Technical data

OM 1191 77
Diagnostics
Table 53 continued: Fault Listing
Fault Code Fault Name In Panel Description and Recommended Corrective Action
101 SERF CORRUPT
Error internal to the drive. Contact your local Daikin sales representative and report the error number.
102 RESERVED
103 SERF MACRO
104 RESERVED
105 RESERVED
201 DSP T1 OVERLOAD
Error in the system. Contact your local Daikin sales representative and report the error number.
202 DSP T2 OVERLOAD
203 DSP T3 OVERLOAD
204 DSP STACK ERROR
205 RESERVED (obsolete)
206 OMIO ID ERROR
207 EFB LOAD ERR
1000 PAR HZRPM LIMITS
Parameter values are inconsistent. Check for any of the following:
• 2001* MINIMUM SPEED > 2002* MAXIMUM SPEED.
• 2007* MINIMUM FREQ > 2008* MAXIMUM FREQ.
• 2001* MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range (> 50)
• 2002* MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range (> 50)
• 2007* MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range (> 50)
• 2008* MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range (> 50)
*
These are factory set and tested. Contact your local
Daikin sales representative if there is a problem.
1001 PAR PFAREFNG
Parameter values are inconsistent. Check for the following:
• 2007 MINIMUM FREQ is negative, when 8123 PFA ENABLE is active.
1002 RESERVED (Obsolete)
1003 PAR AI SCALE
Parameter values are inconsistent. Check for any of the following:
• 1301* AI 1 MIN > 1302 AI 1 MAX.
• 1304* AI 2 MIN > 1305 AI 2 MAX.
*Not used with MicroTech III.
1004 PAR AO SCALE
Parameter values are inconsistent. Check for any of the following:
• 1504* AO 1 MIN > 1505 AO 1 MAX.
• 1510* AO 2 MIN > 1511 AO 2 MAX.
*Not used with MicroTech III.
1005 PAR PCU 2
Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal power. Check for
the following:
• 1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / P
n
) < 3.0
• Where: P
n
= 1000 * 9909 MOTOR NOM POWER (if units are kW)
or P
n
= 746 * 9909 MOTOR NOM POWER (if units are HP, e.g. in US)
1006 EXT ROMISSING
Parameter values are inconsistent. Check for the following:
• Extension relay module not connected and
• 1410…1412 RELAY OUTPUTS 4…6 have non-zero values.
1007 PAR FBUSMISSING
Parameter values are inconsistent. Check for and correct:
A parameter is set for eldbus control (e.g. 1001 EXT1 COMMANDS = 10 (COMM)), but 9802 COMM PROT SEL =
0.
1008 PAR PFAWOSCALAR
Parameter values are inconsistent – 9904 MOTOR CTRL MODE must be = 3 (SCALAR: SPEED), when 8123 PFA
ENABLE is activated.
1009 PAR PCU1
Parameter values for power control are inconsistent: Improper motor nominal frequency or speed. Check for both of the
following:
• 1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16
• 0.8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ / Motor Poles) < 0.992
1010 PAR PFA OVERRIDE
Both the override mode and PFA are activated at the same time. These modes are mutually incompatible, because PFA
interlocks cannot be observed in the override mode.
1011 PAR OVERRIDE PARS
Override is enabled, but parameters are incompatible. Verify that 1701 is not zero, and (depending on 9904* value)
1702* or 1703* is not zero. *Not used with MicroTech III.
1012 PAR PFA IO 1
IO conguration is not complete – not enough relays are parameterized to PFA. Or, a conict exists between Group 14,
parameter 8117*, NR OF AUX MOT, and parameter 8118*, AUTOCHNG INTERV. *Not used with MicroTech III.
1013 PAR PFA IO 2
IO conguration is not complete – the actual number of PFA motors (parameter 8127, MOTORS) does not match the
PFA motors in Group 14* and parameter 8118* AUTOCHNG INTERV. *Not used with MicroTech III.
1014 PAR PFA IO 3
IO conguration is not complete – the drive is unable to allocate a digital input (interlock) for each PFA motor
(parameters 8120* INTERLOCKS and 8127* MOTORS). *Not used with MicroTech III.