Installation manual
Page 52 / IM 178
Control parameter record (cont’d)
MENU MENU NAME MENU ITEM =
FINAL
SETTING
18 Duct Pressure (VAV) Duct Spt = ____ "WC ___________
Max Spt = ____ "WC ___________
Programs: ART1, ART2, ART3 Reset = No Reset ___________
and ART4 Network
Position
Deadband = ____ "WC ___________
Mod Lim = ____ "WC ___________
Wait Time = ____ Sec ___________
Max Step = ____ Sec ___________
19 Ret Fan Cntl (VAV with fan W/ Ex-SFMax = ____ % ___________
tracking control) W/ Ex-RFMax = ____ % ___________
W/ Ex-SFMin = ____ % ___________
Programs: ART1 and ART3 W/ Ex-RFMin = ____ % ___________
No Ex-SFMax = ____ % ___________
No Ex-RFMax = ____ % ___________
No Ex-SFMin = ____ % ___________
No Ex-RFMin = ____ % ___________
19 Bldg Pressure Zone Spt = ____ "WC ___________
Deadbd = ____ "WC ___________
Programs: ART2, ART4, ART5 Stg Time = ____ Sec ___________
and ART6 Mod Lim = ____ "WC ___________
Wait Time = ____ Sec ___________
Max Step = ____ Sec ___________
20 Fan Balance (VAV with fan Balance = Off ___________
tracking control) On
Set Max W/ Ex = No ___________
Programs: ART1 and ART3 Yes
Set Max No Ex = No ___________
Yes
Set Min W/ Ex = No ___________
Yes
Set Min No Ex = No ___________
Yes
21 Outdr Damper (VAV) Min Airflow = ____ % ___________
Min Type = None ___________
Programs: ART1, ART2, ART3 Auto
and ART4 External
____ % @ 5V Ext ___________
Enthalpy = Yes ___________
No
Changeover = ____ °F ___________
Chngovr Diff = ____ °F ___________
Max Purge = ____ Min ___________
Deadband = ____ °F ___________
Mod Limit = ____ °F ___________
Wait Time = ____ Sec ___________
Max Step = ____ Sec ___________
PA Time = ____ Sec ___________
Max OD Pos Spt = ____ % ___________
Max OD Pos @ RF = ____ % ___________
Min OD Pos @ RF = ____ % ___________
Continued