Installation manual

McQuay IM 487-4 111
Maintenance
Terminals
The terminals are spring clamp type. They only require
inserting (see
in Figure 124) and clamping the wire to be
stripped, which offers several advantages over screw
terminals. The clamping is done by inserting a flat-bladed
screw driver (up to 9/64" wide). See
in Figure 124.
Spring connection does not require torquing and resists
vibration
Easily identifiable terminal markers
Built-in test ports on each terminal, up to 2.3 mm diameter
See
in Figure 124.
Figure 124. Terminal connectors
Phase Voltage Monitor (PVM) (see page 84)
The phase voltage monitor is designed to protect three-phase
loads from damaging power conditions. A microprocessor-
based voltage and phase sensing circuit constantly monitors
the three-phase voltages to detect harmful power line
conditions. When a harmful condition is detected, its output
relay is deactivated after a specified trip delay (Trip Delay).
The output relay reactivates after power line conditions return
to an acceptable level for a specified amount of time (Restart
Delay). The trip and restart delays prevent nuisance tripping
due to rapidly fluctuating power line conditions.
Other features:
LED display to indicate status (see
in Figure 125)
– Loss of phase
– High or low voltage
– Voltage unbalance
– Phase reversal
– Rapid cycling
– Standard 1 to 500 second variable restart delay (see
in
Figure 125)
Standard 2% to 8% variable voltage unbalance (see
in
Figure 125)
Standard 1 to 30 second trip delay (see
in Figure 125)
Figure 125. Phase voltage monitor
1
Standard
1–500 second
variable
restart delay
LED display
Standard 2%–8%
variable voltage
unbalance
4
Standard
1–30 second
trip delay