Specifications
IM 934-5 Page 33 of 48
Wall-Mounted, 7, 5-2 & 5-1-1
ProgrammableThermostat Specs
Manual Changeover One-Stage Heat and Cool or
One-Stage Heat Pump
Daikin McQuay Part No. 910116772 (1-Pk, White
with Wall Plate)
Specications
Electrical Rating:
• 24 VAC (18 to 30 VAC)
• 1 amp maximum per terminal
• 3 amp maximum total load
• 30-minute power loss memory retention
• Easy access terminal block
Temperature Control Ranges:
• 45°F to 90°F, Accuracy: ± 1°F
System Congurations:
• 1 stage heat, 1 stage cool or single stage electric
heat pump
Terminations:
• RC, RH, C, W, Y, O, B, G
Standard Auto or Manual-Changeover
Two-Stage Heat/ Two-Stage Cool Specs
Daikin McQuay Part No. 910116774 (1-Pk, White with
Wall Plate)
Specications
Electrical Rating:
• 24 VAC (18 to 30 VAC)
• 1 amp maximum per terminal
• 4 amp maximum total load
• 30-minute power loss memory retention
• Easy access terminal block
Temperature Control Ranges:
• 45°F to 90
o
F, Accuracy: ± 1°F
System Congurations:
• Single or two-stage heat/cool
• Single or two-stage heat pump
Terminations:
• R, C, W1/O/B, Y1, W2, Y2, G
Optional Remote Sensor
Part No. 667720401 (Used in Conjunction with
Thermostat Part No. 910116774 Only)
The Fast, Easy Solution For Temperature Sensing
Problems.
• For tamper prone areas
• Poor airow areas
• Troubled applications
• Foam gasket prevents drafts through wall opening
• Mounts to standard 2" × 4" outlet box
• 2
3
/4"W × 4
1
/2"H