Technical data

OM 1191 89
Appendix
Appendix
Table 63: Parameter Settings
MD5 Parameters Unit RoofPak & Self C Maverick II Maverick II RoofPak Maverick II & Rebel
# Name SAF, RAF & EAF SAF EAF Ener Rec Wheel Ener Rec Wheel
9802 COMM PROT SEL STD MODBUS STD MODBUS STD MODBUS STD MODBUS STD MODBUS
9901 LANGUAGE ENGLISH ENGLISH ENGLISH ENGLISH ENGLISH
9902 APPLIC MARCO HVAC DEFAULT HVAC DEFAULT HVAC DEFAULT HVAC DEFAULT HVAC DEFAULT
9905 MOTOR NOM VOLT V 575 575 575 575 575
9906 MOTOR NOM CURR A 57 28 4 2
0.4
9907 MOTOR NOM FREQ Hz 60 60 60 60 60
9908 MOTOR NOM SPEED rpm 1775 1775 1140 1775 1775
9909 MOTOR NOM POWER hp 60 30 3 1
0.2
1001 EXT1 COMMANDS COMM COMM COMM COMM COMM
1102 EXT1/EXT2 SEL EXT1 EXT1 EXT1 EXT1 EXT1
1103 REF1 SELECT COMM COMM COMM COMM COMM
1104 REF1 MIN Hz 0 0 0 0 0
1105 REF1 MAX Hz 60 60 60 60 60
1106 REF2 SELECT KEYPAD KEYPAD KEYPAD KEYPAD KEYPAD
1201 CONST SPEED SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
1601 RUN ENABLE COMM COMM COMM COMM COMM
1604 FAULT RESET SEL COMM COMM COMM COMM COMM
1607 PARAM SAVE DONE DONE DONE DONE DONE
1608 START ENABLE 1 COMM COMM COMM COMM COMM
1611 PARAMETER VIEW DEFAULT DEFAULT DEFAULT DEFAULT DEFAULT
2101 START FUNCTION SCALAR FLYST SCALAR FLYST SCALAR FLYST SCALAR FLYST SCALAR FLYST
2202 ACCELER TIME 1 s 60 60 60 60 60
2203 DECELER TIME 1 s 60 60 60 60 60
2605 U/F RATIO LINEAR LINEAR LINEAR LINEAR LINEAR
3003 EXTERNAL FAULT 1 DI 2(INV) NOT SEL NOT SEL NOT SEL NOT SEL
3009 BREAK POINT FREQ Hz 45 45 45 45 45
3101 NUMBER TRIALS 5
5 5 5 5
3103 DELAY TIME s 3 3 3 3 3
3104 AR OVERCURRENT ENABLE ENABLE ENABLE ENABLE ENABLE
3404 OUTPUT1 DSP FORM DIRECT DIRECT DIRECT DIRECT DIRECT
3405 OUTPUT1 UNIT % Hz Hz Hz Hz
3415 SIGNAL3 PARAM AI 1 SPEED SPEED SPEED SPEED
3418 OUTPUT3 DSP FORM
+0.0 DIRECT DIRECT DIRECT DIRECT
3421 OUTPUT3 MAX 44ma 1800 rpm 1800 rpm 1800 rpm 1800 rpm
4201 GAIN
The Daikin software version [will grow over time]
4202 INTEGRATION TIME s 451 370 468 165 284
5302 EFB STATION ID SAF=1, R/EAF=2 1 2 3 3
5303 EFB BAUD RATE 192 192 192 192 192
5304 EFP PARITY 8 NONE 2 8 NONE 2 8 NONE 2 8 NONE 2 8 NONE 2
5306 EFB OK MESSAGES Usually a big number that continues to grow
5307 EFB CRC ERRORS 0 0 0 0 0
5308 EFB UART ERRORS Usually a small number that grows slowly unless there is a MicroTech III communication problem
5309 EFB STATUS ON-LINE ON-LINE ON-LINE ON-LINE ON-LINE
8120 INTERLOCKS NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
1002 EXT2 COMMANDS NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
1301 MINIMUM AI1 % MicroTech III limits minimum speed to 20 hz
1302 MAXIMUM AI1 % MicroTech III limits maximum speed to 60 hz
3416 SIGNAL3MIN 0% 0 rpm 0 rpm 0% 0 rpm
3419 OUTOUT3UNIT mA rpm rpm rpm rpm
3420 OUTPUT3MIN mA 0 0 0 0 0
Vary depending on motor nameplate voltage and hp
These values vary depending on the application
Not important, will be HVAC default values