Instruction manual
Table Of Contents
- Introduction
- Using the Keypad/Display
- Keypad/Display Menu Structure
- System Summary Menu
- Standard Menus
- System Menu
- Occupancy Menu
- Temperature Menu
- Flow Summary Menu
- Supply Fan Speed Menu
- Return/Exhaust Fan Speed Menu
- Cooling Menu
- Head Pressure Menu
- Evap Condensing Menu
- Economizer Menu
- Min OA Damper Menu
- Heating Menu
- Energy Recovery
- Dehumidification Menu
- Daily Schedule Menu
- One Event Schedule Menu
- Holiday Schedule Menu
- Optimal Start Menu
- Operating Hours Menu
- Extended Menus
- Unit Setup Menu
- Timer Settings Menu
- Time/Date Menu
- Supply Fan Setup Menu
- Return/Exhaust Fan Setup Menu
- Zone Temperature Setup Menu
- Compressor Setup Menu
- Head Pressure Setup Menu
- Chilled Water Setup Menu
- Economizer Setup Menu
- Design Flow Setup Menu
- Heating Setup Menu
- Dehumidification Setup Menu
- Alarm Out Configuration Setup Menu
- Alarm Limits Setup Menu
- Manual Control Menu
- LON/BACnetIP/BACnetMSTP Setup Menu
- Active Alarm Menu
- Alarm Log Menu
- Advanced Menus
- Unit Configuration Setup Menu
- Save/Restore Menu
- Alarm Delays Setup Menu
- Analog Input Status Menu
- Universal I/O Status Menu
- Digital Input Status Menu
- Digital Output Status Menu
- Adv Setup Settings Menu
- Adv Status Parameters Menu
- Alarms
- Operator’s Guide
- Determining Unit State
- Off Operating State
- Start Up Operating State
- Recirculating Operating State
- Heating
- Economizer
- Mechanical Cooling
- Determining Unit Status
- Determining Control Mode
- Determining Cooling Status
- Determining Heat Status
- Determining Economizer Status
- Determining Cooling Capacity
- Determining Heating Capacity
- Determining Supply Air Fan Capacity
- Determining RF/EF Capacity
- Determining Outside Air Damper Position
- Determining Emergency Mode
- Determining Application Mode
- Determining Occupancy Status
- Determining Occupancy Mode
- Determining Occupancy Source
- Unoccupied Operation
- Scheduling
- Temperature Control Configurations
- Heat/Cool Changeover
- Dehumidification
- Energy Recovery
- Outside Air Damper Control
- Outside Air Damper Control, Two Position
- Special Procedures for Units with WRV and More Than Two Circuits.
- Water Pump Control
- Cooling: Multistage
- Cooling: Modulating
- Heating Control
- Modulating
- Min DAT
- Indoor Air Fan - On/Off Control

McQuay OM 920 71
Operator’s Guide
Determining Occupancy Status
Occupancy is a status item which indicates whether the unit is in an occupied, unoccupied or
tenant override mode of operation. The current Occupancy status can be viewed via the
following path: Standard Menus/Occupancy/Occupancy. The following are descriptions of the
various “Occupancy” states.
Occ
The Occupancy parameter indicates “Occ” when the unit is in the occupied mode. In this
mode, the unit starts and runs continuously, cooling and heating as required to maintain the
occupied temperature set points. The unit is in the occupied mode if any of the following
conditions are true:
• The Occ Mode entry on the keypad is set to occupied
• The Occ Mode entry on the keypad is set to Auto, and a manual network occupancy
command is sent to the controller
• The Occ Mode entry on the keypad is set to Auto, a manual network occupancy command is
set to Auto, and any of the following is true:
• The External Start/Stop switch is closed
• A network schedule signal is set to Occupied or Standby
• The internal schedule function is in the Occupied condition
Unocc
The Occupancy parameter indicates “Unocc” when the unit is in the unoccupied mode. In this
mode, the unit remains off unless unoccupied operation becomes active. When unoccupied
operation is active the unit operates normally except that Minimum OA Position is set to zero.
See Unoccupied Operation below for information regarding when unoccupied operation is
activated.
TntOvrd
The Occupancy parameter indicates “TntOvrd” when the unit is in the tenant override mode.
In this mode, the unit starts and runs continuously, cooling and heating as required to maintain
the occupied temperature.
Tenant override operation is initiated when the Tenant Override Timer is greater than zero.
The Tenant Override Timer is set equal to the Local Tenant Override Time (Timer Settings
menu) if the unit is enabled and any of the following is true:
• The Space Temperature sensor is present and is shorted for less than 10 seconds. Nothing
happens if the button is pushed for more than 10 seconds but less than the time required to
initiate a shorted sensor alarm (30 seconds). Subsequent presses on the button resets the
Tenant Override Timer to the Local Tenant Override Time, i.e. the max time
• The Occ Mode entry on the keypad is set to Tenant Override. After the Tenant Override
Timer is set, the Occ Mode entry on the keypad reverts to auto after a 2 second time delay
• The Occ Mode entry on the keypad is set to Auto or Unocc, and a manual network
occupancy command is set to Bypass. After the Tenant Override Timer is set, the network
occupancy command reverts to Auto
Subsequent presses on the button, setting of the keypad occupancy entry to Tenant Override
again, or setting of the network occupancy command to Bypass again resets the Tenant
Override Timer to the Local Tenant Override Time.
The TOTime entry on the keypad can also be manually set to a non-zero value. In this case the
value begins timing down from the edited value.
Tenant Override Operation may be terminated by manually setting the Tenant Override
parameter on the keypad to zero or by disabling the unit.