvrd,” the unit is manually placed in the tenant override mode
of operation.
Note – Once tenant override operation is activated the parameter automatically reverts back to
“Auto.”
Auto
When Occ Mode is set to “Auto” the automatically changes between occupied, unoccupied
and tenant override operation.
Determining Occupancy Source
When the Occupancy parameter indicates Occ, the Occupied Source is set to one of the
following values to indicate the function responsible for placing the unit into the occupied
mode of operation. The current Occupancy Source can be viewed via the following path:
Standard Menu/Occupancy/OccSrc.
None The Occ Src= parameter indicates “None” when the Occupancy= parameter indicates
“Unocc” or “Tnt Ovrd.”
NetSchedule The Occ Src= parameter indicates “Net Schd” when the Occupancy= parameter
indicates “Occ” due to a network schedule indicating an occupied period.
IntSchedule The Occ Src= parameter indicates “Int Sched” when the Occupancy= parameter
indicates “Occ” due to the unit internal Schedule.
OneEventSchedule The Occ Src= parameter indicates “Int Sched” when the Occupancy=
parameter indicates “Occ” due to the unit one event Schedule.
RemoteSwitch The Occ Src= parameter indicates “Remote Sw” when the Occupancy=
parameter indicates “Occ” due to a field supplied external time clock or a tenant override
switch signal in the form of a set of dry contacts is closed across terminals 101 and102 on the
unit field terminal block TB2.
OccManCmd The Occ Src= parameter indicates “OccManCmd” when OccMode is set to
Auto and the network manual occupancy command is set to Occupied.
OccMode The Occ Src= parameter indicates “Occ Mode” when the Occupancy= parameter
indicates “Occ” due to the Occupancy Mode being manually set to “Occ.”
TStatTO The Occ Src = parameter indicates “TStatTO” when the Occupancy= parameter
indicates “Occ” due to the tenant override button on the zone thermostat is pushed. The button
must be held for at least 1 second but not more than 30 seconds.
ManTO The Occ Src = parameter indicates “ManTO” when the Occupancy= parameter
indicates “Occ” due to the being manually set via the keypad/display. When the Tenant
Override Timer is set to a non-zero value, the unit starts and runs in the tenant override mode
regardless of any scheduling features. The unit stops when the timer expires. The Tenant
Override Timer can be set from 0-300 minutes.