Operating instructions
IM 950-1 / Page 17 of 38
System Select Operation Using Remote 
Thermostat
System will run in Heat mode and engage certain 
outputs based on the system selection (jumper) as 
described below (see Standard Digital Control Board 
Wiring Diagram on page 31).
AC/ELE
  •  If AC/ELE is selected then a signal on W 
    terminal will call for heating. 
HP or HP/ELE
  •  If HP or HP/ELE is selected then signals on Y 
    and B terminals will call for heating.
NOTES:  
1.  Hot start and Sleep features are not available in 
Remote T’stat heat mode.
2.  Control’s operation is subject to its own protection 
features when controlled by a Remote T’stat
3.  Indoor fan mode and the speed will default to 
“cycle” and “high” when unit is controlled by 
Remote T’stat
4.  The indoor fan is turned on when G signal is high. 
When there is no signal on G terminal then the 
indoor fan will be turned off.
Control Lockout Feature
 The control is placed in a lockout mode of 
operation when Mode button is held pressed for 10 
seconds. Display will show “LC” to conrm Lockout 
Mode has been entered. Once in this Lockout Mode 
the control board will not take any commands at all. In 
Lockout, unit will continue to operate with the same 
settings just prior to Lockout Mode. This means the 
touchpad will no longer be able to pass commands 
to the control. User’s set point will normally be 
displayed. Any button pushed will bring “LC” on 
display for ve seconds.
To exit the Lockout Mode and return to normal 
(regular) mode of operation, press the Mode button for 
10 seconds. Display will show “nL” for ve seconds to 
conrm normal mode has been resumed.
Controls
Standard Digital Touchpad Control
Modes of Operation
Cool Mode
In Cool Mode, the compressor will start if the 
temperature at the space temperature sensor is 1°F 
or higher than the set point. It will stop if the space 
temperature sensor is 2°F or lower than the set point, 
subject to timing requirements.
In the Cool Mode, the indoor fan will operate 
according to the user settings for Fan Mode – 
Continuous or Cycle and Speed.
Cold Start
Cold start is initiated when the control has not 
called for cooling for more than two (2) hours or 
during a power-on-reset. During cold start, the set 
point is lowered by 4°F (Tset-4°F) if the differential 
calls for cooling. The unit will operate in cold start 
until the new set point is satised (+ or – 1°F) or until 
the unit has run in cold start for at least 20 minutes. 
After one or both conditions are met, the set point will 
be reset to the user setting and the unit will run in the 
regular cool mode.
The indoor fan will operate according to the user 
settings for mode – Continuous or Cycle and Speed.
Cold start is not available with the Sleep feature.
Sleep Function
Sleep time is adjustable by the user from 1 to 15 
hours in one (1) hour increments in a closed loop. The 
sleep time is adjusted and set via the touchpad and by 
pressing the Sleep Button repeatedly. On the touchpad, 
the display will show the set time in numbers for ve 
(5) seconds. Before the sleep time expires, the setting 
can be adjusted above the number of hours passed by 
pressing the Sleep Button. Pressing the On/Off Button 
can terminate the Sleep Mode.
A changeover from Heat to Cool or another Mode 
will reset the Sleep Timer.
The Sleep Function will be deactivated by pressing 
the power-on-reset or any button (except sleep) on the 
touchpad or the Remote Control.