Specifications

18
R22 MODELS
(HEATPUMP – COOLING MODE)
MODEL : MWM 007FR / MLC 007BR
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
2.534 2.338 2.162 1.987 1.812 1.602
SC
2.534 2.338 2.162 1.987 1.812 1.602
15 TC
2.563 2.376 2.208 2.041 1.874 1.673
SC
2.390 2.227 2.081 1.935 1.790 1.615
18 TC
2.643 2.480 2.334 2.188 2.042 1.867
SC
1.999 1.925 1.859 1.793 1.727 1.648
19.4 TC
2.681 2.529 2.393 2.257 2.121 1.958
SC
1.817 1.784 1.756 1.727 1.698 1.664
20 TC
2.697 2.548 2.415 2.282 2.149 1.990
SC
1.738 1.709 1.683 1.657 1.631 1.599
22 TC
2.750 2.613 2.490 2.367 2.245 2.097
SC
1.478 1.458 1.440 1.422 1.405 1.383
24 TC
2.804 2.678 2.565 2.453 2.340 2.205
SC
1.217 1.206 1.197 1.188 1.179 1.168
MODEL : MWM 010FR / MLC 010BR
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
2.662 2.518 2.389 2.260 2.131 1.977
SC
2.662 2.518 2.389 2.260 2.131 1.977
15 TC
2.849 2.675 2.520 2.365 2.210 2.024
SC
2.557 2.422 2.302 2.182 2.062 1.918
18 TC
3.357 3.104 2.877 2.651 2.424 2.153
SC
2.270 2.162 2.066 1.969 1.873 1.757
19.4 TC
3.595 3.304 3.044 2.784 2.525 2.213
SC
2.137 2.041 1.955 1.870 1.784 1.682
20 TC
3.697 3.398 3.132 2.865 2.599 2.279
SC
2.079 1.984 1.899 1.814 1.729 1.627
22 TC
4.036 3.712 3.424 3.135 2.846 2.500
SC
1.888 1.795 1.712 1.629 1.545 1.446
24 TC
4.375 4.026 3.715 3.404 3.093 2.720
SC
1.697 1.606 1.525 1.443 1.362 1.264
MODEL : MWM 015FR / MLC 015BR
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
3.206 3.070 2.949 2.827 2.705 2.559
SC
3.103 2.988 2.886 2.784 2.682 2.559
15 TC
3.407 3.254 3.118 2.983 2.847 2.684
SC
2.954 2.862 2.780 2.698 2.617 2.518
18 TC
3.953 3.757 3.582 3.407 3.232 3.022
SC
2.548 2.518 2.491 2.465 2.438 2.406
19.4 TC
4.208 3.991 3.798 3.605 3.412 3.180
SC
2.359 2.358 2.357 2.355 2.354 2.353
20 TC
4.317 4.087 3.882 3.676 3.471 3.225
SC
2.278 2.273 2.268 2.264 2.259 2.254
22 TC
4.681 4.406 4.160 3.914 3.668 3.373
SC
2.007 1.989 1.974 1.958 1.942 1.923
24 TC
5.045 4.724 4.438 4.152 3.866 3.522
SC
1.737 1.706 1.679 1.652 1.625 1.592
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MWM 007FR MWM 010FR MWM 015FR
MLC 007BR MLC 010BR MLC 015BR
Bypass Factor
0.30 0.36 0.35