Instruction manual

Table Of Contents
114 McQuay OM 920
Operators Guide
An example of discharge temperature reset based on outdoor air temperature is illustrated in
Figure 13 (Cooling Reset Type Flag is set to “OAT” in this example). When the current
outdoor air temperature is greater than or equal to the Minimum Cooling Set Point Reset Value
(90°F in this example), the Discharge Cooling Set Point is set equal to the Minimum
Discharge Cooling Set Point (55°F in this example). This is shown as Point C in Figure 13.
When the current outdoor air temperature is less than or equal to the
Maximum Cooling Set Point Reset Value (70°F in this example), the Discharge Cooling Set
Point is set equal to the Maximum Discharge Cooling Set Point (65°F in this example). This is
shown as Point A in Figure 13. When the current outdoor air temperature is between the
Minimum Cooling Set Point Reset Value and the Maximum Cooling Set Point Reset Value,
the Discharge Cooling Set Point varies linearly between the Minimum Discharge Cooling Set
Point and Maximum Discharge Cooling Set Point. This is shown as Point B in Figure 13.
Figure 13: Discharge Temperature Reset Based on Temperature
Indoor Air Fan - On/Off Control
A Supply fan is provided on every unit. That may be the only fan, but either a Return Fan or
an Exhaust Fan can be provided also. The start/stop signal and the speed signal for fans that
are controlled by variable frequency drives are provided via an internal ModBus network.
Constant volume Supply and Return fans are started and stopped through a digital output.
Exhaust Fans are always controlled by variable frequency drives.
Supply Fan
The Supply Fan is turned on when the unit enters the Recirculation state. The Supply Fan is
turned off when the unit transitions to the Off state, but it stays on for a OffHtClDelayTime
(Default- 120 seconds) if the unit is turned off while DX cooling or Staged heating is active.
The OffHtClDelayTime function is overridden when and Emergency Off or Duct High Limit
fault is active.
Return Fan
A Return fan driven by a variable frequency drive is started four seconds after the Supply Fan
is started to reduce the amp draw peak on startup. A constant volume Return Fan is turned on
through the same output as the Supply Fan. An external Fan Delay Relay is used to provide a
delay between startups if required.