Instruction manual
Table Of Contents
- Introduction
- Using the Keypad/Display
- Keypad/Display Menu Structure
- System Summary Menu
- Standard Menus
- System Menu
- Occupancy Menu
- Temperature Menu
- Flow Summary Menu
- Supply Fan Speed Menu
- Return/Exhaust Fan Speed Menu
- Cooling Menu
- Head Pressure Menu
- Evap Condensing Menu
- Economizer Menu
- Min OA Damper Menu
- Heating Menu
- Energy Recovery
- Dehumidification Menu
- Daily Schedule Menu
- One Event Schedule Menu
- Holiday Schedule Menu
- Optimal Start Menu
- Operating Hours Menu
- Extended Menus
- Unit Setup Menu
- Timer Settings Menu
- Time/Date Menu
- Supply Fan Setup Menu
- Return/Exhaust Fan Setup Menu
- Zone Temperature Setup Menu
- Compressor Setup Menu
- Head Pressure Setup Menu
- Chilled Water Setup Menu
- Economizer Setup Menu
- Design Flow Setup Menu
- Heating Setup Menu
- Dehumidification Setup Menu
- Alarm Out Configuration Setup Menu
- Alarm Limits Setup Menu
- Manual Control Menu
- LON/BACnetIP/BACnetMSTP Setup Menu
- Active Alarm Menu
- Alarm Log Menu
- Advanced Menus
- Unit Configuration Setup Menu
- Save/Restore Menu
- Alarm Delays Setup Menu
- Analog Input Status Menu
- Universal I/O Status Menu
- Digital Input Status Menu
- Digital Output Status Menu
- Adv Setup Settings Menu
- Adv Status Parameters Menu
- Alarms
- Operator’s Guide
- Determining Unit State
- Off Operating State
- Start Up Operating State
- Recirculating Operating State
- Heating
- Economizer
- Mechanical Cooling
- Determining Unit Status
- Determining Control Mode
- Determining Cooling Status
- Determining Heat Status
- Determining Economizer Status
- Determining Cooling Capacity
- Determining Heating Capacity
- Determining Supply Air Fan Capacity
- Determining RF/EF Capacity
- Determining Outside Air Damper Position
- Determining Emergency Mode
- Determining Application Mode
- Determining Occupancy Status
- Determining Occupancy Mode
- Determining Occupancy Source
- Unoccupied Operation
- Scheduling
- Temperature Control Configurations
- Heat/Cool Changeover
- Dehumidification
- Energy Recovery
- Outside Air Damper Control
- Outside Air Damper Control, Two Position
- Special Procedures for Units with WRV and More Than Two Circuits.
- Water Pump Control
- Cooling: Multistage
- Cooling: Modulating
- Heating Control
- Modulating
- Min DAT
- Indoor Air Fan - On/Off Control

McQuay OM 920 105
Operator’s Guide
When Airflow is selected, the values “Min Clg Spt @” and “Max Clg Spt @” are entered as
percentage values. When Ext mA is selected, the values “Min Clg Spt @” and “Max Clg Spt
@” are entered as mA values. When Ext VDC is selected, the values “Min Clg Spt @” and
“Max Clg Spt @” are entered as VDC values.
If Ext mA or Ext V is selected as the type of reset, the Min Clg Spt @ value may be set above
the Max Clg Spt @ value to cause a decrease in the DAT setpoint as the external signal or the
Min Clg Spt @ value may be set below the Max Clg Spt @ value to cause an increase in the
DAT setpoint as the external signal increase.
Actually, the Min Clg Spt @ value can be set below the Max Clg Spt @ value for all types of
reset, but it only makes sense for external reset.
When ever the Clg Reset Type or Engineering Units is changed, the Min Clg Spt @ and Max
Clg Spt @ values revert to default values as follows:
• None: Min Clg Spt @=0NA, Max Clg Spt @=100NA
• Network: Min Clg Spt @=0NA, Max Clg Spt @=100NA
• Space, Return: Min Clg Spt @=73.0F, Max Clg Spt @=71.0F
• OAT: Min Clg Spt @=90.0F, Max Clg Spt @=70.0F
• ExtmA: Min Clg Spt @=4.0mA, Max Clg Spt @=20.0mA
• ExtVDC: Min Clg Spt @=0.0V, Max Clg Spt @=10.0V
• Airflow: Min Clg Spt @=0%, Max Clg Spt @=100%
Condenser Fan Control
There are up to four condenser fans per circuit. The first fan on each circuit is always turned
on when any compressor on the circuit is turned on through auxiliary switches on the
compressor contactors. The second two fans on each circuit (if applicable) are controlled by
outputs from the Main Controller. These are controlled via Condenser Fan Output A (MCB-
DO7) and Condenser Fan Output B (MCB -DO8). The last fan on each circuit (if applicable)
is controller by an external refrigerant pressure switch.
Cond Fan Output A is turned on when any compressor on is on and the OAT rises above the
Condenser Fan A Set Point. Cond Fan Output A is turned off when all compressors are off or
the OAT drops below the Condenser Fan A Set Point by more than the Condenser Fan
Differential (Default = 5°F). External relays allow operation of condenser fans associated with
a specific circuit only when a compressor on that circuit is on.
Cond Fan Output B is turned on when any compressor on is on and the OAT rises above the
Condenser Fan B Set Point. Cond Fan Output B is turned off when all compressors are off or
the OAT drops below the Condenser Fan B Set Point by more than the Condenser Fan
Differential (Default = 5°F). External relays allow operation of condenser fans associated with
a specific circuit only when a compressor on that circuit is on.
Note – During the phase in/out period of R22 to R410A there will be a time period in which a third
condenser fan output will be required on R22 units. This output will be designated Cond
Fan Output C (EMA-DO3).
Cond Fan Output C is turned on when any compressor on is on and the OAT rises above the
Condenser Fan C Set Point. Cond Fan Output C is turned off when all compressors are off or
the OAT drops below the Condenser Fan C Set Point by more than the Condenser Fan
Differential (Default = 5°F). External relays allow operation of condenser fans associated with
a specific circuit only when a compressor on that circuit is on.