Technical data

80 OM 1191
Maintenance
Maintenance
WARNING
Read Safety on page 1-3 before performing any
maintenance on the equipment. Ignoring the safety
instructions can cause injury or death.
Maintenance Intervals
If installed in an appropriate environment, the drive
requires very little maintenance. This table lists the routine
maintenance intervals recommended by Daikin.
Table 55: Maintenance Intervals
Maintenance Application Interval Instruction
Check/replace R7/R8 enclosure inlet
air lter
R7/R8 UL type 12 enclosures
Check every 3 months. Replace as
needed.
Frame Sizes R7/R8 – UL type 12
enclosure inlet air lter on page 81
Check/replace R7/R8 enclosure
exhaust air lter.
R7/R8 UL type 12 enclosures
Check every 6 months. Replace as
needed.
Frame Sizes R7/R8 – UL type 12
enclosure exhaust lters on page 81
Check and clean heatsink. All
Depends on the dustiness of the
environment (every 6…12 months)
See Heatsink below.
Replace drive module fan. Al Every six years
See Drive module fan replacement on
below.
Replace drive module fan. UL type 12 enclosures Every three years.
See Enclosure fan replacement – UL
Type 12 enclosures on page 81.
Change capacitor. Frame sizes R5 and R6 Every ten years See Capacitors on page 81.
Replace battery in the Assistant control
panel
All Every ten years See Control panel on page 81.
Heatsink
Theheatsinknsaccumulatedustfromthecoolingair.
Sinceadustyheatsinkislessefcientatcoolingthedrive,
overtemperature faults become more likely. In a “normal”
environment (not dusty, not clean) check the heatsink
annually, in a dusty environment check more often.
Clean the heatsink as follows (when necessary):
1. Remove power from drive.
2. Remove the cooling fan (see Figure 12 and Figure 13).
3. Blow clean compressed air (not humid) from bottom to
top and simultaneously use a vacuum cleaner at the air
outlet to trap the dust.
4. Replace the cooling fan.
5. Restore power.
NOTE: If there is a risk of the dust entering adjoining
equipment, perform the cleaning in another room.
Drive Module Fan Replacement
The drive module fan cools the heatsink. Fan failure can be
predicted by the increasing noise from fan bearings and the
gradual rise in the heatsink temperature in spite of heatsink
cleaning. If the drive is operated in a critical part of a process,
fan replacement is recommended once these symptoms start
appearing. Replacement fans are available from Daikin.Do
notuseotherthanDaikinspecifiedspare parts.
Frame Sizes R1—R4
To replace the fan:
1. Remove power from drive.
2. Remove drive cover.
3. For Frame Size:
R1, R2: Press together the retaining clips on the fan
cover sides, and lift.
R3, R4: Press in on the lever located on the left side
of the fan mount, and rotate the fan up and out.
4. Disconnect the fan cable.
5. Install the fan in reverse order.
6. Restore power.