Technical data
OM 1191 73
Fieldbus Adapter
Generic Prole Technical Data
Overview
Thegenericproleaimstofullltheindustry-standarddrive
proleforeachprotocol(e.g.PROFIdriveforPROFIBUS,
AC/DC Drive for DeviceNet).
Control Word
As described earlier in Control interface the CONTROL
WORD is the principal means for controlling the drive from a
eldbussystem.ForspecicCONTROLWORDcontent,see
the user’s manual provided with the FBA module.
Status Word
As described earlier in Control interface, the contents of the
STATUS WORD is status information, sent by the drive to
themasterstation.ForspecicSTATUSWORDcontent,see
the user’s manual provided with the FBA module.
Reference
As described earlier in Control interface, the REFERENCE
word is a speed or frequency reference.
NOTE: REF2 is not supported by the Generic Drive proles.
Reference Scaling
REFERENCEscalingiseldbustypespecic.However,at
thedrive,themeaningofa100%REFERENCEvalueisxed
as described in the table below. For a detailed description
on the range and scaling of the REFERENCE, see the user’s
manual supplied with the FBA module.
Table 52: Generic Prole
Reference Range Reference Type Scaling Remarks
REF Fieldbus specic
Speed
-100% = -(par. 9908)
0 = 0
+100 = (par. 9908)
Final reference limited by
1104/1105.
Actual motor speed limited by
2001/2002 (speed).
Frequency
-100% = -(par. 9907)
0 = 0
+100 = (par. 9907)
Final reference limited by
1104/1105.
Actual motor speed limited by
2007/2008 (frequency)
Actual Values
As described earlier in Control interface, Actual Values are
words containing drive values.
Actual Value Scaling
For Actual Values, scale the feedback integer using the
parameter’s resolution. (See Complete parameter descriptions
section for parameter resolutions.) For example:
Feedback
Integer
Parameter
Resolution
(Feedback Integer) × (Parameter
Resolution) = Scaled Value
1
0.1 mA
1 × 0.1 mA = 0.1 mA
10 0.1%
10 × 0.1% = 1%
Where parameters are in percent, the Complete parameter
descriptionssectionspecieswhatparametercorrespondsto
100%. In such cases, to convert from percent to engineering
units,multiplybythevalueoftheparameterthatdenes
100% and divide by 100%. For example:
Feedback
Integer
Parameter
Resolution
Value of the
Parameter
that denes
100%
(Feedback Integer) × (Parameter
Resolution) ×
(Value of 100% Ref.)
/ 100% = Scaled Value
10
0.1% 1500 rpm
1
10 × 0.1% × 1500 RPM / 100%
= 15 rpm
100
0.1% 500 Hz
2
100 × 0.1% × 500 Hz / 100% = 50 Hz
1. Assuming, for the sake of this example, that the Actual
Valueusesparameter9908MOTNOMSPEEDasthe
100%reference,andthat9908=1500rpm.
2. Assuming, for the sake of this example, that the Actual
Valueusesparameter9907MOTNOMFREQasthe
100%reference,andthat9907=500Hz.
Actual Value Mapping
See the user’s manual supplied with the FBA module.