Technical data
OM 1191 9
Application Macros
Application Macros
Overview
Macroschangeagroupofparameterstonew,predened
valuesdesignedforspecicapplications.Usemacros
to minimize the need for manual editing of parameters.
Selecting a macro sets (always use HVAC Defaults) all other
parameters to their default values, except:
• Group99:Start-upDataparameters(exceptparameter
9904)
• The PARAMETER LOCK 1602
• The PARAM SAVE 1607
• The COMM FAULT FUNC 3018 and COMM FAULT
TIME3019
• TheCOMMPROTSEL9802
• Groups 51…53 serial communication parameters
• Group29:Maintenancetriggers
After selecting a macro, additional parameter changes can be
made manually using the control panel.
Application macros are enabled by setting the value for
parameter9902APPLICMACRO.Bydefault,HVACDefault
(value 1) is the enabled macro.
General Considerations
The following considerations apply for all macros:
• When using a direct speed reference in AUTO mode,
connect the speed reference to analog input 1 (AI1),
and provide the START command using digital input 1
(DI1). In HAND/OFF mode, the control panel provides
the speed reference and START command.
• When using process PID, connect the feedback signal
to analog input 2 (AI2). As a default, the control panel
sets the Setpoint, but analog input 1 can be used
as an alternate source. You can set up process PID
using parameters (Group 40) or using the PID control
assistant (recommended).
Table 2: Application/Macro Listing
This describes the following macros:
9902 Value Macro
1 HVAC Default**
2 Supply Fan
3 Return Fan
4 Condenser
6 Booster Pump
7 Pump Alternation
8 Internal Timer
9 Internal Timer with Constant Speeds
10 Floating Point
11 Dual Setpoint PID
12 Dual Setpoint PID with Constant Speeds
13 E-bypass
14 Hand Control
15 E-Clipse
** Daikin users must use the HVAC Defaults










