Specifications

Page 30 of 48 IM 934-5
1.2 Adjust the time by pressing and buttons. By
holding pressed or buttons, time will change
in 15 minutes increments or decrements respectively.
AM and PM will show in rotation.
1.3 By pressing FAN MODE button, move to the
conrmation day of the week. Numbers represent
days of the week, Monday being 1 and so forth.
TODAY will ash on display. Adjust the number that
represents the day of the week by pressing and
buttons:
TODAY
AM
9:45
1.4 Exit the clock set menu by pressing FAN MODE
(TIME) and FAN SPEED (DAY) simultaneously for
5 seconds
Conguration
The conguration mode is meant for temperature scale set-
ting, limits for minimum and maximum operating tempera-
tures and displaying sensor readings. To enter the congura-
tion mode hold pressed and buttons for 5 seconds.
Moving from one screen to another and rolling over is done
by pressing Mode button.
2.1 Once in the conguration mode, the default
temperature scale will be displayed as shown below.
Toggle the temperature scale to degree Celsius by
pressing either or button:
2.2 To adjust the lower operating temperature limit (cool
minimum set point) press and hold the Fan Mode but-
ton, and repeatedly press or buttons. COOL
and the setting will be displayed as shown below. The
minimum and factory default setting is 60°F (15°C).
An example of what can be displayed:
AUTO Non-Programmable Mode:
Display shows both HEAT and COOL icons
Temperature set point displays between the HEAT and
COOL icons
Setpoint is adjusted with Up and Down arrows
Heating initiates when the room temperature falls one
degree below the thermostat setpoint. Heating terminates
when the room temperature reaches two degrees above
the setpoint
Cooling initiates when the room temperature reaches one
degree above the thermostat setpoint. Cooling terminates
when the room temperature falls two degrees below the
setpoint
AUTO Programmable Mode:
HEAT and COOL icons alternatively ash with their
respective programmed setpoints
The system engages cooling and heating automatically to
maintain respective setpoints according to system model
selection
The 2-degree gap between setpoints represents the
deadband and is necessary to prevent unecessary
switching between heating and cooling
The 2 degree deadband provides the following:
Heating activates when the room temperature is one
degree below the thermostat setpoint plus the 2 degree
deadband.
Cooling activates when the room temperature is one
degree above the thermostat setpoint plus the 2 degree
deadband
Figure 38: Keys and Indicators Labels
ON/OFF, FAN SPEED, MODE,
8 Push Buttons
FAN MODE, SLEEP, PROG-ON/OFF
Temp buttons: for
Temp UP and for Temp DOWN
9 LED Indicators
SLEEP, COOL, AUTO, FAN,
HEAT, HIGH, LOW, CYCLE, CONT.
LED 2 Digit Displays No Label
Premium (Programmable) Digital
Touchpad Control
Clock Set Menu
1.1 To set the time and day of the week, press FAN
MODE and FAN SPEED buttons simultaneously for
5 seconds. Time will be displayed rst:
AM
9:45