Catalog Wall Mounted Split Systems Models: MWM MWM MWM MWM MWM MWM MWM 007G/GR 009G/GR 010G/GR 015G/GR 020G/GR 025G/GR 030F/FR M5WM 007G/GR M5WM 009G/GR M5WM 010G/GR M5WM 015G/GR M5WM 020G/GR M5WM 025G/GR M5WM 031F/030FR MWM - G - 2007
Table of Contents Nomeneclature ............................................................................................................... 1 - Product Line-up ................................................................................................... 3 Features ......................................................................................................................... 6 Application Information - Operating Range .......................................................................
Nomenc la tur e Nomencla latur ture Indoor Others A : First issue Grille Type A : Grille A Air Treatment Devices & Control I : Negative Ion with wireless controller N : NTP with wireless controller X : Oxygen unit Market Region C : Export with CE mark U : UTL Spec.
Outdoor Others A : First issue Specification Variation O : Standard Unit B : With Contactor G : Low Ambient Kit H : High Ambient Kit I : Gold Fins L : Long Piping Unit S : With H/L Pressure Switch X : Oxygen Unit Compressor P : Matsushita Rotary T : Toshiba Rotary M : Mitsubishi Rotary S : Samsung Rotary Market Region C : Export with CE marking E : Export without marking U : ETL Spec.
Product Line Up INDOOR UNIT MWM-G SERIES PRODUCT LINE UP Grille G11 Negative Ion Nano Technology Air Filteration CE A 007G ACIAC X X X X X X 009G ACIAC X X X X X X 010G ACIAC X X X X X X 015G ACIAC X X X X X X 020G ACIAC X X X X X X 025G ACIAC X X X X X X 030F AFDB Heatpump Model Cooling Model X X X X Non-Thermal Plasma (NTP) Saranet Filter Ionizer Filter Air Purification U1.5 D2.0 PCB L2.
INDOOR UNIT M5WM-G SERIES PRODUCT LINE UP Marking Grille Nomenclature G11 Negative Ion Nano Technology Air Filteration CE A CLASSIFICATIONS 007G ACIAC X X X X X X 009G ACIAC X X X X X X 010G ACIAC X X X X X X 015G ACIAC X X X X X X 020G ACIAC X X X X X X 025G ACIAC X X X X X X 031F AFCA X X X 007GR ACIAC X X X X X X 009GR ACIAC X X X X X X 010GR ACIAC X X X X X X 015GR ACIAC X X X X X X 020GR ACIAC X X X X X
OUTDOOR UNIT MLC PRODUCT LINE UP X ACPOB X X ACPIB X X ACPOD X X ACPID X X ATPOD X X ACPOD X X ACPID X X ACPBD X X ACPOD X X ACPID X X ACPBD X X ATPOD X X ACPBD X X ACPOD X X ACPID X X ACPOD X X ACPID X X ACPBD X X ACPOD X X ACPID X X ACPBD X X ACPBD X X 025CR ACPOD X X ACPID X X 010C 015C 018C 020C 025C 018CR 020CR X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
OUTDOOR UNIT M5LC PRODUCT LINE UP Compressor Marking Others X 010C ACPOB X X X 015C ACPOC X X X 020C ACPOC X X X 025C ACPOC X X X 028C ACPOA X X X 007CR ACPOE X X X X 010CR ACPOB X X X X 015CR ACPOC X X X X 020CR ACPOC X X X X 025CR ACPOC X X X X 028CR ACPOA X X X X LP X HP X Contactor ACPOE Gold Fin 007C Cap. Tube CE Marking Safety Devices Mat.
Fea tur es eatur tures • EASY INSTALLATION - The wall mounted fan coil unit is easily installed because of its compact size, slimness and light weight. Slim and short outdoor unit can be easily installed even in a narrow balcony and passageway and yet have a stable profile. • SPACE SAVING - No space is required on either floor or ceiling. This newly developed super slim design for wall mounting maximizes floor space usage and enhances ceiling appearance where ceilings are low.
• HIGH EFFICIENCY HEAT EXCHANGER - The compact design of the 3-fold structure heat exchanger provides a large surface are for better and efficient heat exchange. - The unique Hydrophilic slit fin has greatly improved the air flow and the contact surfaces with the air thus to boost the cooling capacity. • ROTARY COMPRESSOR - The ever popular rotary compressor is more energy efficient and has a higher output to weight ratio.
Applica tion Inf or ma tion pplication Infor orma mation Operating Range Ensure the operating temperature is in allowable range. Cooling only Cooling Outdoor temp. (°CDB) 54 HIGH AMBIENT UNIT 46 Caution : 35 STD The use of your air conditioner outside the range of working temperature and humidity can result in serious failure. 19 LOW AMBIENT KIT 0 24 15 Indoor temp. (°CWB) Heatpump Heating Cooling 54 Outdoor temp. (°CDB) Outdoor temp.
Refrigerant Circuit Diagram Cooling Only Models MODEL : MWM 007G - MLC 007C MWM 009G - MLC 009C MWM 010G - MLC 010C MWM 015G - MLC 015C M5WM 007G - M5LC 007C M5WM009G - M5LC 010C M5WM 010G - M5LC 010C M5WM 015G - M5LC 015C 10
Cooling Only Models MODEL : MWM 020G - MLC 018C MWM 020G - MLC 020C M5WM 020G - M5LC 020C M5WM 025G - M5LC 025C MODEL : MWM 025G - MLC 025C M5WM 031F - M5LC 028C 11
Cooling Only Models MODEL : MWM 030F - MLC 028C 12
Heatpump Models MODEL : MWM 009GR - MLC 009CR M5WM 007GR - M5LC 007CR MODEL : MWM 010GR - MLC 010CR M5WM 009GR - M5LC 010CR M5WM 010GR - M5LC 010CR 13
Heatpump Models MODEL : MWM 015GR - MLC 015CR M5WM 015GR - M5LC 015CR 14
Heatpump Models MODEL : MWM 020GR - MLC 020CR M5WM 020GR - M5LC 020CR M5WM 025GR - M5LC 025CR MODEL : MWM 025GR - MLC 025CR 15
Heatpump Models MODEL : MWM 030FR - MLC 028CR M5WM 030FR - M5LC 028CR 16
Controllers G11 REMOTE CONTROLLER Temperature Setting On/Off Button • • Press Once to start the air conditioner • Press again to stop the unit To set the desired room temperature, press the button to increase or decrease the set temperature. • The temperature setting range is from 16°C to 30°C • Press both buttons simultaneously to toggle the temperature setting between °C and °F Personalised Setting • Press and hold the button for 3s to initiate personalized setting.
Indicator Lights MWM / M5WM - G SERIES IR signal receiver When there is infrared remote control operating IR Receiver signal, the signal receiver on indoor unit will made a LED indicator lights (beep) for signal acceptance confirmation. Cooling unit / Heatpump unit LED Indicator Lights for Cooling Unit / Heatpump The table below shows the LED indicator light for air Unit conditioner unit under normal operation and fault condition.
MWM 030F / 030FR , M5WM 031F / 030FR LED Indicator Lights For Cooling Unit LED Indicator Lights : Normal Operation And Fault Conditions For Cooling Unit Operation / Fault Indication Power Continuously Dry Timer / Action Sleep Timer on - Sleep mode on - Dry mode on Clean the filter and switch to high fan Frost prevention Room air sensor contact loose / short Call your dealer Indoor coil sensor contact loose / short Call your dealer Sensor contact problem, compressor overload protection trip
LED Indicator Lights For Heatpump Unit Cooling mode Dry mode Heat/Fan mode (red/green) Sleep mode LED Indicator Lights : Normal Operation And Fault Conditions For Cooling Unit Normal Operation / Fault Indication Cool Dry Fan Heat Action Sleep Cooling mode - Dry mode - Fan mode - / Heat mode - / Auto mode in heating operation - / Auto mode in cooling operation - Defrost operation - / Compressor overload protection Call your dealer Indoor coil sensor contact loose/short Call you
Controller Specifications (A) 3 HOT SYSTEM (HEATING CYCLE) a) Hot start At the beginning of heating operation (cold start, after defrosting or thermostat resumes operation) the indoor fan operation is controlled in accordance with the temperature of the indoor heat exchanger to send warm air from the start.
Hot Keep (Apply to MWM-GR) After thermostat cut out, the indoor fan operation is controlled in accordance with the indoor heat exchanger temperature to utilize the extra heat and preserve indoor comfort. The indoor fan can be switched to ON, OFF by setting the slide switch shown in the diagram. This slide switch is located at the front frame cover. Multisplit Model Selection The indoor unit can be changed to multisplit model by just selecting MS through the slide switch.
(B) TURBO MODE (APPLY TO MWM-GR) TURBO function is available in COOL, HEAT and DRY modes only. When TURBO function is set, working temperature for cooling cycle is decreased by 2oC, working temperature for heating cycle is increased by 2oC. The indoor fan will force to HIGH fan. After 20 minutes, this function will clear automatically, no more offset temperature for set temperature and indoor fan will restore. Cold start will be overridden when TURBO function is activated.
(E) FROST PREVENTION AND FILTER CHECK In order to prevent the freezing of indoor coil, the controller will operate as follow. 1°C (F) AUTO RANDOM RESTART When power resumed, the unit will automatically restart and operate at the previous setting as before power failure occurred.
Installation Installation Diagram 25
CAUTION: Before installing the unit, ensure that the power supply matches the power requirement of the air conditioner. 1) SELECTION OF LOCATION AND SPACE (A) INDOOR UNIT Install the fan coil (indoor) unit at a location with the following requirements • Location is suitable for wiring, piping and drainage. • No obstruction of air flow into and out of unit where cooler air can be evenly distributed.(See fig. 1) • Ensure that air discharge is not short circuited with air intake.
(B) OUTDOOR UNIT As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected for outdoor unit should fulfill the following requirements : • Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the unit.
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT (HEATPUMP UNIT ONLY) • • • There are 2 holes on the base of outdoor unit for condensed water to flow out. Insert the drain elbow to one of the holes. To install the drain elbow, first insert one portion of the hook to the base (portion A), then pull the drain elbow in the direction shown by the arrow while inserting the other portion to the base. After installation, check to ensure that the drain elbow clings to base firmly.
2) DRILLING HOLES AND MOUNTING INSTALLATION PLATE CAUTION: i) Please check the unit weight for each model. Always ensure that the wall is sufficiently strong to withstand the weight. If not, it is necessary to reinforce the wall with plate, beams or pillars. ii) The unit cannot be directly fixed onto the wall or the likes. In all cases, the installation plate provided MUST be used. • Paste the installation plan provided on the desired location on the wall and mark the holes location accordingly.
• Fixing method:WOODEN FRAME WALL REINFORCED CONCRETE BUILDING NUT ANCHOR BOLT ANCHOR 3) INDOOR UNIT PREPARATION • The refrigerant piping can be routed to the unit in 5 • Carefully bend the pipes to the required position to direction, by using the cut outs in the unit casing. (See fig. 1) align with the hole. For right hand and rear side draw out, hold the bottom of the piping and fix direction before shaping it to the desired position (See fig. 2).
6) WIRING ELECTRICAL CONNECTION • Wiring regulation on wire diameters differ from country to country. Please refer to your LOCAL ELECTRICAL CODES for field wiring rules. Be sure that installation comply with such rules and regulations. GENERAL PRECAUTIONS • Ensure that the rated voltage of the unit corresponds to the name plate before carrying out proper wiring according to the wiring diagram. • Provide a power outlet to be used exclusively for each unit.
• Remove burr with the burr remover. Hold the flaring end down to prevent burrs from dropping inside pipe. • The exact length of pipe protruding from the face of the flare die is determined by the flaring tool. The table shows the use of an imperial die and riged die. PIPE ∅, D (mm) A(mm) IMPERIAL DIE RIGED DIE 6.35 (1/4”) 1.3 0.7 9.52 (3/8”) 1.6 1 12.7 (1/2”) 1.9 1.3 15.88 (5/8”) 2.2 1.7 Fix the pipe firmly on the flare die.
Steps : a) Directly connect the “Female” nut of orifice pipe to the liquid pipe. b) Flare the liquid pipe and connect it to the “Male” joint of the orifice pipe. ii) Outdoor Installation Space Is Limited If the orifice pipe can not be connected directly to the liquid valve due to limitation space, it can be connected between the liquid pipes. Steps : a) Flare the liquid pipe and connect it to the liquid valve. b) Braze an addition “Male” joint to the liquid pipe.
c) Connect the “Female” nut of the orifice pipe to the “Male” joint. d) Flare another liquid pipe and connect it to the “Male”joint of the orifice pipe. 9) VACUUMING AND CHARGING • The precharged outdoor unit does not need any vacuuming or charging. However once it is connected, the connecting pipe line and the indoor need to be vacuumed before releasing the R22/R407C/R410A from the outdoor unit. 1) Open the service port core cap. 2) Connect pressure gauge to the service port.
5) Decision by low side pressure. Turn compressor on for 10 or 15 min. Standard Condition Indoor 27°C / Outdoor 35°C Model Heavy Load Condition Indoor 32°C / Outdoor 43°C MWM 007G MWM 009G MWM 010G MWM 015G MWM 020G MWM 025G MWM 030F MWM 007GR MWM 009GR MWM 010GR MWM 015GR MWM 020GR MWM 025GR MWM 030FR kg/cm² 5.2 ~ 5.7 4.7 ~ 5.5 4.9 ~ 5.7 4.7 ~ 5.2 4.6 ~ 4.8 4.1 ~ 4.7 4.0 ~ 4.8 5.2 ~ 5.8 4.8 ~ 5.7 4.9 ~ 5.9 4.9 ~ 6.3 4.6 ~ 5.0 4.2 ~ 4.8 4.0 ~ 4.8 psig 74.3 ~ 81.0 66.6 ~ 78.6 70.6 ~ 81.8 67.6 ~ 74.
Diagram shows typical charging method. Note : R22 - Nil R410A - Nil CAUTION FOR R410A Avoid prolong exposure of an opened compressor, or the internal part of refrigerant piping to moist air. The POE oil in the compressor and piping can absorb moisture from air. 10) FINAL CHECKING • Ensure that steps 1 to 8 are closely followed. • Ensure the following, in particular :1) The unit is mounted solidly and rigidly in position. 2) Piping and connections are leak proof after charging.
SPECIAL PRECAUTIONS WHEN DEALING WITH REFRIGERANT R410A UNIT 1) WHAT IS NEW REFRIGERANT R410A? R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is essential. 2) COMPONENTS Mixture weight composition R32(50%) and R125(50%) 3) CHARACTERISTIC • R410A liquid and vapor components have different compositions when the fluid evaporates or condenses.
d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to ensure that only the original composition of R410A is being delivered into the system. The liquid composition can be different from the vapor composition. Invert cylinder without dip-pipe Dip-pipe Liquid withdrawal f) Normally, the R410A cylinder or can is being equipped with a dip pipe for liquid withdrawal.
Sound Da ta Data Sound Pressure Level (Measured In Anechoic Room) WALL MOUNTED FAN COIL UNIT Speed Model MWM 007G/GR MWM 009G/GR M5WM 007G/GR M5WM 009G/GR MWM 010G/GR M5WM 010G/GR MWM 015G/GR M5WM 015G/GR MWM 020G/GR M5WM 020G/GR MWM 025G/GR M5WM 025G/GR MWM 030F/030FR M5WM 031F/030FR (RPM) 125 Hz 1/1 Octave Sound Pressure Level (dB, ref 20µPa) 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz Overall (dBA) Noise Criteria HIGH 32 34 38 37 32 23 15 40 36 MEDIUM 27 30 34 32 26 17 14 35 31 L
MWM 007G, 009 G/GR , M5WM 007 / 009 G/GR NC CURVES 60 Sound pressure level (dB,ref 20µPa) 50 NC-45 40 NC-40 High Fan NC-35 Medium Fan 30 NC-30 Low Fan NC-25 20 NC-20 10 0 125 250 500 1000 2000 4000 8000 Octave-band frequency (Hz) MWM 010 G/GR , M5WM 010 G/GR NC CURVES 60 Sound pressure level (dB, ref 20µPa) 50 NC-45 40 NC-40 High Fan NC-35 Medium Fan 30 NC-30 NC-25 Low Fan 20 NC-20 10 0 125 250 500 1000 Octave-band frequency (Hz) 40 2000 4000 8000
MWM 015 G/GR , M5WM 015 G/GR NC CURVES 60 Sound pressure level (dB, ref 20µPa) 50 NC-45 40 NC-40 High Fan NC-35 Medium Fan 30 NC-30 NC-25 20 NC-20 Low Fan 10 0 125 250 500 1000 2000 4000 8000 Octave-band frequency (Hz) MWM 020 G/GR , M5WM 020 G/GR NC CURVES 60 Sound pressure level (dB, ref 20 µPa) 50 High Fan 40 NC-45 Medium Fan NC-40 Low Fan NC-35 30 NC-30 NC-25 20 NC-20 10 0 125 250 500 1000 Octave-band frequency (Hz) 41 2000 4000 8000
MWM 025 G/GR , M5WM 025 G/GR NC CURVES 60 Sound pressure level (dB, ref 20 µPa) 50 High Fan Medium Fan NC-45 Low Fan 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 10 0 125 250 500 1000 2000 4000 8000 Octave-band frequency (Hz) MWM 030F/030FR , M5WM 031F/030FR NC CURVES 70 Sound pressure level (dB, ref20µPa) 60 50 NC-50 NC-45 High Fan 40 NC-40 Medium Fan Low Fan NC-35 30 NC-25 20 NC-20 10 0 125 250 500 1000 Octave-band frequency (Hz) 42 2000 4000 8000
Engineering and Ph ysical Da ta Physical Data General Data - Cooling Only (R22) INDOOR UNIT MWM 007G MWM 009G OUTDOOR UNIT MLC 007C MLC 009C Btu/h 7000 9000 W 2050 2640 NOMINAL TOTAL INPUT POWER W 590 919 NOMINAL RUNNING CURRENT A 2.7 4.1 MODEL NOMINAL CAPACITY POWER SOURCE 220-240/1/50 V/Ph/Hz EER W/W 3.47 R22 REFRIGERANT TYPE OUTDOOR CAP.
General Data - Cooling Only (R22) INDOOR UNIT MWM 010G MWM 015G OUTDOOR UNIT MLC 010C MLC 015C Btu/h 9500 12000 W 2780 3520 NOMINAL TOTAL INPUT POWER W 860 1100 NOMINAL RUNNING CURRENT A 3.8 5.4 MODEL NOMINAL CAPACITY POWER SOURCE 220-240/1/50 V/Ph/Hz EER W/W 3.23 R22 REFRIGERANT TYPE OUTDOOR CAP.
General Data - Cooling Only (R22) INDOOR UNIT MWM 020G MWM 020G OUTDOOR UNIT MLC 018C MLC 020C Btu/h 18000 19000 W 5280 5570 NOMINAL TOTAL INPUT POWER W 1,810 1,807 NOMINAL RUNNING CURRENT A 8.1 MODEL NOMINAL CAPACITY POWER SOURCE EER W/W 2.92 OUTDOOR CAP. TUBE REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR UNIT LCD REMOTE CONTROL OPERATION HIGH l/s / cfm 231 / 490 MEDIUM l/s / cfm 193 / 410 LOW l/s / cfm 160 / 340 dBA 43 / 40 / 35 HEIGHT mm/in 304 / 12.
General Data - Cooling Only (R22) INDOOR UNIT MWM 025G MWM 030F OUTDOOR UNIT MLC 025C MLC 028C Btu/h 23,500 27000 W 6,890 7913 NOMINAL TOTAL INPUT POWER W 2,530 2732 NOMINAL RUNNING CURRENT A 11.3 13.1 MODEL NOMINAL CAPACITY POWER SOURCE 220-240 /1/50 V/Ph/Hz EER W/W 2.72 R22 REFRIGERANT TYPE OUTDOOR CAP.
General Data - Heatpump Only (R22) MODEL INDOOR UNIT MWM 009GR OUTDOOR UNIT MLC 009CR Btu/h 9000 W 2640 Btu/h 9000 W 2640 NOMINAL TOTAL INPUT POWER (COOLING) W 910 NOMINAL TOTAL INPUT POWER (HEATING) W 750 NOMINAL RUNNING CURRENT (COOLING) A 4.0 NOMINAL RUNNING CURRENT (HEATING) A 3.4 V/Ph/Hz 220-240/1/50 EER W/W 2.9 COP W/W 3.
General Data - Heatpump (R22) INDOOR UNIT MWM 010GR MWM 015GR OUTDOOR UNIT MLC 010CR MLC 015CR Btu/h 9500 12000 W 2780 3520 Btu/h 9500 12000 W 2780 3520 NOMINAL TOTAL INPUT POWER (COOLING) W 837 1100 NOMINAL TOTAL INPUT POWER (HEATING) W 757 980 NOMINAL RUNNING CURRENT (COOLING) A 3.8 5.0 NOMINAL RUNNING CURRENT (HEATING) A 3.4 4.5 MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY POWER SOURCE 220-240/1/50 V/Ph/Hz EER W/W 3.32 3.2 COP W/W 3.67 3.
General Data - Heatpump (R22) INDOOR UNIT MWM 020GR MWM 020GR OUTDOOR UNIT MLC 018CR MLC 020CR Btu/h 18000 19000 W 5280 5570 Btu/h 18400 19500 W 5390 5720 NOMINAL TOTAL INPUT POWER (COOLING) W 1,820 1,807 NOMINAL TOTAL INPUT POWER (HEATING) W 1,660 1,757 NOMINAL RUNNING CURRENT (COOLING) A 8.1 8.0 NOMINAL RUNNING CURRENT (HEATING) A 7.4 7.8 MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY POWER SOURCE 220-240/1/50 V/Ph/Hz EER W/W 2.9 3.08 COP W/W 3.25 3.
General Data - Heatpump (R22) MODEL INDOOR UNIT OUTDOOR UNIT Btu/h NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY MWM 025GR MWM 030FR MLC 025CR MLC 028CR 23,500 27000 W 6,890 7913 Btu/h 24,000 27000 W 7,030 7913 NOMINAL TOTAL INPUT POWER (COOLING) W 2,530 2778 NOMINAL TOTAL INPUT POWER (HEATING) W 2,450 2818 NOMINAL RUNNING CURRENT (COOLING) A 11.3 13.2 NOMINAL RUNNING CURRENT (HEATING) A 11.1 13.3 POWER SOURCE 220-240/1/50 V/Ph/Hz EER W/W 2.72 2.85 COP W/W 2.
General Data - Cooling Only (R410A) INDOOR UNIT M5WM 007G M5WM 009G OUTDOOR UNIT M5LC 007C M5LC 010C Btu/h 7500 9000 W 2200 2640 NOMINAL TOTAL INPUT POWER W 620 865 NOMINAL RUNNING CURRENT A 2.9 3.9 MODEL NOMINAL CAPACITY POWER SOURCE 220-240/1/50 V/Ph/Hz EER W/W 3.54 R410A REFRIGERANT TYPE OUTDOOR CAP.
General Data - Cooling Only (R410A) INDOOR UNIT M5WM 010G M5WM 015G OUTDOOR UNIT M5LC 010C M5LC 015C Btu/h 9500 12000 W 2780 3520 NOMINAL TOTAL INPUT POWER W 867 1230 NOMINAL RUNNING CURRENT A 3.9 5.5 MODEL NOMINAL CAPACITY POWER SOURCE 220-240/1/50 V/Ph/Hz EER W/W 3.21 R410A REFRIGERANT TYPE OUTDOOR CAP.
General Data - Cooling Only (R410A) INDOOR UNIT M5WM 020G M5WM 025G OUTDOOR UNIT M5LC 020C M5LC 025C Btu/h 18000 / <18000> 21000 / <22500> W 5280 / <5280> 6155 / <6590> NOMINAL TOTAL INPUT POWER - 1Ø / <3Ø> W 1652 / <1663> 1915 / <2195> NOMINAL RUNNING CURRENT - 1Ø / <3Ø> A 7.3 / <3.2> 8.4 / <4.2> MODEL NOMINAL CAPACITY - 1Ø / <3Ø> POWER SOURCE 220-240/ 1/ 50 / <380-415/ 3/ 50> V/Ph/Hz EER - 1Ø / <3Ø> W/W 3.2 / <3.17> R410A REFRIGERANT TYPE OUTDOOR CAP.
General Data - Cooling Only (R410A) MODEL INDOOR UNIT M5WM 031F OUTDOOR UNIT M5LC 028C Btu/h 26000 / <26000> W 7620 / <7620> NOMINAL TOTAL INPUT POWER - 1Ø / <3Ø> W 2560 / <2631> NOMINAL RUNNING CURRENT - 1Ø / <3Ø> A 12.2 / <4.6> V/Ph/Hz 220-240/ 1/ 50 / <380-415/ 3/ 50> W/W 2.98 / <2.
General Data - Heatpump (R410A) INDOOR UNIT M5WM 007GR M5WM 009GR OUTDOOR UNIT M5LC 007CR M5LC 010CR Btu/h 7500 9000 W 2200 2640 Btu/h 7500 9000 W 2200 2640 NOMINAL TOTAL INPUT POWER (COOLING) W 680 860 NOMINAL TOTAL INPUT POWER (HEATING) W 550 745 NOMINAL RUNNING CURRENT (COOLING) A 3.1 3.9 NOMINAL RUNNING CURRENT (HEATING) A 2.6 3.4 MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY POWER SOURCE 220-240/1/50 V/Ph/Hz EER W/W 3.24 3.07 COP W/W 4 3.
General Data - Heatpump (R410A) INDOOR UNIT M5WM 010GR M5WM 015GR OUTDOOR UNIT M5LC 010CR M5LC 015CR Btu/h 9500 12000 W 2780 3520 Btu/h 9500 12000 W 2780 3520 NOMINAL TOTAL INPUT POWER (COOLING) W 867 1230 NOMINAL TOTAL INPUT POWER (HEATING) W 747 1080 NOMINAL RUNNING CURRENT (COOLING) A 3.9 5.4 NOMINAL RUNNING CURRENT (HEATING) A 3.4 4.9 MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY POWER SOURCE 220-240/1/50 V/Ph/Hz EER W/W 3.21 2.86 COP W/W 3.72 3.
General Data - Heatpump (R410A) MODEL INDOOR UNIT M5WM 020GR M5WM 025GR OUTDOOR UNIT M5LC 020CR M5LC 025CR 17850 / <18000> 20350 / <22500> NOMINAL COOLING CAPACITY - 1Ø / <3Ø> NOMINAL HEATING CAPACITY - 1Ø / <3Ø> Btu/h W 5230 / <5280> 5960 / <6590> Btu/h 18000 / <18500> 22000 / <23000> W 5280 / <5420> 6450 / <6740> NOMINAL TOTAL INPUT POWER (COOLING) - 1Ø / <3Ø> W 1630 / <1663> 1860 / <2195> NOMINAL TOTAL INPUT POWER (HEATING) - 1Ø / <3Ø> W 1546 / <1630> 1870 / <2106> NOMINAL RUN
General Data - Heatpump (R410A) MODEL INDOOR UNIT M5WM 030FR OUTDOOR UNIT M5LC 028CR NOMINAL COOLING CAPACITY - 1Ø / <3Ø> NOMINAL HEATING CAPACITY - 1Ø / <3Ø> Btu/h 26000 / <26000> W 7620 / <7620> Btu/h 26000 / <26000> W 7620 / <7620> NOMINAL TOTAL INPUT POWER (COOLING) - 1Ø / <3Ø> W 2560 / <2631> NOMINAL TOTAL INPUT POWER (HEATING) - 1Ø / <3Ø> W 2442 / <2294> NOMINAL RUNNING CURRENT (COOLING) - 1Ø / <3Ø> A 12.2 / <4.6> NOMINAL RUNNING CURRENT (HEATING) - 1Ø / <3Ø> A 11.6 / <4.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MWM 007G MWM 009G OUTDOOR UNIT MLC 007C MLC 009C CROSS FLOW FAN TYPE INDOOR FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 97/3.8 617.5/24.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MWM 010G MWM 015G OUTDOOR UNIT MLC 010C MLC 015C CROSS FLOW FAN TYPE INDOOR FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 97/3.8 717.5/28.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MWM 020G MWM 020G OUTDOOR UNIT MLC 018C MLC 020C CROSS FLOW FAN TYPE INDOOR FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 108/4.25 810/31.9 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY IP20 INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRYL STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 457.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MWM 025G MWM 030F OUTDOOR UNIT MLC 025C MLC 028C TYPE INDOOR FAN CROSS FLOW FAN 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 108/4.25 TYPE INDOOR FAN MOTOR ANTI FUNGUS CROSS FLOW FAN QUANTITY 106 / 4.17 810/31.9 950 / 37.
Components Data - Heatpump (R22) MODEL INDOOR UNIT MWM 009GR OUTDOOR UNIT MLC 009CR TYPE INDOOR FAN ANTI FUNGUS SKEW FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DRIVE DIRECT DIAMETER mm/in 97/3.8 LENGTH mm/in 617.5/24.
Components Data - Heatpump (R22) MODEL INDOOR UNIT MWM 010GR MWM 015GR OUTDOOR UNIT MLC 010CR MLC 015CR ANTI FUNGUS SKEW FAN TYPE INDOOR FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 97/3.8 717.5/28.
Components Data - Heatpump (R22) MODEL INDOOR UNIT MWM 020GR MWM 020GR OUTDOOR UNIT MLC 018CR MLC 020CR CROSS FLOW FAN TYPE INDOOR FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 108/4.25 810/31.9 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY IP20 INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRYL STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 457.
Components Data - Heatpump (R22) MODEL INDOOR UNIT MWM 025GR MWM 030FR OUTDOOR UNIT MLC 025CR MLC 028CR TYPE INDOOR FAN CROSS FLOW FAN 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in 108/4.25 LENGTH mm/in 810/31.9 106 / 4.17 950 / 37.4 INDUCTION TYPE INDOOR FAN MOTOR ANTI FUNGUS CROSS FLOW FAN QUANTITY 1 QUANTITY INDEX OF PROTECTION (IP) IP20 IP24 PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRYL STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 457.
Components Data - Cooling Only (R410A) MODEL INDOOR UNIT M5WM 007G M5WM 009G OUTDOOR UNIT M5LC 007C M5LC 010C ANTI FUNGUS SKEW FAN TYPE INDOOR FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 97/3.8 617.5/24.
Components Data - Cooling Only (R410A) MODEL INDOOR UNIT M5WM 010G M5WM 015G OUTDOOR UNIT M5LC 010C M5LC 015C ANTI FUNGUS SKEW FAN TYPE INDOOR FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 97/3.8 717.5/28.
Components Data - Cooling Only (R410A) MODEL INDOOR UNIT M5WM 020G M5WM 025G OUTDOOR UNIT M5LC 020C M5LC 025C ANTI FUNGUS SKEW FAN TYPE INDOOR FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 108/4.25 810/31.9 TYPE INDOOR FAN MOTOR INDUCTION 1 QUANTITY INDEX OF PROTECTION (IP) IP20 PROPELLER TYPE QUANTITY 1 GLASS REINFORCED ACRYL STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 457.
Components Data - Cooling Only (R410A) MODEL INDOOR UNIT M5WM 031F OUTDOOR UNIT M5LC 028C TYPE INDOOR FAN ANTI FUNGUS CROSS FLOW FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DRIVE DIRECT DIAMETER mm/in LENGTH mm/in 106 / 4.17 950 / 37.4 TYPE INDOOR FAN MOTOR INDUCTION QUANTITY 1 INDEX OF PROTECTION (IP) IP24 TYPE PROPELLER QUANTITY 1 OUTDOOR FAN MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN DRIVE DIRECT DIAMETER mm/in 457.
Components Data - Heatpump (R410A) MODEL INDOOR UNIT M5WM 007GR M5WM 009GR OUTDOOR UNIT M5LC 007CR M5LC 010CR TYPE INDOOR FAN ANTI FUNGUS SKEW FAN 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER LENGTH mm/in 97/3.8 mm/in 617.5/24.
Components Data - Heatpump (R410A) MODEL INDOOR UNIT M5WM 010GR M5WM 015GR OUTDOOR UNIT M5LC 010CR M5LC 015CR TYPE INDOOR FAN ANTI FUNGUS SKEW FAN 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER LENGTH mm/in 97/3.8 mm/in 717.5/28.
Components Data - Heatpump (R410A) MODEL INDOOR UNIT M5WM 020GR M5WM 025GR OUTDOOR UNIT M5LC 020CR M5LC 025CR CROSS FLOW FAN TYPE INDOOR FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DIRECT DRIVE DIAMETER mm/in 108/4.25 LENGTH mm/in 810/31.9 INDUCTION TYPE INDOOR FAN MOTOR QUANTITY 1 INDEX OF PROTECTION (IP) IP20 TYPE PROPELLER QUANTITY 1 OUTDOOR FAN MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN DRIVE DIRECT DIAMETER 457.
Components Data - Heatpump (R410A) MODEL INDOOR UNIT M5WM 030FR OUTDOOR UNIT M5LC 028CR TYPE INDOOR FAN ANTI FUNGUS CROSS FLOW FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DRIVE DIRECT DIAMETER mm/in LENGTH mm/in 106 / 4.17 950 / 37.4 TYPE INDOOR FAN MOTOR INDUCTION QUANTITY 1 INDEX OF PROTECTION (IP) IP24 TYPE PROPELLER QUANTITY 1 OUTDOOR FAN MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN DRIVE DIRECT DIAMETER 457.
Perf or mance Table erfor ormance Interpolation and Extrapolation method can be used to get the total capacity, TC and sensible capacity, SC at those temperatures which are not stated out in the table. Example: Model: MWM 010G / MLC 010C Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 37°C DB Solution: Overall Based on the Performance table of MWM 010G / MLC 010C 1. Refer to the Indoor DB column, - 23°C is located between 20°C and 24°C (Thus, Interpolation need to be applied) 2.
Details: 1st Step: To obtain the Total capacity and Sensible capacity for (a) Indoor Condition: 24°C DB, 15°C WB Outdoor Condition: 35°C DB Indoor DB °C Indoor WB °C 24 15 16 17 Outdoor DB ° C 35 TC (kW) SC (kW) x1 2.623 2.687 y1 1.892 1.794 Total capacity, TC ⇒ x1 = 2.558kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 35°C Outdoor WB)* Sensible capacity, SC Extrapolation Method: 1.794kW - y1 ⇒ 17°C - 15°C = 17°C - 16°C 1.794kW - 1.892kW ⇒ y1 = 1.
2nd Step: To obtain the Total capacity and Sensible capacity for (a) Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 35°C DB Indoor DB °C Indoor WB °C 20 23 24 15 15 15 Outdoor DB ° C 35 TC (kW) SC (kW) 2.558 x3 2.558 1.403 y3 1.990 Total capacity, TC ⇒ x3 = 2.558kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 35°C Outdoor WB)* Sensible capacity, SC Interpolation Method: ⇒ 24°C - 20°C 1.990kW - 1.403kW = 24°C - 23°C 1.990kW - y3 ⇒ y3 = 1.
3rd Step: To obtain the Total capacity and Sensible capacity for (a) Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 37°C DB Indoor DB °C Indoor WB °C 23 15 35 TC (kW) SC (kW) 2.558 1.844 Total capacity, TC Interpolation Method: ⇒ 40°C - 35°C = 2.355kW - 2.558kW 40°C - 37°C 2.355kW - x ⇒ x = 2.477kW Sensible capacity, SC Interpolation Method: ⇒ 40°C - 35°C = 1.655kW - 1.844kW 40°C - 37°C 1.655kW - y ⇒ y = 1.768kW 78 Outdoor DB ° C 37 TC (kW) SC (kW) x y 40 TC (kW) SC (kW) 2.355 1.
R22 Models (Cooling Only) MODEL : MWM 007G / MLC 007C Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 2.418 1.484 2.249 1.335 2.080 1.186 1.910 1.037 1.741 0.889 1.538 0.710 16 2.453 1.349 2.286 1.221 2.119 1.094 1.952 0.966 1.785 0.839 1.585 0.686 16 2.453 1.799 2.286 1.671 2.119 1.544 1.952 1.416 1.785 1.288 1.585 1.135 17 2.488 1.664 2.323 1.
R22 Models (Cooling only) MODEL : MWM 010G / MLC 010C Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 3.169 1.968 2.966 1.780 2.762 1.592 2.558 1.403 2.355 1.215 2.111 0.989 16 3.206 1.800 3.012 1.635 2.817 1.470 2.623 1.306 2.429 1.141 2.195 0.943 16 3.206 2.386 3.012 2.222 2.817 2.057 2.623 1.892 2.429 1.728 2.195 1.530 17 3.243 2.218 3.058 2.
R22 Models (Cooling only) MODEL : MWM 020G / MLC 018C Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 5.954 3.645 5.566 3.311 5.179 2.977 4.791 2.642 4.404 2.308 3.939 1.907 16 6.132 3.309 5.730 3.009 5.329 2.709 4.927 2.409 4.525 2.109 4.043 1.749 16 6.132 4.352 5.730 4.052 5.329 3.752 4.927 3.451 4.525 3.151 4.043 2.791 17 6.310 4.016 5.894 3.
R22 Models (Cooling only) MODEL : MWM 025G / MLC 025C Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 7.657 5.145 7.196 4.692 6.735 4.238 6.275 3.785 5.814 3.331 5.261 2.787 16 7.728 4.693 7.300 4.280 6.873 3.867 6.446 3.454 6.019 3.042 5.507 2.546 16 7.728 5.852 7.300 5.439 6.873 5.026 6.446 4.614 6.019 4.201 5.507 3.705 17 7.798 5.400 7.405 5.
R22 Models (Heatpump) MODEL : MWM 009GR / MLC 009CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 3.163 2.063 2.934 1.852 2.705 1.641 2.476 1.430 2.247 1.219 1.972 0.966 16 3.205 1.896 2.978 1.704 2.752 1.513 2.525 1.322 2.299 1.130 2.027 0.901 16 3.205 2.420 2.978 2.228 2.752 2.037 2.525 1.846 2.299 1.654 2.027 1.425 17 3.246 2.
R22 Models (Heatpump) MODEL : MWM 010GR / MLC 010CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 20 ID WB°C 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 3.169 1.968 2.966 1.780 2.762 1.592 2.558 1.403 2.355 1.215 2.111 0.989 16 3.206 1.800 3.012 1.635 2.817 1.470 2.623 1.306 2.429 1.141 2.195 0.943 16 3.206 2.386 3.012 2.222 2.817 2.057 2.623 1.892 2.429 1.728 2.195 1.530 17 3.243 2.
R22 Models (Heatpump) MODEL : MWM 015GR / MLC 015CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 35 30 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 3.852 2.383 3.608 2.179 3.365 1.974 3.121 1.769 2.877 1.564 2.584 1.318 16 4.062 2.259 3.784 2.056 3.506 1.852 3.228 1.648 2.950 1.445 2.616 1.201 16 4.062 2.917 3.784 2.713 3.506 2.510 3.228 2.306 2.950 2.103 2.616 1.858 17 4.271 2.
R22 Models (Heatpump) MODEL : MWM 020GR / MLC 018CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 5.954 3.645 5.566 3.311 5.179 2.977 4.791 2.642 4.404 2.308 3.939 1.907 16 6.132 3.309 5.730 3.009 5.329 2.709 4.927 2.409 4.525 2.109 4.043 1.749 16 6.132 4.352 5.730 4.052 5.329 3.752 4.927 3.451 4.525 3.151 4.043 2.791 17 6.310 4.
R22 Models (Heatpump) MODEL : MWM 020GR / MLC 020CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 5.778 3.640 5.473 3.396 5.169 3.153 4.864 2.909 4.559 2.666 4.194 2.373 16 6.026 3.334 5.701 3.125 5.376 2.917 5.051 2.709 4.726 2.501 4.336 2.251 16 6.026 4.248 5.701 4.040 5.376 3.832 5.051 3.624 4.726 3.416 4.336 3.166 17 6.274 3.
R22 Models (Heatpump) MODEL : MWM 025GR / MLC 025CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 7.657 5.145 7.196 4.692 6.735 4.238 6.275 3.785 5.814 3.331 5.261 2.787 16 7.728 4.693 7.300 4.280 6.873 3.867 6.446 3.454 6.019 3.042 5.507 2.546 16 7.728 5.852 7.300 5.439 6.873 5.026 6.446 4.614 6.019 4.201 5.507 3.705 17 7.798 5.
R22 Models (Heatpump) MODEL : MWM 030FR / MLC 028CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 8.187 5.330 7.772 4.967 7.356 4.604 6.941 4.241 6.525 3.877 6.026 3.441 16 8.441 4.894 8.027 4.579 7.614 4.265 7.200 3.951 6.786 3.637 6.289 3.260 16 8.441 6.144 8.027 5.830 7.614 5.516 7.200 5.202 6.786 4.888 6.289 4.511 17 8.695 5.
R410A Models (Cooling only) MODEL : M5WM 007G / M5LC 007C Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 2.541 1.631 2.345 1.434 2.152 1.241 1.959 1.048 1.766 0.854 1.535 0.623 16 2.588 1.515 2.402 1.335 2.217 1.157 2.033 0.979 1.849 0.801 1.627 0.588 16 2.588 2.038 2.402 1.858 2.217 1.680 2.033 1.502 1.849 1.325 1.627 1.111 17 2.635 1.922 2.
R410A Models (Cooling only) MODEL : M5WM 010G / M5LC 010C Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 3.028 1.998 2.824 1.793 2.631 1.600 2.439 1.407 2.247 1.215 2.016 0.983 16 3.110 1.857 2.909 1.675 2.714 1.500 2.519 1.324 2.325 1.148 2.091 0.937 16 3.110 2.450 2.909 2.268 2.714 2.093 2.519 1.917 2.325 1.741 2.091 1.530 17 3.192 2.309 2.
R410A Models (Cooling only) MODEL : M5WM 020G / M5LC 020C Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 5.147 3.507 4.918 3.236 4.654 3.002 4.390 2.769 4.126 2.535 3.809 2.255 16 5.349 3.308 5.102 3.073 4.838 2.858 4.574 2.642 4.310 2.427 3.992 2.168 16 5.349 4.197 5.102 3.963 4.838 3.747 4.574 3.532 4.310 3.316 3.992 3.057 17 5.551 3.997 5.
R410A Models (Cooling only) MODEL : M5WM 031F / M5LC 028C Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 7.648 4.989 7.255 4.595 6.798 4.252 6.341 3.908 5.884 3.565 5.336 3.153 16 7.911 4.701 7.503 4.359 7.062 4.043 6.621 3.727 6.180 3.411 5.650 3.032 16 7.911 5.947 7.503 5.606 7.062 5.290 6.621 4.974 6.180 4.658 5.650 4.278 17 8.175 5.659 7.
R410A Models (Heatpump) MODEL : M5WM 007GR / M5LC 007CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 2.247 1.520 2.115 1.388 1.997 1.269 1.878 1.151 1.760 1.032 1.618 0.890 16 2.329 1.431 2.195 1.314 2.067 1.204 1.940 1.094 1.813 0.985 1.660 0.853 16 2.329 1.849 2.195 1.732 2.067 1.622 1.940 1.513 1.813 1.403 1.660 1.271 17 2.
R410A Models (Heatpump) MODEL : M5WM 009GR / M5LC 010CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 2.779 1.868 2.617 1.706 2.474 1.562 2.330 1.419 2.187 1.275 2.014 1.102 16 2.868 1.747 2.707 1.607 2.555 1.476 2.403 1.345 2.250 1.214 2.067 1.056 16 2.868 2.271 2.707 2.131 2.555 2.000 2.403 1.869 2.250 1.738 2.067 1.580 17 2.
R410A Models (Heatpump) MODEL : M5WM 010GR / M5LC 010CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 3.107 2.083 2.884 1.859 2.669 1.644 2.455 1.429 2.241 1.214 1.983 0.956 16 3.179 1.934 2.958 1.734 2.742 1.538 2.527 1.342 2.311 1.146 2.052 0.911 16 3.179 2.524 2.958 2.324 2.742 2.128 2.527 1.932 2.311 1.736 2.052 1.501 17 3.
R410A Models (Heatpump) MODEL : M5WM 015GR / M5LC 015CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 3.618 2.383 3.422 2.162 3.193 1.960 2.965 1.757 2.736 1.555 2.461 1.312 16 3.728 2.236 3.525 2.040 3.305 1.853 3.085 1.667 2.865 1.480 2.601 1.256 16 3.728 2.892 3.525 2.697 3.305 2.510 3.085 2.323 2.865 2.137 2.601 1.913 17 3.
R410A Models (Heatpump) MODEL : M5WM 020GR / M5LC 020CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 5.147 3.507 4.918 3.236 4.654 3.002 4.390 2.769 4.126 2.535 3.809 2.255 16 5.349 3.308 5.102 3.073 4.838 2.858 4.574 2.642 4.310 2.427 3.992 2.168 16 5.349 4.197 5.102 3.963 4.838 3.747 4.574 3.532 4.310 3.316 3.992 3.057 17 5.
R410A Models (Heatpump) MODEL : M5WM 025GR / M5LC 025CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 6.276 4.244 5.917 3.885 5.599 3.567 5.282 3.250 4.964 2.932 4.583 2.551 16 6.510 3.997 6.156 3.682 5.822 3.388 5.489 3.094 5.156 2.800 4.756 2.447 16 6.510 5.158 6.156 4.843 5.822 4.549 5.489 4.255 5.156 3.961 4.756 3.608 17 6.
R410A Models (Heatpump) MODEL : M5WM 030FR / M5LC 028CR COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 7.648 4.989 7.255 4.595 6.798 4.252 6.341 3.908 5.884 3.565 5.336 3.153 16 7.911 4.701 7.503 4.359 7.062 4.043 6.621 3.727 6.180 3.411 5.650 3.032 16 7.911 5.947 7.503 5.606 7.062 5.290 6.621 4.974 6.180 4.658 5.650 4.278 17 8.
R410A Models (Cooling only) MODEL : M5WM 020G / M5LC 020C (3 PHASE) Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 5.206 3.550 4.976 3.280 4.711 3.049 4.447 2.818 4.182 2.587 3.864 2.310 16 5.402 3.346 5.156 3.114 4.892 2.902 4.628 2.689 4.365 2.477 4.049 2.222 16 5.402 4.235 5.156 4.003 4.892 3.791 4.628 3.579 4.365 3.366 4.049 3.112 17 5.597 4.
R410A Models (Cooling only) MODEL : M5WM 031F / M5LC 028C (3 PHASE) Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 7.648 4.989 7.255 4.595 6.798 4.252 6.341 3.908 5.884 3.565 5.336 3.153 16 7.911 4.701 7.503 4.359 7.062 4.043 6.621 3.727 6.180 3.411 5.650 3.032 16 7.911 5.947 7.503 5.606 7.062 5.290 6.621 4.974 6.180 4.658 5.650 4.278 17 8.175 5.
R410A Models (Heatpump) MODEL : M5WM 020GR / M5LC 020CR (3 PHASE) COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 5.206 3.550 4.976 3.280 4.711 3.049 4.447 2.818 4.182 2.587 3.864 2.310 16 5.402 3.346 5.156 3.114 4.892 2.902 4.628 2.689 4.365 2.477 4.049 2.222 16 5.402 4.235 5.156 4.003 4.892 3.791 4.628 3.579 4.365 3.366 4.049 3.
R410A Models (Heatpump) MODEL : M5WM 025GR / M5LC 025CR (3 PHASE) COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 6.762 4.377 6.391 3.963 5.957 3.582 5.523 3.202 5.089 2.821 4.568 2.365 16 6.971 4.123 6.585 3.751 6.168 3.397 5.751 3.042 5.333 2.687 4.832 2.261 16 6.971 5.382 6.585 5.010 6.168 4.655 5.751 4.301 5.333 3.946 4.832 3.
R410A Models (Heatpump) MODEL : M5WM 030FR / M5LC 028CR (3 PHASE) COOLING MODE Outdoor DB°C ID DB°C 20 24 28 30 ID WB°C 20 25 30 35 40 46 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 7.648 4.989 7.255 4.595 6.798 4.252 6.341 3.908 5.884 3.565 5.336 3.153 16 7.911 4.701 7.503 4.359 7.062 4.043 6.621 3.727 6.180 3.411 5.650 3.032 16 7.911 5.947 7.503 5.606 7.062 5.290 6.621 4.974 6.180 4.658 5.650 4.
Outlines And Dimensions INDOOR UNIT MODEL : MWM 007G / 007GR / 009G / 009GR M5WM 007G / 007GR / 009G / 009GR Note : Dimension in mm OUTDOOR UNIT MODEL : MLC 009C / 009CR M5LC 007C / 007CR Note : Dimension in mm 106
INDOOR UNIT MODEL : MWM 010G / 010GR / 015G / 015GR M5WM 010G / 010GR / 015G / 015GR Note : Dimension in mm OUTDOOR UNIT MODEL : MLC 010C / 010CR / 015C / 015CR M5LC 010C / 010CR / 015C / 015CR Note : Dimension in mm 107
INDOOR UNIT MODEL : MWM 020G / 020GR / 025G / 025GR M5WM 020G / 020GR / 025G / 025GR Note : Dimension in mm OUTDOOR UNIT MODEL : MLC 018C / 020C / 020CR / 025C / 025CR M5LC 020C / 020CR / 025C / 025CR For M5LC / MLC 025 C/CR Note : Dimension in mm MODEL A B C D E F G H I J K L M N O P Q R S T MLC 018C/020C/020CR M5LC 020C/020CR 855 628 328 508 181 44 93 149 101 113 603 126 164 17 49 32 3 23 73 75 MLC 025C/025CR M5LC 025C/025CR 855 730 328 513 182 44 93 1
INDOOR UNIT MODEL : M5WM 031F / 030FR Note : Dimension in mm OUTDOOR UNIT MODEL : M5LC 028C / 028CR For M5LC / MLC 028 C/CR Only Note : Dimension in mm MODEL A B C D E F G H I J K L M N O P Q R S T MLC 028C/028CR M5LC 028C/028CR 855 730 328 513 182 44 93 149 101 113 603 126 164 17 47 32 3 23 73 75 109
Electrical Da ta Data MODEL INDOOR UNIT MWM 007G MWM 009G OUTDOOR UNIT MLC 007C MLC 009C E E 220-240/1/50 INSULATION GRADE POWER SOURCE INDOOR MOTOR V/Ph/Hz 220-240/1/50 RATED INPUT POWER W 23 24 RATED RUNNING CURRENT A 0.11 0.11 MOTOR OUTPUT W 8 8 POLES 4 4 INSULATION GRADE B B 220-240/1/50 POWER SOURCE OUTDOOR MOTOR V/Ph/Hz 220-240/1/50 RATED INPUT POWER W 41 45 RATED RUNNING CURRENT A 0.19 0.
MODEL INDOOR UNIT MWM 020G OUTDOOR UNIT MLC 018C INDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 47 RATED RUNNING CURRENT A 0.22 MOTOR OUTPUT W 20 POLES 4 INSULATION GRADE B POWER SOURCE OUTDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 120 120 RATED RUNNING CURRENT A 0.53 0.
MODEL INDOOR UNIT MWM 009GR OUTDOOR UNIT MLC 009CR E INSULATION GRADE POWER SOURCE INDOOR MOTOR W 24 RATED RUNNING CURRENT A 0.11 MOTOR OUTPUT W 8 POLES 4 INSULATION GRADE B POWER SOURCE OUTDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 40 RATED RUNNING CURRENT A 0.
MODEL INDOOR UNIT MWM 020GR OUTDOOR UNIT MLC 018CR INDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 47 RATED RUNNING CURRENT A 0.22 MOTOR OUTPUT W 20 POLES 4 INSULATION GRADE B POWER SOURCE OUTDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 120 120 RATED RUNNING CURRENT A 0.53 0.
MODEL INDOOR UNIT M5WM 007G OUTDOOR UNIT M5LC 007C INDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 24 RATED RUNNING CURRENT A 0.11 MOTOR OUTPUT W 8 POLES 4 INSULATION GRADE B POWER SOURCE OUTDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 40 52 RATED RUNNING CURRENT A 0.18 0.
MODEL INDOOR UNIT M5WM 020G OUTDOOR UNIT M5LC 020C INDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 47 66 RATED RUNNING CURRENT A 0.22 0.29 MOTOR OUTPUT W 20 B INSULATION GRADE POWER SOURCE 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 120 132 RATED RUNNING CURRENT A 0.53 0.
MODEL INDOOR UNIT M5WM 007GR OUTDOOR UNIT M5LC 007CR INDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 24 RATED RUNNING CURRENT A 0.11 MOTOR OUTPUT W 8 POLES 4 INSULATION GRADE B POWER SOURCE OUTDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 40 52 RATED RUNNING CURRENT A 0.18 0.
MODEL INDOOR UNIT M5WM 020GR OUTDOOR UNIT M5LC 020CR INDOOR MOTOR 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 47 66 RATED RUNNING CURRENT A 0.22 0.29 MOTOR OUTPUT W 20 B INSULATION GRADE POWER SOURCE 220-240/1/50 V/Ph/Hz RATED INPUT POWER W 120 132 RATED RUNNING CURRENT A 0.53 0.
W iring Dia grams Diag COOLING ONLY MODELS OUTDOOR UNIT MODEL : MLC 009C / 010C , M5LC 007C / 010C / 015C INDOOR UNIT MODEL : MWM 009G / 010G , M5WM 007G / 009G / 010G / 015G (WITH IONIZER) 118
COOLING ONLY MODELS OUTDOOR UNIT MODEL : MLC 015C INDOOR UNIT MODEL : MWM 015G (WITH IONIZER) 119
COOLING ONLY MODELS OUTDOOR UNIT MODEL : MLC / M5LC 020C / 025C INDOOR UNIT MODEL : MWM / M5WM 020G / 025G (WITH IONIZER) 120
COOLING ONLY MODELS OUTDOOR UNIT MODEL : MLC 018C INDOOR UNIT MODEL : MWM 020G (WITH IONIZER) 121
COOLING ONLY MODELS OUTDOOR UNIT MODEL : MLC 028C, M5LC 028C INDOOR UNIT MODEL : MWM 030F, M5WM 031F 122
HEATPUMP MODELS OUTDOOR UNIT MODEL : MLC 009CR / 010CR , M5LC 007CR / 010CR / 015CR INDOOR UNIT MODEL : MWM 009GR / 010GR , M5WM 007GR / 010GR / 015GR (WITH IONIZER) 123
HEATPUMP MODELS OUTDOOR UNIT MODEL : MLC 015CR INDOOR UNIT MODEL : MWM 015GR (WITH IONIZER) 124
HEATPUMP MODELS OUTDOOR UNIT MODEL : MLC / M5LC 020CR / 025CR INDOOR UNIT MODEL : MWM / M5WM 020GR / 025GR (WITH IONIZER) 125
HEATPUMP MODELS OUTDOOR UNIT MODEL : MLC 028CR, M5LC 028CR INDOOR UNIT MODEL : MWM 030FR, M5WM 030FR 126
Ser vicing And Maintenance Servicing 1 2 3 4 5 Off the unit Unscrew the air discharge housing Flip open the air discharge housing Clean the blower Close the air discharge housing and tighten it with screw The unit is designed to give a long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention. Components Maintenance Procedure Recommended Schedule Indoor Air Filter 1 .
PRE START UP MAINTENANCE (AFTER EXTENDED SHUTDOWN) – – – – – – – Inspect thoroughly and clean indoor and outdoor units. Clean or replace air filters. Clean condensate drain line. Clean clogged indoor and outdoor coils. Check fan imbalance before operation. Tighten all wiring connections and panels. Check for refrigerant leakage. The design of the MLC outdoor series allows servicing to be carried out readily and easily. The removal of the top/front and back panel make almost every part accessible.
Troub leshooting oubleshooting When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply before proceeding with the following troubleshooting procedures. The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which are not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.
Diagnostic Guidelines By means of pressure reading: High side Low side ● ● High side Low side High side Low side High side Low side High side Low side Probable cause Too high A little high Normal Circuit Too low Data A little low Pressure ● ● ● ● ● ● ● 1. 2. 3. 4. Overcharged with refrigerant. Non-condensable gases in refrigerant circuit (e.g. air) Obstructed air-intake / discharge. Hot air short circuiting in outdoor unit. 1. Poor compression / no compression (compressor defective) 2.
By means of diagnostic flow chart: Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling/heating. “Starting failure” is caused by electrical defect while improper application or defects in refrigerant circuit causes “Insufficient cooling / heating”. i) Diagnosis of Electric Circuit The a) b) c) d) e) most common causes of air conditioner failure to “start” are : Voltage not within ±10% of rated voltage. Power supply interrupted. Improper control settings.
ii ) Diagnosis of Refrigerant Circuit / Application There might be some causes where the unit starts running but does not perform satisfactorily, i.e. insufficient cooling. Judgement could be made by measuring temperature difference of indoor unit’s intake and discharge air as well as running current. Satisfactory operation with temperature difference of air intake & discharge of indoor unit 8°C to 13°C.
Satisfactory operation with temperature difference of air intake & discharge of indoor unit 14°C to 20°C.
Exploded Vie w And P ar ts List iew Par arts INDOOR UNIT MODEL:M5WM / MWM 007G / 007GR / 009G / 009GR / 010G / 010GR / 015G / 015GR 134
M5WM / MWM 007G / 009G / 010G / 015G No Descriptions 1 Assy., Chassis M5WM / MWM 007/009G M5WM / MWM 010/015G 2 Fan, Motor M5WM / MWM 007/009G M5WM / MWM 010/015G 3 Cross Flow Fan M5WM / MWM 007/009G M5WM / MWM 010/015G 4 Fan, Bush 5 Assy., Coil M5WM / MWM 007/009G M5WM / MWM 010/015G 6 Piping, Clamp 7 Assy., Drain Pan M5WM / MWM 007/009G M5WM / MWM 010/015G 8 Drain Hose 9 Assy., Control Box 10 Assy.
MODEL: M5WM / MWM 020G / 020GR / 025G / 025GR 136
Model : M5WM / MWM 020G / 025G No Descriptions 1 Assy., Chassis 2 Fan, Motor MWM 020G MWM 025G 3 Cross Flow Fan 4 Fan, Bush 5 Assy., Coil MWM 020G MWM 025G M5WM 020G M5WM 025G 6 Piping, Clamp 7 Assy., Drain Pan Part No R50124068170 R03034074205 R03034074204 R03029209158 R11014023775 R50024072203 R50024072204 R50024074031 R50024074032 R12014071297 R50124068171 No 8 9 10 11 12 13 14 15 16 17 18 19 20 Descriptions Drain Hose Assy., Control Box Assy., Control Box Cover Assy.
MODEL: MWM 030F / 030FR, M5WM 031F / 030FR 138
MODEL : M5WM 031F / MWM 030F No Descriptions Part No No Descriptions R50014050721 11 ASSY, CONTROL BOX Part No 1 ASSY, INSTALLATION BRACKET R50044090264 2 ASSY. CHASSIS R50124050703 12 LED LIGHT BRACKET R12014050679 3 PIPING CLAMP R07014024546 13 G11 HANDSET R04084065335 4 FAN BUSH BRACKET R12014050709 14 CONTROL BOX COVER R12014050681 5 CROSS FLOW FAN R03029013842 15 ASSY. DRAIN HOSE R10024015319 6 FAN BUSH R11019013841 16 AIR SWING MOTOR R03039007088 7 ASSY.
Model : MLC 007C No Descriptions 1 ASSY,PAN BASE SL07C COMPRESSOR, 2RS122D5BC02 2 Matsushita 3 ASSY., OUTDOOR COIL - (5)SL09C 7MM RL 4 5 6 7 8 9 VALVE,BRACKET ASSY, PARTITION SL07C/09C(R) ASSY SUCTION TUBE ASSY DISCHARGE TUBE ASSY., CAP. TUBE - SL07C BRACKET,FAN MOTOR MOTOR, MSL 09C-502-WL 10 WELLING 11 FAN PROPELLER SL09C Ø355.0 x 115mm Part No R50014057372 No Descriptions 12 PANEL,LEFT PANEL,RIGHT 13 (SL07/09C/CR)(639.
Model : MLC 009C No Descriptions 1 ASSY,PAN BASE SL07C ASSY., OUTDOOR COIL - (5)SL09C 2 7MM RL 3 4 VALVE BRACKET COMPRESSOR, 2PS156D3CB02 MATSUSHITA 5 ASSY, PARTITION SL07C/09C(R) ASSY,CAPILLARY TUBE (SL09C7.0MM COIL) 6 ASSY,CAPILLARY TUBE (SL09C2PS156D COMP) 7 8 9 BRACKET,FAN MOTOR MOTOR, MSL 09C-502-WL WELLING FAN PROPELLER SL09C Part No R50014057372 No Descriptions 10 PANEL,LEFT PANEL,RIGHT 11 (SL07/09C/CR)(639.
Model : MLC 010 / 015C No Descriptions 1 ASSY,PAN BASE SL10/15C 2 ASSY,OUTDOOR COIL SL15C/CR COMPRESSOR, 2PS206D2AF02 3 MATSUSHITA 4 5 6 VALVE BRACKET Assy, 2 way flare valve 1/4" PARTITION ASSY,CAPILLARY TUBE (SL15C) 2PS206D2AF02 Part No R50014051158 R50024087838 No Descriptions 14 ASSY,VALVE COVER PANEL,TOP/FRONT 15 ASSY,FRONT GRILLE (SL10C/15C) R04019027709 R01014051164 R50054054950 R01014051165 16 FAN PROPELLER, DIA401.
Model : MLC 018 / 020C No Descriptions 1 ASSY,PAN BASE (5SL20C/CR) ASSY,OUTDOOR COIL 7mm coil 2 MLC 018C MLC 020C 3 BRACKET MOTOR (SL20C/CR) MOTOR, YDK64-6C/MSL25C-5014 WL Part No R50014078281 R50024089940 R50024084570 R01014070601 FAN PROPELLER, ¥460 0Z40700 SUNWILL CHINA R03019023393 6 ASSY VALVE BRACKET (SL20C/CR)-R22 R50014072861 PANEL RIGHT BACK (SL20C/CR) COMPRESSOR, 2KS324D5AA04 Matsushita R01014070599 9 PANEL FRONT/LEFT (SL20C/CR) 10 PANEL SERVICE (SL20C/CR) PANEL TERMINAL COVER 11 (SL20C/
Model : MLC 025C No Descriptions 1 ASSY,PAN BASE (5SL20C/CR) ASSY.
Model: MLC 009CR No 1 2 3 4 5 6 7 8 9 Descriptions Assy., Base Pan Assy., Condenser Coil Valve Bracket Compressor MLC 009CR Assy., Partition Assy., 4 Way Vlave MLC 009CR Assy., Cap Tube MLC 009CR Bracket, Fan Motor Fan Motor Part No R50014057372 R50024064204 R01014051164 No 10 11 12 13 14 15 16 17 18 19 20 21 R50049016211 R50064065275 R50024065011 R50024065046 R01014052516 R03039015324 145 Descriptions Fan Blade Left Panel Right Panel Assy. Control Panel Assy., Front Panel Assy., Valve Cover Assy.
Model: MLC 010CR / 015CR No Descriptions 1 Assy., Base Pan 2 Assy., Condenser Coil MLC 010CR MLC 015CR 3 Valve Bracket 4 Compressor MLC 010CR MLC 015CR 5 Assy., Partition 6 Assy., 4 Way Valve 7 Assy.
Model: MLC 018CR / 020CR No Descriptions 1 ASSY,PAN BASE (5SL20C/CR) 2 ASSY,OUTDOOR COIL 7mm coil MLC 018CR MLC 020CR 3 BRACKET MOTOR (SL20C/CR) MOTOR, YDK64-6C/MSL25C-5014 WL Part No R50014078281 R50024090296 R50024075143 R01014070601 FAN PROPELLER, ¥460 0Z40700 SUNWILL CHINA R03019023393 6 ASSY VALVE BRACKET (SL20C/CR)-R22 R50014072861 PANEL RIGHT BACK (SL20C/CR) COMPRESSOR, 2KS324D5AA04 Matsushita R01014070599 9 PANEL FRONT/LEFT (SL20C/CR) 10 PANEL SERVICE (SL20C/CR) PANEL TERMINAL COVER 11 (SL
Model: MLC 025CR No Descriptions 1 ASSY,PAN BASE (5SL20C/CR) ASSY.
OUTDOOR UNIT MODEL: M5LC 007C No 1 2 3 4 5 6 7 8 9 Descriptions Assy., Base Pan Assy., Condenser Coil Valve Bracket Compressor Assy., Partition Assy., Cap Tube Bracket, Fan Motor Fan Motor Fan Blade Part No R50014057372 R50024064720 R01014051164 R04019019592 R50064065275 R50024064527 R01014052516 R03039015324 R03019004131 No 10 11 12 13 14 15 16 17 18 19 149 Descriptions Left Panel Right Panel Assy. Control Panel Assy., Front Panel Assy., Valve Cover Assy.
Model: M5LC 010C / 015C No 1 2 3 4 Descriptions Assy., Base Pan Assy., Condenser Coil Valve Bracket Compressor M5LC 10C M5LC 15C 5 Assy., Partition 6 Assy.
MODEL: M5LC 020C No Descriptions 1 Assy. Base Pan MLC 018C M5LC/MLC 020C 2 Assy. Outdoor Coil MLC 018C MLC 020C M5LC 020C 3 Motor Bracket 4 Fan Motor MLC 018C M5LC/MLC 020C 5 Fan Blade 6 Valve Bracket 7 Assy. Flare Valve 3 Ways 5/8" MLC 018C/020C Assy. Flare Valve 3 Ways 1/2" M5LC 020C 8 Assy. Flare Valve 2 Ways 1/4" MLC 018C/020C 9 Assy.
MODEL: M5LC 025 / 028C No Descriptions 1 Assy. Base Pan 2 Assy. Outdoor Coil MLC 025C/028C M5LC 025C/028C 3 Motor Bracket 4 Fan Motor M5LC/MLC 025C M5LC/MLC 028C 5 Fan Blade 6 Valve Bracket 7 Assy. Flare Valve 3 Ways 5/8" MLC 025C/028C M5LC 025C/028C 8 Assy. Flare Valve 2 Ways 3/8" MLC 025C/028C M5LC 025C Assy.
MODEL: M5LC 007CR No 1 2 3 4 5 6 7 8 9 10 11 Descriptions Assy., Base Pan Assy., Condenser Coil Valve Bracket Compressor Assy., Partition Assy., 4 Way Vlave Assy., Cap Tube Bracket, Fan Motor Fan Motor Fan Blade Left Panel Part No R50014057372 R50024064720 R01014051164 R04019019592 R50064065275 R50024066259 R50024066452 R01014052516 R03039015324 R03019004131 R01014052510 No 12 13 14 15 16 17 18 19 20 21 153 Descriptions Right Panel Assy. Control Panel Assy., Front Panel Assy., Valve Cover Assy.
Model: M5LC 010CR / 015CR No Descriptions 1 Assy., Base Pan 2 Assy., Condenser Coil M5LC 10CR M5LC 15CR 3 Valve Bracket 4 Compressor M5LC 10CR M5LC 15CR 5 Assy., Partition 6 Assy., 4 Way Valve 7 Assy.
MODEL: M5LC 020CR No Descriptions 1 Assy. Base Pan 2 Assy. Outdoor Coil MLC 020CR M5LC 020CR 3 Motor Bracket 4 Fan Motor 5 Fan Blade 6 Valve Bracket 7 Assy. Flare Valve 3 Ways 5/8" MLC 020CR Assy. Flare Valve 3 Ways 1/2" M5LC 020CR 8 Assy.
MODEL: M5LC 025CR / 028CR No Descriptions 1 Assy. Base Pan 2 Assy. Outdoor Coil MLC 025CR/028CR M5LC 025CR/028CR 3 Motor Bracket 4 Fan Motor M5LC/MLC 025CR M5LC/MLC 028CR 5 Fan Blade 6 Valve Bracket 7 Assy. Flare Valve 3 Ways 5/8" MLC 025CR/028CR M5LC 025CR/028CR 8 Assy. Flare Valve 2 Ways 3/8" MLC 025CR/028CR M5LC 025CR Assy.
Model : M5LC 020C (3 PHASE) No Descriptions 1 ASSY,PAN BASE (5SL20C/CR) ASSY,OUTDOOR COIL 2 (5SL20C)2RX28THX18FPI 3 4 BRACKET MOTOR (SL20C/CR) MOTOR, MSL20C/25C-501 64W WELLING CHINA Part No R50014078281 R50024079078 R03039023391 FAN PROPELLER, ¥460 0Z40700 SUNWILL CHIN R03019023393 6 ASSY,VALVE BRACKET (5SL20C/CR) R50014078280 PANEL RIGHT BACK (SL20C/CR) COMPRESSOR, 5KS205PAB01 MATSUSHITA R01014070599 9 PANEL FRONT/LEFT (SL20C/CR) 10 PANEL SERVICE (SL20C/CR) ASSY CONTROL PANEL (5SL20C 11 3PH)
Model : M5LC 025C (3 PHASE) No Descriptions Part No No Descriptions ASSY VALVE COVER 15 (SL25C/28C/CR) 1 ASSY PAN BASE (SL20/25/28C(R)) R50014073884 2 ASSY,OUTDOOR COIL (5SL25C)2RX34THX18FPI R50024079238 16 3 BRACKET MOTOR (SL25C/28C/CR) R01014070948 17 PARTITION (SL25C/28C/CR) 4 MOTOR, MSL20C/25C-501 64W WELLING CHINA R03039023391 18 5 FAN PROPELLER, ¥460 0Z40700 SUNWILL CHIN R03019023393 6 ASSY,VALVE BRACKET (5SL25C/25CR) R50014078321 7 PANEL RIGHT BACK (SL25C/28C/CR) R010140709
Model : M5LC 028C (3 PHASE) No Descriptions Part No No Descriptions ASSY VALVE COVER 15 (SL25C/28C/CR) Part No R50124073905 1 ASSY PAN BASE (SL20/25/28C(R)) R50014073884 2 ASSY,OUTDOOR COIL (5SL25C)2RX34THX18FPI R50024079238 3 BRACKET MOTOR (SL25C/28C/CR) R01014070948 4 MOTOR, YDK75-6S/MSL28C-501WL R03039024538 5 FAN PROPELLER, ¥460 0Z40700 SUNWILL CHIN R03019023393 6 ASSY,VALVE BRACKET (5SL28C/CR) R50014080371 ASSY,3 WAY VALVE (3/8")5SL28C/CR R50059024820 7 PANEL RIGHT BACK (SL25C
Model : M5LC 020CR (3 PHASE) No Descriptions Part No 1 ASSY,PAN BASE (5SL20C/CR) R50014078281 ASSY,OUTDOOR COIL (5SL20C/CRR50024075143 2 2RX28TH) 3 4 BRACKET MOTOR (SL20C/CR) MOTOR,YDK64-6C/MSL25C-501WL R01014070601 5 R03019023393 6 ASSY,VALVE BRACKET (5SL20C/CR) R50014078280 7 PANEL RIGHT BACK (SL20C/CR) R01014070599 8 COMPRESSOR, 5KS205PAB01 MAT 9 PANEL FRONT/LEFT (SL20C/CR) 10 PANEL SERVICE (SL20C/CR) ASSY CONTROL PANEL (5SL20CR 11 3PH) R04019029246 R01014070597 R01014070598 12 PANEL TOP (S
Model : M5LC 025CR (3 PHASE) No Descriptions Part No No Descriptions ASSY VALVE COVER 15 (SL25C/28C/CR) Part No R50124073905 1 ASSY PAN BASE (SL20/25/28C(R)) R50014073884 2 ASSY.
Model : M5LC 028CR (3 PHASE) No Descriptions Part No 1 ASSY PAN BASE (SL20/25/28C(R)) R50014073884 2 ASSY.
Products manufactured in an ISO certified facility. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com. © 2007 McQuay International +1 (800) 432-1342 www.mcquay.