OM 1191 87
Technical Data
Ambient Conditions
The following table lists the MD5 environmental requirements.
Table 61: Ambient Environment Requirements
Installation Site
Storage and Transportation in
the protective package
Altitude
0…1000 m (0…3,300 ft)
1000…2000 m (3,300…6,600 ft) if P
n
and I2 derated 1% every 100 m above 1000 m (300 ft above
3,300 ft)
Ambient temperature
Min. -15 ºC (5 ºF) – no frost allowed
Max. (fsw = 1 or 4) 40 ºC (104 ºF); 50 ºC (122 ºF) if P
n
and I2 derated to 90%
Max. (fsw = 8) 40 ºC (104 ºF) if P
n
and I2 derated to 80%
Max. (fsw = 12) 30 ºC (86 ºF) if P
n
and I2 derated to 65% (to 50% for 600 V, R4 frame sizes, that is
for MD5-xx-032A-6…MD5-xx- 062A-6).
-40…70 ºC (-40…158 ºF)
Relative humidity < 95% (non-condensing)
Contamination Levels
(IEC 721-3-3)
No conductive dust allowed.
The MD5 should be installed in clean air according to enclosure classication.
Cooling air must be clean, free from corrosive materials and free from electrically conductive dust.
Chemical gases: Class 3C2
Solid particles: Class 3S2
Storage
• No conductive dust allowed.
• Chemical gases: Class 1C2
• Solid particles: Class 1S2
Transportation
• No conductive dust allowed.
• Chemical gases: Class 2C2
• Solid particles: Class 2S2
Applicable Standards
Drivecompliancewiththefollowingstandardsisidentiedbythestandards“marks”onthetypecodelabel.
Table 62: Applicable Standards
Mark Applicable Standards
EN 50178 (1997) Electronic equipment for use in power installations
EN 60204-1 (1997 + corrigendum Sep. 1998)
Safety of machinery. Electrical equipment of
machines. Part 1:
General requirements. Provisions for compliance:
The nal assembler of the machine is responsible for
installing:
An emergency-stop device
A supply disconnecting device
EN 60529 (1991 + corrigendum May 1993 +
amendment A1:2000)
Degrees of protection provided by enclosures (IP
code)
EN 61800-3 (1996) + Amendment A11 (2000) EMC product standard including specic test methods
EN 61800-3 (1996) + Amendment A11 (2000) EMC product standard including specic test methods
UL 508C and C22.2 No. 14
UL Standard for Safety, Power Conversion
Equipment, second edition and CSA Standard for
Industrial Control Equipment
C22.2 No. 14 CSA Standard for Industrial Control Equipment
Compliance is valid with the following provisions:
Themotorandcontrolcablesarechosenasspeciedin
this manual.
The installation rules of this manual are followed.
UL Markings
WhenaULmarkisattachedtotheMD5ACdrive,itveries
that the drive follows the provisions of UL 508C.
When a CSA mark is attached to the MD5 AC drive, it
veriesthatthedrivefollowstheprovisionsofC22.2No.14.